Broan AI Series Use and care manual

B110H65RT B110H65RS
B130H65RT B130H65RS
B130E65RT B130E65RS
B150H75NT* B150H75NS*
B160H75RT B160H75RS
B160H65RT B160H65RS
B160E65RT B160E65RS
B150E75NT* B150E75NS*
B160E75RT B160E75RS
USER AND INSTALLER MANUAL
INSTALLER: READ THESE INSTRUCTIONS
SAVE THEM FOR USER
RESIDENTIAL USE ONLY
23832 REV. N
REGISTER YOUR PRODUCT ONLINE AT:
www.broan-nutone.com/en-us/home/customer-service/product-registration
For additional information, visit www.Broan-NuTone.com
FAULT INDICATOR DISPLAY REQUIREMENTS
*Recirculation mode is not offered on these
models.
Broan-NuTone LLC, 926 West State Street, Hartford, Wisconsin, USA 53027 Broan-NuTone.com 800-558-1711

2
Please take note that this manual uses the following symbols to emphasize particular information:
Identies an instruction which, if not followed, might cause serious personal injuries including possibility of death.
CAUTION
Denotes an instruction which, if not followed, may severely damage the unit and/or its components.
NOTE: Indicates supplementary information needed to fully complete an instruction.
LIMITATION
For residential (domestic) installation only. Installation work and electrical wiring must be done by a qualied person in accordance with
all applicable codes and standards, including re-rated construction codes and standards.
⚠WARNING
TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK, OR INJURY TO PERSON(S) OBSERVE THE FOLLOWING:
1. Use this unit only in the manner intended by the manufacturer.
2. Before servicing or cleaning this unit, disconnect power cord from electrical outlet.
3. This unit is not designed to provide combustion and/or dilution air for fuel-burning appliances.
4. When cutting or drilling into a wall or ceiling, do not damage electrical wiring and other hidden utilities.
5. Do not use this unit with any solid-state speed control device other than those specied in section 3.1.
6. This unit must be grounded. The power supply cord has a 3-prong grounding plug for your personal safety. It must be plugged into
a mating 3-prong grounding receptacle, grounded in accordance with the national electrical code and local codes and ordinances.
Do not remove the ground prong. Do not use an extension cord.
7. Do not install in a cooking area or connect directly to any appliances.
8. Do not use to exhaust hazardous or explosive materials and vapors.
9. When performing installation, servicing or cleaning this unit, it is recommended to wear safety glasses and gloves.
10. When applicable local regulation comprises more restrictive installation and/or certication requirements, the aforementioned
requirements prevail on those of this document and the installer agrees to conform to these at his own expense.
CAUTION
1. To avoid prematurely clogged lters, turn the unit OFF during construction or renovation.
2. Please read specication label on product for further information and requirements.
3. Be sure to duct air outside – Do not intake/exhaust air into spaces within walls or ceiling or into attics, crawl spaces, or garage. Do
not attempt to recover the exhaust air from a dryer or a range hood.
4. Intended for residential installation only in accordance with the requirements of NFPA 90B (for a unit installed in U.S.A.) or Part 9 of
the National Building Code of Canada (for a unit installed in Canada).
5. Do not run any air ducts directly above or within 2 ft. of a furnace or its supply plenum, boiler, or other heat producing appliance. If
a duct has to be connected to the furnace return plenum, it must be connected 10 ft. away from plenum connection to the furnace.
6. The ductwork is intended to be installed in compliance with all applicable local and national codes.
7. When leaving the house for a long period of time (more than two weeks), a responsible person should regularly check if the unit
operates adequately.
8. If the ductwork passes through an unconditioned space (e.g.: attic), the unit must operate continuously except when performing
maintenance and/or repair. Also, the ambient temperature of the house should never drop below 65°F (18°C).
9. At least once a year, the unit mechanical and electronic parts should be inspected by qualied service personnel.
10. Do not use your unit during construction or renovation of your house or when sanding drywall. Certain types of dust and vapors may
damage your system.
11. Make sure at all times that the outside intake and exhaust hoods are free from any snow during the winter season. It is important to
check your unit during a big snow storm, so it doesn’t draw in any snow. If this is the case, please turn the unit OFF for a few hours.
12. Since the electronic control system of the unit uses a microprocessor, it may not operate correctly because of external noise or very
short power failure. If this happens, unplug the unit and wait approximately 10 seconds. Then, plug the unit in again.
13. Do not make excessive use of fragrance appliances or chemicals since some may damage the unit components material.
WARNING
!

