Burkert ME24 User manual

Operating Instructions
Type ME24
I/O-Module

We reserve the right to make technical changes without notice.
Technische Änderungen vorbehalten.
Sous réserve de modifications techniques.
© Bürkert Werke GmbH & Co. KG, 2015 -2017
Operating Instructions 1710/02_EU-EN_00810473 / Original DE

3
Content
1 THE OPERATING INSTRUCTIONS .............................................................................................................................................6
1.1 Symbols ......................................................................................................................................................................................6
1.2 Definition of the term “product” .....................................................................................................................................6
2 AUTHORIZED USE .............................................................................................................................................................................7
3 BASIC SAFETY INSTRUCTIONS .................................................................................................................................................8
4 GENERAL INFORMATION ................................................................................................................................................................9
4.1 Contact address .....................................................................................................................................................................9
4.2 Warranty ......................................................................................................................................................................................9
4.3 Information on the Internet ...............................................................................................................................................9
5 DESCRIPTION OF THE DEVICE ...............................................................................................................................................10
5.1 Possible combinations .....................................................................................................................................................10
6 TECHNICAL DATA .............................................................................................................................................................................11
6.1 Conformity ..............................................................................................................................................................................11
6.2 Standards ................................................................................................................................................................................11
6.3 Operating conditions ........................................................................................................................................................11
6.4 Mechanical data ...................................................................................................................................................................12
6.5 Electrical data .......................................................................................................................................................................13
6.5.1 Electrical properties of the inputs and outputs ...........................................................................13
7 INSTALLATION ...................................................................................................................................................................................15
7.1 Safety instructions .............................................................................................................................................................15
7.2 Mount Type ME24 on backplane Type BEF1 ........................................................................................................15
7.3 Connect external sensors and actuators ...............................................................................................................16
7.3.1 Plug configuration and wiring ..........................................................................................................17
8 START-UP .............................................................................................................................................................................................23
8.1 Safety instructions .............................................................................................................................................................23
8.2 Configuration of Type ME24 ..........................................................................................................................................23
I/O module
Type ME24
English

4
Type ME24
9 CONFIGURATION USING THE DISPLAY .............................................................................................................................24
9.1 Brief description of the user interface ....................................................................................................................24
9.1.1 Description of buttons .......................................................................................................................25
9.2 Operating structure ...........................................................................................................................................................26
9.3 User level (access rights) ..............................................................................................................................................27
9.3.1 Changing the user level (access rights) .......................................................................................27
9.3.2 Logging off the user level .................................................................................................................28
9.3.3 Changing password (PIN) ................................................................................................................28
9.4 Switching to the Parameter, Maintenance or Diagnostics detailed view .............................................29
9.5 Setting Bürkert system bus (büS) .............................................................................................................................30
9.5.1 Detailed views in the büS function .................................................................................................31
9.6 Setting input module ........................................................................................................................................................32
9.6.1 Setting analog input ...........................................................................................................................32
9.6.2 Calibrating analog input ....................................................................................................................35
9.6.3 Reset analog input to factory settings ...........................................................................................37
9.6.4 Setting digital input ............................................................................................................................37
9.6.5 Reset totalizer, only when Flow rate operating mode active ....................................................40
9.6.6 Calibrate digital input, for Flow rate operating mode only ........................................................41
9.6.7 Resetting digital input to factory settings .....................................................................................42
9.6.8 Simulation of a process value on the input module ....................................................................43
9.7 Setting output module .....................................................................................................................................................44
9.7.1 Setting analog output ........................................................................................................................44
9.7.2 Calibrating analog output .................................................................................................................47
9.7.3 Resetting analog output to factory settings .................................................................................48
9.7.4 Setting digital output .........................................................................................................................48
9.7.5 Manually actuating output module ..................................................................................................62
10 DISPLAY ELEMENTS ......................................................................................................................................................................63
10.7.1 Display of device status ....................................................................................................................64
11 MAINTENANCE ..................................................................................................................................................................................65
11.1 Safety instructions .............................................................................................................................................................65
11.2 Replacing devices ...............................................................................................................................................................65
11.3 Replacing the memory card ..........................................................................................................................................67
11.4 Troubleshooting ...................................................................................................................................................................69
English

5
Type ME24
12 ACCESSORIES ..................................................................................................................................................................................70
13 PACKAGING AND TRANSPORT ...............................................................................................................................................71
14 STORAGE ..............................................................................................................................................................................................71
15 DISPOSAL ............................................................................................................................................................................................71
English

6
The operating instructions
Type ME24
1 THE OPERATING INSTRUCTIONS
The operating instructions describe the entire life cycle of the device. Keep these instructions in a location which is
easily accessible to every user and make these instructions available to every new owner of the device.
Important Safety Information.
Read the operating instructions carefully and thoroughly. Study in particular the chapters entitled “2 Authorized
use” and “3 Basic safety instructions”.
▶The operating instructions must be read and understood.
1.1 Symbols
DANGER!
Warns of an immediate danger.
▶Failure to observe the warning will result in a fatal or serious injury.
WARNING!
Warns of a potentially dangerous situation.
▶Failure to observe the warning may result in serious injuries or death.
CAUTION!
Warns of a possible danger.
▶Failure to observe this warning may result in a moderate or minor injury.
NOTE!
Warns of damage to property.
• Failure to observe the warning may result in damage to the device or the equipment.
Indicates important additional information, tips and recommendations.
Refers to information in these operating instructions or in other documentation.
▶Designates instructions for risk prevention.
→Designates a procedure which you must carry out.
Indicates a result.
1.2 Definition of the term “product”
In these instructions, the term „product“ always refers to the I/O module, Type ME24.
English

7
Authorized use
Type ME24
2 AUTHORIZED USE
Non-authorized use of the Type ME24 may be dangerous to people, nearby equipment, and the
environment.
The I/O module Type ME24 collects, converts and compares physical measurement data from external sensors
or receives switching commands from büS participants via the büS interface. This measurement data or these
switching commands are relayed to external actuators or to büS participants via the büS interface.
▶Use according to the authorized data, operating conditions and conditions of use specified in the contract
documents and operating instructions.
Observe the following when using the product
▶Use the device only in conjunction with third-party devices and components recommended and authorized by
Bürkert.
▶Use only when in perfect condition and always ensure proper storage, transportation, installation and
operation.
▶Use only as intended.
English

8
Basic safety instructions
Type ME24
3 BASIC SAFETY INSTRUCTIONS
These safety instructions do not make allowance for any
• contingencies and events which may arise during the assembly, operation, and maintenance.
• local safety regulations