3
TABLE OF CONTENTS
1. TECHNICAL DATA ...............................................................................................................4
1.1 AIR DISTRIBUTION (NORMAL OPERATION) .............................................................................................4
2. INSTALLATION....................................................................................................................4
2.1 LOCATING AND MOUNTING THE UNIT .....................................................................................................4
2.2 INSTALLING THE DUCTWORK AND THE REGISTERS.............................................................................6
2.2.1 FULLY DUCTED SYSTEM (T-1) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.)............................6
2.2.2 EXHAUST DUCTED SYSTEM (T-2) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.) .......................6
2.2.3 SIMPLIFIED INSTALLATION (T-4) (THIS CONFIGURATION DOES NOT ALLOW RECIRCULATION MODE TO OPERATE.) ..............7
2.3 CONNECTING THE DRAIN (HRV ONLY)....................................................................................................8
2.4 INSTALLING DUAL EXTERIOR HOOD USING TANDEM®TRANSITION KIT (OPTIONAL) .......................8
2.5 INSTALLING THE EXTERIOR HOODS .......................................................................................................9
2.6 CONNECTING THE DUCTS TO THE UNIT.................................................................................................9
2.6.1 DUCTS CONNECTION ................................................................................................................................. 10
3. CONNECTIONS.................................................................................................................11
3.1 ELECTRICAL CONNECTION TO OPTIONAL MAIN WALL CONTROL .................................................... 11
3.1.1 ELECTRICAL CONNECTION TO SPEED, DEHUMIDISTAT OR AUTOMATIC OPTIONAL MAIN WALL CONTROL ..................... 11
3.1.2 ELECTRICAL CONNECTION TO ADVANCED OPTIONAL MAIN WALL CONTROL.......................................................... 11
3.2 ELECTRICAL CONNECTION TO OPTIONAL AUXILIARY WALL CONTROL ........................................... 12
3.2.1 ELECTRICAL CONNECTION TO 20-40-60 OPTIONAL AUXILIARY WALL CONTROL................................................... 12
3.2.2 ELECTRICAL CONNECTION TO DRY CONTACT OPTIONAL AUXILIARY WALL CONTROL (E.G. CRANK TIMER)................. 12
3.3 CONNECTION TO THE CENTRAL FORCED-AIR SYSTEM .....................................................................13
3.3.1 UNIT OPERATION USING ADRY CONTACT CONNECTION................................................................................... 13
3.3.2 UNIT INTERCONNECTION WITH CENTRAL FORCED-AIR SYSTEM (R/C/G/GF)....................................................... 13
3.3.3 SYNCHRONIZATION WITH CENTRAL FORCED-AIR SYSTEM FUNCTION................................................................... 13
4. WIRING DIAGRAM ............................................................................................................14
5. NAVIGATION ON LCD SCREEN.......................................................................................15
5.1 LCD SCREEN ............................................................................................................................................ 16
5.2 UNIT FIRST BOOT.....................................................................................................................................16
5.3 SETTINGS MODIFICATION....................................................................................................................... 16
5.3.1 PROCEDURE TO MODIFY MIN CFM SETTING.................................................................................................... 16
5.3.2 PROCEDURE TO MODIFY MAX CFM SETTING................................................................................................... 16
5.3.3 PROCEDURE TO MODIFY OPTIONS SETTING................................................................................................... 16
5.3.4 PROCEDURE TO MODIFY INDEPENDENT AIRFLOWS SETTING.............................................................................. 16
5.4 FACTORY SETTINGS RESET ...................................................................................................................17
6. USING THIS UNIT..............................................................................................................17
6.1 YOUR VENTILATION SYSTEM .................................................................................................................. 17
6.2 INTEGRATED CONTROL ..........................................................................................................................17
6.3 AHU MODE DISPLAY ................................................................................................................................ 17
7. SERVICE PARTS................................................................................................................18
8. INSTALLER’S TROUBLESHOOTING ...............................................................................20
9. MAINTENANCE.................................................................................................................23
9.1 QUARTERLY ..............................................................................................................................................23
9.2 ANNUAL (AT FALL) ....................................................................................................................................24
10. USER’S TROUBLESHOOTING .......................................................................................24
11. WARRANTY......................................................................................................................25

4
1. TECHNICAL DATA
1.1 AIR DISTRIBUTION (NORMAL OPERATION)
VF0077
NOTE: The dimensions, performance charts, defrost cycle tables and specications are listed on the specication sheets of the unit.
Visit our website at www.Broan-NuTone.com.
2. INSTALLATION
2.1 LOCATING AND MOUNTING THE UNIT
The wearing of safety glasses and gloves is recommended when installing, maintaining or cleaning the unit to reduce the risk of injury
that could be caused by the presence of thin metal and/or high moving parts.
WARNING
!
Stale
air from
building Stale
air from
building
Stale air to
outdoors
Stale air to
outdoors
Fresh
air from
outdoors
Fresh
air from
outdoors
Fresh air to
building Fresh air to
building
Choose an appropriate location for the unit:
• Within an area of the house where the ambient temperature is kept between 50°F and 149°F;
• Away from living areas (dining room, living room, bedroom), if possible;
• So as to provide easy access to the interior cabinet for maintenance, and to the control panel on the side of the unit;
• Close to an exterior wall, so as to limit the length of the insulated exible ducts to and from the unit;
• HRV units only: close to a drain. If no drain is close by, use a pail to collect run-off;
• Away from hot chimneys, electrical panel and other re hazards;
• Within 6 feet of a power source (standard outlet).
Consumer Information
A. To ensure quiet operation of the H/ERV, each product model must be installed using sound attenuation techniques appropriate for
the installation.
B. The way your heat/energy-recovery ventilator is installed can make a signicant difference to the electrical energy you use. To
minimize the electricity use of the heat/energy-recovery ventilator, a stand-alone fully ducted installation is recommended. If you
choose a simplied installation that operates your furnace air handler for room-to-room ventilation, an electrically efcient furnace that
has an electronically commutated (EC) variable speed blower motor will minimize your electrical energy consumption and operating
cost.
C. Installation of a user-accessible control with your product model will improve comfort and may signicantly reduce the product
model’s energy use.
CAUTION
Make sure that no piece of mineral wool will enter in the unit during installation. Otherwise, this could reduce airow and generate
vibrations and noise in the unit.

5
VD0488
Wall mounted:
• Choose the appropriate location(s) for the mounting brackets
(see illustration below) according to stud(s) position.
• Insert the provided brackets under the unit frame (see illustration
hereafter).
• Fix the bracket using the screw no. 8 x 3/8".
• Using the 4 no. 8 x 1½" screws provided, secure the unit to the
wall making sure that the 4 screws engage into a stud.
• Always make sure that the unit is no more than 1/4" off level.
VD0486
VD0485
Suspended to the joists or trusts:
• Slightly bend the brackets on the unit to insert the provided
chains.
• Hang the unit to the joists (or trusts) using the chains. Springs are
not required.
• Always make sure that the unit is no more than 1/4" off level.
OR
VD0487
INSTALLATION WITH 2 BRACKETS INSTALLATION WITH 4 BRACKETS
2.1 LOCATING AND MOUNTING THE UNIT (CONT.)

6
VH0165
A
B
STALE AIR FROM BUILDING:
• Install registers in areas where contaminants and humidity are
produced: kitchen, bathrooms, laundry room, etc.
• Install registers on an interior wall, 6 to 12 inches away from the
ceiling OR in the ceiling.
• Install the kitchen register at least 4 feet away from the range.
• Bathroom fans and range hoods can be used to better exhaust stale
air.
• Homes with more than one level require at least one exhaust register
at the highest level.
FRESH AIR TO BUILDING:
• Install registers in bedrooms, dining room, living room and
basement.
• Install registers in the ceiling OR high on the walls with the airow
directed towards the ceiling.
• If a register must be installed in the oor, direct the airow up the
wall.
2.2.1 FULLY DUCTED SYSTEM (T-1) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.)
2.2 INSTALLING THE DUCTWORK AND THE REGISTERS
Never install a stale air exhaust register in a room where there is a combustion device, such as a furnace, gas water heater, replace or
any appliance or equipment that can generate gaseous contaminants, or pollutants. The negative pressure this could create in the room
may impair proper evacuation of the gas or pollutants, which may have severe health consequences.
WARNING
!
STALE AIR FROM BUILDING:
Same as for Fully Ducted System, described on point 2.2.1.
FRESH AIR TO BUILDING:
• Connect the fresh air distribution duct of the unit to the central forced-
air system return duct at least 10 feet away from the central forced-air
system (A+B)*.
*This 10-ft. distance applies only in areas where the outside temperature
falls below the freezing point (32°F).
NOTE: The central forced-air system blower operation can be synchronized
with the unit (see section 3.3). It is recommended, but not essential that the
central forced-air system blower runs when the unit is in operation.
2.2.2 EXHAUST DUCTED SYSTEM (T-2) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO OPERATE.)
Duct connection to the central forced-air system can be regulated by some codes and standards. It is your responsibility to consider and
comply with your local requirements to avoid any non-compliance.
WARNING
!
NOTE: For this type of conguration, the T-1 option must be selected on the LCD screen when auto-balancing the unit (see section 5.2).
NOTE: For this type of conguration, the T-2 option must be selected
on the LCD screen when auto-balancing the unit (see section 5.2).
A+B= MIN 10’
Stale air from building
(e.g. bathroom)
Fresh air to
building
Stale air to
outdoors
Fresh air from
outdoors
If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts to prevent condensation formation inside
and outside ducts, which could cause material damage and/or mold growth. Moreover, if fresh air to building duct and/or stale air
from building duct goes/go through an unconditioned space, the unit must be set to operate continuously in cold conditions (below
10°C/50°F). Continuous air movement inside ducts will prevent condensation formation. The unit can be stopped temporarily for
maintenance and/or repair purposes in such conditions.
CAUTION

7
2.2.3 SIMPLIFIED INSTALLATION (T-4) (THIS CONFIGURATION DOES NOT ALLOW RECIRCULATION MODE TO OPERATE.)
The central forced-air system must be synchronized with the unit since fresh air evacuation and distribution come from the same section.
The central forced-air system must operate to avoid fresh air to be directly drawn by the evacuation, which would reduce signicantly
fresh air supply to the building. See section 3.3 for ducting.
CAUTION
Duct connection to the central forced-air system can be regulated by some codes and standards. It is your responsibility to consider and
comply with your local requirements to avoid any non-compliance.
WARNING
!
VH0168
Fresh air and exhaust air ow through the central forced-air system ducts,
which simplies the installation.
The use of bathroom fans and a range hood is suggested to exhaust stale
air.
STALE AIR FROM BUILDING:
Connect the stale air intake port of the unit to the central forced-air
system return duct at least 3 feet ahead of the fresh air distribution from
the unit.
FRESH AIR TO BUILDING:
Connect the fresh air distribution duct of the unit to the central forced-
air system return duct at least 10 feet away from the central forced-air
system (A+B)*.
*This 10-ft. distance applies only in areas where the outside temperature
falls below the freezing point (32°F).
VH0167
C
B
A
A+B= MIN 10’
C=3’
ALTERNATE INSTALLATION (T-5) (THIS CONFIGURATION DOES NOT ALLOW RECIRCULATION
MODE TO OPERATE.)
Unit should be synchronized with central forced-air system operation
to avoid condensation and mold growth in central forced-air system
distribution ducting if cooling mode of central forced-air system is used.
Fresh air to
building
Stale air from
building
Stale air to
outdoors
Fresh air from
outdoors
This conguration is not recommended with high velocity central forced-
air system. High pressures produced by these systems could affect unit
proper operation and generate errors.
CAUTION
NOTE: For this type of conguration, the T-5 option must be
selected on the LCD screen when auto-balancing the unit (see section 5.2).
Stale air to
outdoors
Fresh air from
outdoors
Fresh air to
building
Stale air from
building
NOTE: For this type of conguration, the T-4 option must be
selected on the LCD screen when auto-balancing the unit (see section 5.2).
VH0166
ALTERNATE INSTALLATION (T-3) (THIS CONFIGURATION ALLOWS RECIRCULATION MODE TO
OPERATE.)
Unit should be synchronized with central forced-air system operation
to avoid condensation and mold growth in central forced-air system
distribution ducting if cooling mode of central forced-air system is used.
This conguration is not recommended with high velocity central forced-
air system. High pressures produced by these systems could affect unit
proper operation and generate errors.
CAUTION
NOTE: For this type of conguration, the T-3 option must be selected
on the LCD screen when auto-balancing the unit (see section 5.2).
Stale air from building
(e.g. bathroom)
Fresh air to
building
Stale air to
outdoors
Fresh air from
outdoors

8
2.3 CONNECTING THE DRAIN (HRV ONLY)
Install the drain hose included and run it to a drain or a pail. This unit may generate a large amount of water in cooler weather. It is
necessary to install the drain hose properly to prevent water damage and/or material damage.
CAUTION
• Cut the appropriate length of drain tubing (see illustrations below).
• Connect the tubing to the provided adaptor.
• Make a water trap loop in the tube to prevent the unit from drawing unpleasant odors from the drain source.
• Add water in the loop to prevent noise or hiss.
• Make sure there is a distance of at least 2" between the unit and the tubing loop (see illustration below).
• Using the tie wrap provided, attach the tubing as illustrated below.
• Run the tube to the oor drain or to an alternate drain pipe or pail.
• IMPORTANT: If using a pail to collect water, place the tube end approximately 1” inside the pail in order to prevent water from being
drawn back up into the unit.
VO0290A
13"
(330 mm)
13"
(330 mm)
VO0083
± 1”
TIE WRAP
≥ 2”
2.4 INSTALLING DUAL EXTERIOR HOOD USING TANDEM®TRANSITION KIT (OPTIONAL)
For units set at 110 CFM or less, a Tandem transition kit can be used instead of 2 exterior hoods;
but take into account this device will generate approximately an additional 0.2 in w.g. static pressure
depending on the installation.
The minimum joist opening needed to install the Tandem®transition is 9¾”. The maximum height of
the Tandem transition is 8¾”.
To connect the insulated exible ducts to the Tandem transition (Exhaust air to outdoors and Fresh air
from outdoors), follow the instructions included with the Tandem transition kit (part no.VTYIK1).
VR0003

9
TRANSITIONING TO 6-IN. DUCTS (FOR 110, 130 AND 150 CFM UNITS ONLY)
If using 6-in. ducts, install 5-in. to 6-in. transitions on the ports, and secure using duct tape only. If rigid ducting is used, install a 12-in.
section of exible duct between the transition and the rigid ducting (see above).
RIGID DUCTS
To prevent potential water leakage in cold side rigid ducting insulation, seal all rigid ducting joints with duct tape.
To avoid transmission of vibrations, always use a 12-inch section of exible duct to connect rigid ducts to the unit. To connect insulated
rigid ducts to the unit (cold side) using insulated exible ducts, follow instructions in section 2.5. To connect regular rigid ducts (warm
side) to the unit using non-insulated exible ducts, use a tie wrap.
2.6 CONNECTING THE DUCTS TO THE UNIT
INSULATED FLEXIBLE DUCTS
Use the following procedure to connect the insulated exible ducts to the ports of the unit (exhaust to outside and fresh air from outside).
1. Expose the exible duct by pulling back the insulation, and place it over the inner port ring.
2. Attach the exible duct to the port using a tie wrap.
3. Seal the joint using duct tape.
4. Pull the insulation and vapor barrier over the joint, tuck them between the inner and outer rings of the double collar and fasten them
in place using duct tape.
V
J0157
• If ducts have to go through an unconditioned space (e.g.: attic), always use insulated ducts to prevent condensation formation inside
and outside ducts, which could cause material damage and/or mold growth.
• Do not use screws to connect the ducts or transitions to the ports so as not to interfere with ports inner dampers operation. A
non-functioning damper could freeze the unit, which could cause damages.
CAUTION
The vapor barrier should remain intact and free of cracks or openings. An opening could produce condensation inside or outside duct,
which could cause material damage and/or mold growth in the long run.
CAUTION
2.5 INSTALLING THE EXTERIOR HOODS
To avoid cross-contamination:
• Keep at least 10 feet between both hoods OR use approved combined hoods
model VTYIK1.
• Install hood(s) at least at 18 inches away from the ground OR depth of expected
snow accumulation, whichever is greater.
Refer to illustration at right for proper connection method of the insulated ducts
to the hoods. An “Anti-Gust Intake Hood” should be installed in regions where a
lot of snow is expected to fall.
VD0028
EXHAUST
HOOD
INTAKE
HOOD
18”
18”
6” ø
10’
6’
18”
OPTIONAL
DUCT LOCATION
TAPE AND DUCT TIE
CAULKING
Make sure intake hood is at least 6 feet (1.8 m) away from any of the following:
• Dryer exhaust, high efciency central forced-air system vent, central vacuum
vent
• Gas meter exhaust, gas barbecue-grill
• Any exhaust from a combustion source
• Garbage bin and any other source of contamination.
Ignoring these recommendations could signicantly degrade the quality of the
incoming air which, in some cases, could result in health consequences.
In the event of a conict between our conditions and local requirements, the
latter will have priority.
WARNING
!
NOTE: It is recommended to use 6"ducting instead of 5"ducting for 150H75NT, 150H75NS, 150E75NT and 150E75NS units if
required airow is over 130 CFM. It will prevent having too high static pressure in the ducting.

10
2.6.1 DUCTS CONNECTION
VD0489
CORRECT INSTALLATION
VD0490
INCORRECT INSTALLATION
IMPORTANT: Make sure to connect ducting as illustrated below to get airows reading accuracy. Correct installation will also allow
proper drainage of water that may accumulate in ducting.
Insulated ducts must have the same diameter as the ports to ensure proper drainage of water that may accumulate in ducts.
CAUTION
Ducting must not be too crushed. Otherwise, airows reading accuracy will be affected.
CAUTION
R = 3"minimum
NOTE: Route ducts as straight as possible, minimize the number of elbows and design and install ducts in accordance with
ACCA’s Manual D.

11
3. CONNECTIONS
3.1 ELECTRICAL CONNECTION TO OPTIONAL MAIN WALL CONTROL
Use the terminal connector included to perform the electrical connection for optional main wall control. Check if all wires are correctly
inserted in their corresponding holes in the terminal connector. Use screws to x wires in the terminal connector.
3.1.1 ELECTRICAL CONNECTION TO SPEED, DEHUMIDISTAT OR AUTOMATIC OPTIONAL MAIN WALL CONTROL
Gnd
D+
12V
D-
VC0241
12V
D-
D+
Gnd
Once the wall control connections have been made, insert the terminal connector in the electrical compartment.
NOTE : For information about the operation of the wall control, refer to the corresponding Installation and User Guide, available at
www.Broan-NuTone.com.
Always disconnect the unit before making any connections. Failure to cut power could result in electrical shock or damage to the wall
control or electronic module inside the unit.
Never install more than one optional main wall control per unit. Make sure that the wires do not short-circuit between themselves or by
touching any other components on the wall control. Avoid poor wiring connections. To reduce the risk of electrical interference (noise),
do not run wall control wiring next to control contactors or near light dimming circuits, electrical motors, dwelling/building power or
lighting wiring or power distribution panel.
CAUTION
WARNING
!
HD0491
UNIT BOTTOM VIEW
TERMINAL CONNECTOR
3.1.2 ELECTRICAL CONNECTION TO ADVANCED OPTIONAL MAIN WALL CONTROL
12V D- D+ Gnd
VC0242
12V D- D+ Gnd

12
3. CONNECTIONS (CONT’D)
3.2 ELECTRICAL CONNECTION TO OPTIONAL AUXILIARY WALL CONTROL
3.2.1 ELECTRICAL CONNECTION TO 20-40-60 OPTIONAL AUXILIARY WALL CONTROL
Gnd
OVR
12V
LED
VC0243
Gnd
OVR
12V
LED
When congurating OVR option on the LCD screen, choose among these 3 congurations: BAL (the unit remains balanced while
providing maximum airow), PER (the unit is slightly unbalanced since the distribution motor is in MAX speed while allowing maximum
exhaust ventilation) and DIS (the unit is unbalanced since air distribution is constant despite a higher need in exhaust ventilation).
NOTE : The auxiliary wall control can be used with a 3-wire connection by removing the LED signals. This optional wiring will not allow an
installation with more than 1 auxiliary wall control to properly synchronize their LEDs on an event requested from a peer. Only the
auxiliary wall control having requested the timer event will have the LEDs updated accordingly.
3.2.2 ELECTRICAL CONNECTION TO DRY CONTACT OPTIONAL AUXILIARY WALL CONTROL (E.G. CRANK TIMER)
Crank Timer
or
Any Dry Contact
12VOVR
VC0256
A miswiring that sends a 24 VAC signal to the 6-position terminal block (OVR, LED, 12V, D-, D+, GND) could permanently damage the
control circuit. Verify carefully wire connections before powering-up the unit.
WARNING
!

13
3.3.2 UNIT INTERCONNECTION WITH CENTRAL FORCED-AIR SYSTEM (R/C/G/GF)
These connections must be done if you want the unit to force the central forced-air system blower operation when ventilating (refer to
solid lines in above diagram).
NOTE : These connections are required for installation conguration T-4. Refer to section 2.2 for more details.
3.3.3 SYNCHRONIZATION WITH CENTRAL FORCED-AIR SYSTEM FUNCTION
The Virtuo technology allows synchronizing the unit operation with the central forced-air system operating time. It prevents unnecessary
central forced-air system operating time while providing a better air distribution.
To use this function, W and Y connections must be added to R and C connections to inform the unit that the central forced-air system is
running (refer to dotted lines in above diagram).
Air Exchanger PCB
Terminal Blocks
Y
W
C
G
R
Y W G R C
Central Forced-Air System Thermostat
Wiring Options with Central Forced-Air System
Vent
Y
W
C
Gf
G
R
J13
Internal
Logic Optional Wiring for Synchronization
Never connect a 120-volt AC circuit to the terminals of the central forced-air system interlock (standard wiring). Only use the low voltage
class 2 circuit of the central forced-air system blower control. The unit is designed for low voltages only. Connecting the unit on 120-volt
circuit would damage it instantly.
WARNING
!
3.3 CONNECTION TO THE CENTRAL FORCED-AIR SYSTEM
3.3.1 UNIT OPERATION USING ADRY CONTACT CONNECTION
This unit can be controlled by any dry contact connection such as the thermostat equipped with an optional ventilation output.
Y
W
C
G
R
Y W G R C Acc+ Acc-
Central Forced-Air System Thermostat
Central Forced-Air System
Wiring for Dry Contact Connection
1
1- External switch or any Dry-contact can be used to
activate Vent input if not available on the Thermostat
Air Exchanger
Terminal Blocks
Alternate Wiring for Dry Contact Independent Installation
Vent
Y
W
C
Gf
G
R
J13
OVR
LED
12V
D-
D+
GND
J9
External Switch or any
alternate Dry-Contact
Air Exchanger
Terminal Blocks
Vent
Y
W
C
Gf
G
R
J13
OVR
LED
12V
D-
D+
GND
J9
Note : Synchronization with a central forced-air system
with W and Y is not available with this configuration.
1 - External switch or any dry contact can be used to activate vent input if not
available on the thermostat. Some thermostats offer a single wire 24VAC output
for accessory ventilation. It can be directly connected to vent input and therefore
the Acc- / R connection is not required.
Once wired, unit will toggle between the
Standby mode when contact is opened and
the selected mode when contact is closed.
Choose among these 4 congurations:
minimum (unit operating in MIN speed),
intermittent (unit operating in MIN speed
20 min/hr then as per INT conguration
selection for 40 min), auto* (unit operating
according to outdoor temperature) and
maximum (unit operating in MAX speed)
in DRY option on the LCD screen when the
VENT contact is activated. Refer to section 5
for more details.
* In auto mode, the unit will operate as
follows:
• Less than -13°F = 10 min/hr
• -13°F to 19°F = 20 min/hr
• 19°F to 50°F = 40 min/hr
• 50°F to 77°F = MIN speed
• 77°F to 82°F = 30 min/hr
• 82°F to 91°F = 20 min/hr
• Above 91°F = 10 min/hr
NOTE : This dry contact option will override the main wall control so we do not recommend
the use of a wall control with this type of connection.
NOTE : Following ducting installation conguration and temperature conditions, it may be
necessary for the unit to operate continuously. Refer to section 2.2 for more details.

14
4. WIRING DIAGRAM
BLK
BLK
GRN
LOGIC DIAGRAM
WIRING COLOR CODE
BLK BLACK
BLU BLUE
GRNGREEN
RED RED
WHT WHITE
Linevoltage factory wiring
Low voltage factory wiring
Low voltage field wiring
(Exhaust)
BLU
RED
120VAC
60Hz
W1
GRN
F1
1
Power
LED
J1
M2
Damper Stepper Motors
Y
M1
WHT
BLK
A1
MAIN ELECTRONIC
ASSEMBLY
M1
Power
Supply
(15VDC)
Line
Neutral
K1
G
Gf
AC
Line
Filter
J1-2
F1
High Voltage
(120VAC)
J1-1
To J
2
MCU
K1
M3
Stepper
Driver
ToJ5
WIRING DIAGRAM
BDM
1
5A/125VAC
J2J
3J5 J6 J7
111
11
J7a
J
15a
1
A2
LCD
ASSEMBLY
GRN
Ventilation Fan Motors
BLU
RED
M2
M3 M4
(Supply )
(Supply)
* Optional
(Recirc)(Exhaust)
MCU
Serial Number
Isolation
Transformer
Motor Fuses
F2
F3
F4
F5
VWGf
CGR
*Optional Central Forced-Air System Wiring
(Isolated 24VAC )
OVR
LED
12V
D-
D+
GND
Main and Auxilliary
Controls Wiring
Thermistor
R1
RT
1
(NTC)
Bridge IPM
Motor 1
IPM
Motor 1
F3
F2
M2
To J
3
F5
F4
Central
Forced-Air
System
Relay
K1
PTC3
Isolated
Supply
(12VDC)
Isolated
Supply
(3.3VDC
)
J9 J1 3
Logic
Supply
(3.3VDC)
PTC2
ToJ9
Logic
Supply
(12VDC)
M4
Stepper
Driver
To J
6
M5
Stepper
Driver
ToJ7
PTC6
PTC4
ToJ13
RTH1
To J
7a
(R1)
LCD
Assembly
Isolated GND
Digital GND
ToJ15a
(A2)
Recirculation
Damper(J6 ) is
not present for
allmodels
J1 4
VE0452A
WARNING
• Risk of electric shocks. Before performing any maintenance or servicing, always disconnect the unit from its power source.
• This product is equipped with an overload protection (fuse). A blown fuse indicates an overload or a short-circuit situation. If the fuse blows, unplug the
product from the outlet. Discontinue using the unit and contact technical support.
!

15
5. NAVIGATION ON LCD SCREEN
+
-
OK
VD0492
OK button To conrm a selection.
+button To increase a value.
To scroll up in a selection.
-button To decrease a value.
To scroll down in a selection.
VQ0211
VQ0209
VQ0210
VQ0203
VQ0212
Indicates current
mode
Indicates
fresh airow
PRESS ON OK BUTTON TO
CHANGE THE OPERATING MODE.
USE +BUTTON OR -BUTTON
TO SELECT THE DESIRED
OPERATING MODE.
+
-
PRESS ON OK BUTTON TO
CONFIRM THE OPERATING
MODE SELECTION.
VQ0205 VQ0207 VQ0201
Indicates
stale airow
+
+
-
-
+
-
+
-
PRESS ON +BUTTON OR - BUTTON TO MODIFY MAX CFM, MIN CFM OR OPTIONS CONFIGURATION.
PRESS ON OK BUTTON DURING 4
SECONDS TO MODIFY MAX CFM
CONFIGURATION.
MAX CFM DATA WILL FLASH.
USE +BUTTON TO INCREASE
VALUE OR -BUTTON TO
DECREASE VALUE.
PRESS ON OK BUTTON TO
CONFIRM VALUE.
PRESS ON OK BUTTON DURING 4
SECONDS TO MODIFY MIN CFM
CONFIGURATION.
MIN CFM DATA WILL FLASH.
USE +BUTTON TO INCREASE
VALUE OR -BUTTON TO
DECREASE VALUE.
PRESS ON OK BUTTON TO
CONFIRM VALUE.
PRESS ON OK BUTTON DURING 4
SECONDS TO MODIFY OPTIONS
CONFIGURATION.
VQ0197
VQ0202
VQ0199
VQ0198
VQ0200
FOR EACH
OPTION
CONFIGURATION,
USE +BUTTON
TO SCROLL UP
IN OPTIONS
AVAILABLE OR
-BUTTON TO
SCROLL DOWN
IN OPTIONS
AVAILABLE.
ONCE OPTION
SELECTION IS
DONE, PRESS
OK BUTTON
TO CONFIRM
SELECTION. THE
NEXT OPTION
CONFIGURATION
WILL THEN
DISPLAY.
VQ0213
+
-
PRESS ON OK BUTTON DURING
4 SECONDS TO ACCESS
COMPLEMENTARY INFORMATION.
VQ0214
VQ0215
VQ0216
+
+
-
-
DISPLAYS ELECTRICAL
POWER CONSUMPTION.
DISPLAYS UNIT
% RUNNING
TIME (PER HOUR)
FOR SELECTED
OPERATING MODE.
DISPLAYS UNIT
AIRFLOWS.
PRESS ON OK BUTTON TO
EXIT COMPLEMENTARY
INFORMATION.
NOTE : According to unit model and conguration, some menus may not be available.
In the example above, the unit provides
114 CFM with a power consumption of
110 W during 50% of the hour. The net
airow is 57 CFM (50% X 114), the net
power consumption is about 55 W
(50% X 110).

16
5.3 SETTINGS MODIFICATION
5.3.1 PROCEDURE TO MODIFY MIN CFM SETTING
• Go to MIN using (+/-) then press on the OK button for 4 seconds.
• Use (+/-) to increase/decrease CFM and OK to conrm.
5.3.2 PROCEDURE TO MODIFY MAX CFM SETTING
• Go to MAX using (+/-) then press on the OK button for 4 seconds.
• Use (+/-) to increase/decrease CFM and OK to conrm.
5.3.3 PROCEDURE TO MODIFY OPTIONS SETTING
• Go to CFG OPT using (+/-) then press on the OK button for 4 seconds.
5.3.4 PROCEDURE TO MODIFY INDEPENDENT AIRFLOWS SETTING
• Press simultaneously (+/-) buttons for 4 seconds.
5.2 UNIT FIRST BOOT
PREPARATION
Follow these steps to ensure accurate measurements:
• Seal all the ductwork with tape. Close all windows and doors.
• Turn off all exhaust devices such as range hood, dryer and bathroom fans.
• If the installation is in any way connected to a ductwork of a central forced-air system, make sure that the central forced-air system
blower is ON. If not, leave central forced-air system blower OFF.
AUTO-BALANCING PROCEDURE
• Plug the unit and wait for the maximum CFM to display on the LCD screen. If unit is colder than ambient temperature, it is normal to
experience a 60 s longer boot-up since motors have to preheat.
• The maximum CFM will display on the LCD screen. Use (+/-) to adjust the CFM and OK to conrm.
• The minimum CFM will display on the LCD screen. Use (+/-) to adjust the CFM and OK to conrm.
• The house that ashes on the LCD screen indicates which side currently limits the airow (supply or exhaust). If the airow reached is
not sufcient, the installer can improve the installation to increase airow.
INSTALLATION CONFIGURATION SELECTION
• INS will display on the LCD screen. Choose among T-1, T-2, T-3, T-4 or T-5 following the installation conguration (Refer to section
2.2 for more details).
• Auto-balancing is completed.
5.1 LCD SCREEN
DISPLAY DEFINITION
STB Standby mode
MED MED speed
INT Intermittent mode
REC Recirculation mode
(Min, Med or Max speed)
AUT AUTO mode
SMT SMART mode
OVR 20 Override 20 min
OVR 40 Override 40 min
V
Q0
217
VQ0218
VQ0219 VQ0220
+
+
-
-
OK
OK
OK
+WHEN MAX DISPLAYS, PRESS ON
+BUTTON TO EXIT INDEPENDENT
AIRFLOWS SETTING.
SUPPLY AIRFLOW VALUE WILL FLASH.
PRESS ON +BUTTON OR - BUTTON TO
INCREASE/DECREASE VALUE.
PRESS OK BUTTON.
EXHAUST AIRFLOW VALUE WILL FLASH.
PRESS ON +BUTTON OR - BUTTON TO
INCREASE/DECREASE VALUE.
PRESS OK BUTTON.
DISPLAY DEFINITION
OVR 60 Override 60 min
OVR CNT Override by dry contact
AHU Refer to section 6.3 for explanation
HUM Humidistat or Dehumidistat override
TUR Turbo mode
OTH Away mode or Scheduling mode
DEF Defrost mode
EXX or WXX
(XX referring to error or warning number)
Refer to section 8 for each error/warning
explanation

17
6. USING THIS UNIT
This balanced ventilation unit is designed to provide fresh air to your home while exhausting stale, humid air. Thanks to its energy/heat
recovery module, the unit recovers a large proportion of heat or energy that is part of indoor or outdoor air according to the seasons to
improve comfort and energy efciency during the heating and the cooling periods. With the Virtuo Air TechnologyTM, this unit responds
to the variations in its environment in an autonomous way, ensuring to provide a proper level of ventilation and air quality. This unit also
features automatic modes (AUTO or SMART) that manage autonomously the required ventilation level as per indoor and/or outdoor
conditions. In colder areas, the unit will perform, at intervals, recovery module discreet defrost to maintain performance and comfort.
6.1 YOUR VENTILATION SYSTEM
6.2 INTEGRATED CONTROL
All units are equipped with an integrated control, located in front of the electrical compartment. For more convenience, these units can
be controlled using an optional wall control or the central forced-air system thermostat equipped with external fan activation.
+
-
OK
VD0492
MODE SELECTION
1. To change the mode, use (+/-) to access the Mode screen. Press OK to edit the mode
and use (+/-) to change the mode (Standby, Min, Max).
2. Press OK to conrm selection. The airows will be displayed for both MIN and MAX
modes.
NOTE: If an optional auxiliary wall control or the central forced-air system thermostat
equipped with external fan activation is used, it overrides the integrated control.
6.3 AHU MODE DISPLAY
Depending on unit conguration and/or installation, the unit could not be able to reach desired minimum CFM. This situation could
happen with congurations T-2 to T-5. In such a case, AHUXX (XX referring to desired minimum CFM value) will display on LCD screen.
In AHU mode, the unit operates in intermittent mode to reach desired minimum CFM value. Intermittent mode duration varies as per
desired minimum CFM value.
5.4 FACTORY SETTINGS RESET
If any change is made to the ducting, reset settings to restart the airow test.
PROCEDURE TO RESET SETTINGS
Press on the OK and (-) buttons simultaneously for 4 seconds. Use (+/-) to select Yes or No and OK to conrm.
Then perform the auto-balancing procedure.
Options Congurations available
DEF (Defrost) DIS* (Discretion - defrost without speed variation for more comfort),
PLU (Plus - extended defrost for colder areas)
INS (Installation) T-1, T-2, T-3, T-4*, T-5 (Refer to section 2.2)
DRY (Dry contact) MIN* (Minimum), INT (Intermittent), AUT (AUTO), MAX (Maximum) (Refer to section 3.3.1)
OVR (Override) BAL* (Balanced), PER (Performance), DIS (Discretion) (Refer to section 3.2.1)
INT (Intermittent)
STB* (Standby - 20 min in MIN speed and 40 min in standby mode), REC** (Recirculation - 20 min in MIN
speed and 40 min in recirculation mode) ** REC (Recirculation) conguration is not available for T-2 to T-5
installation congurations nor for 150H75NT, 150H75NS, 150E75NT and 150E75NS units.
NOTE : Following ducting installation conguration and temperature conditions, it may be necessary for the unit
to operate continuously. Refer to section 2.2 for more details.
* Factory setting
NOTE: If no selection is conrmed within 10 minutes, the unit will exit the menu without saving any changes.

18
7. SERVICE PARTS
ITEM DESCRIPTION PART NUMBER
16" port warm side SV66139 2222
5" port warm side SV66140 2 2 2 2 2
26" metal port motorized damper SV66135 1111
5" metal port motorized damper SV66136 1 1 1 1 1
3 Electronic assembly SV66144** 111111111
4 Terminal blocks SV66145 111111111
56" exhaust port assembly SV66137 1111
5" exhaust port assembly SV66138 1 1 1 1 1
6 Door latches and keepers for door SV61218 111111111
7 Thermistor SV66134 111111111
8 Recirculation damper with thermistor SV66148 1111111
9 Exhaust blower with damper SV66142 111111111
10 Supply blower assembly SV66141 111111111
11
Core ERV 65 % SV66113 1 1
Core ERV 75 % SV66114 1 1
Core HRV 65 % SV66115 1 1 1
Core HRV 75 % SV66116 1 1
12 MERV8 lters kit SV66133 111111111
13 Door SV66150 111111111
14 Exhaust damper SV66143 111111111
15 Separator WE with thermistor SV66149 1 1
* Hardware kit SV66146 111111111
* Fuse for PCB SV66147 111111111
* ½" hose SV00592 111111111
REPLACEMENT PARTS AND REPAIRS
In order to ensure your ventilation
unit remains in good working
condition, you must use Broan-
NuTone LLC genuine replacement
parts only. The Broan-NuTone LLC
genuine replacement parts are
specially designed for each unit
and are manufactured to comply
with all the applicable certication
standards and maintain a high
standard of safety. Any third party
replacement part used may cause
serious damage and drastically
reduce the performance level
of your unit, which will result in
premature failing. Broan-NuTone
LLC recommends to contact a
certied service depot for all
replacement parts and repairs.
* Not shown.
VL0086
B
C
D
E
F
G
=
I
J
K
L
M
N
B110H65RT
B110H65RS
B130H65RT
B130H65RS
B130E65RT
B130E65RS
B160H65RT
B160H65RS
B160E65RT
B160E65RS
B160H75RT
B160H75RS
B160E75RT
B160E75RS
B150H75NT
B150H75NS
B150E75NT
B150E75NS
P
O
** See next page to get the part number that corresponds to the ventilation unit model.

19
VENTILATION UNIT MODEL
ELECTRONIC
ASSEMBLY PART
NUMBER
SV66144-01 X
SV66144-02 X
SV66144-03 X
SV66144-04 X
SV66144-05 X
SV66144-06 X
SV66144-07 X
SV66144-08 X
SV66144-09 X
SV66144-10 X
SV66144-11 X
SV66144-12 X
SV66144-13 X
SV66144-14 X
SV66144-15 X
SV66144-16 X
SV66144-17 X
SV66144-18 X
B110H65RS
B110H65RT
B130H65RS
B130H65RT
B160H65RS
B160H65RT
B150H75NS
B150H75NT
B160H75RS
B160H75RT
B130E65RS
B130E65RT
B160E65RS
B160E65RT
B150E75NS
B150E75NT
B160E75RS
B160E75RT
7. SERVICE PARTS (CONT’D)

20
8. INSTALLER’S TROUBLESHOOTING
The wearing of safety glasses and gloves is recommended since a few diagnosis procedures may require the unit to be in operation
while proceeding. Be careful with moving and live parts to prevent any risk of injury.
WARNING
!
ERROR DESCRIPTION SOLUTION
E01 Supply damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable
obstacle or dirt (lters and core may have to be removed to access the
damper system). Plug the unit.
If STEP 1 did not x the problem, perform STEP 2: Open electrical
compartment, check if connector J5 (white) is well inserted, check for any loose
wires.
If STEP 2 did not x the problem, perform STEP 3: If the damper is not moving
at all, unplug J7 (red) from the electronic assembly, connect the white damper
system connector into J7. If the damper moves (but the system still shows an
error), the electronic assembly must be replaced. Otherwise, replace the damper
system.
E02 Supply damper timeout
E03 Supply damper
E05 Exhaust damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable
obstacle or dirt (lters and core may have to be removed to access the
damper system). Plug the unit.
If STEP 1 did not x the problem, perform STEP 2: Open electrical
compartment, check if connector J7 (red) is well inserted, check for any loose
wires.
If STEP 2 did not x the problem, perform STEP 3: If the damper is not moving at
all, unplug J5 (white) from the electronic assembly, connect the white damper
system connector into J5. If the damper moves (but the system still shows an
error), the electronic assembly must be replaced. Otherwise, replace the damper
system.
E06 Exhaust damper timeout
E07 Exhaust damper
E09 Recirculation damper range STEP 1: Unplug the unit, inspect the damper system, remove any undesirable
obstacle or dirt (lters and core may have to be removed to access the
damper system). Plug the unit.
If STEP 1 did not x the problem, perform STEP 2: Open electrical
compartment, check if connector J6 (blue) is well inserted, check for any loose
wires.
If STEP 2 did not x the problem, perform STEP 3: If the damper is not moving at
all, unplug J5 (white) from the electronic assembly, connect the blue damper
system connector into J5. If the damper moves (but the system still shows an
error), the electronic assembly must be replaced. Otherwise, replace the damper
system.
E10 Recirculation damper timeout
E11 Recirculation damper
E22 Supply airow STEP 1: Unplug the unit. Perform a visual inspection of the supply damper
system. Clean lters, distribution registers and outside supply hood. Inspect
ducting to ensure it is not squeezed or bent. Plug the unit.
If STEP 1 did not x the problem, perform STEP 2: Remove ducting of the supply
path. On the LCD screen, select MAX to check if the unit is able to reach the
selected ow. If so, review the ducting path.
If STEP 2 did not x the problem, perform STEP 3: On the LCD screen, select the
MIN and MAX ow setting values then reset the unit. MAX ow value will display
on the LCD screen. If MAX ow is above desired MAX ow, set MAX and MIN
ows.
If STEP 3 did not x the problem, perform STEP 4: Replace the supply blower
and repeat STEP 3.
If STEP 4 did not x the problem, perform STEP 5: Replace the electronic assembly.
E23 Supply motor (drive over current) STEP 1: Unplug/plug the unit.
If STEP 1 did not x the problem, perform STEP 2: Remove core and clear the
ventilation wheel from any dirt or obstacles.
If STEP 2 did not x the problem, perform STEP 3: Disconnect J2 (white) and
connect a spare blower system. If it works, replace supply blower.
If STEP 3 did not x the problem, perform STEP 4: Replace the electronic assembly.
E27 Supply motor (drive foc duration)
E28 Supply motor (drive speed feedback)
E29 Supply motor (startup)
E24 Supply motor (drive over voltage) STEP 1: Unplug/plug the unit. Under and over voltage may be detected with
severe in-house power supply uctuation and stop the motor for protection.
If STEP 1 did not x the problem, perform STEP 2: Replace the electronic assembly.
E25 Supply motor (drive under voltage)
This manual suits for next models
20
Table of contents
Languages:
Other Broan Fan manuals

Broan
Broan 353 User manual

Broan
Broan S50U User manual

Broan
Broan QTXE110SFLT User manual

Broan
Broan 676 User manual

Broan
Broan qt130le User manual

Broan
Broan HRV150FL User manual

Broan
Broan ZB110HL User manual

Broan
Broan SKY Series User manual

Broan
Broan 761BN User manual

Broan
Broan NuTone ULTRA Pro RN80C User manual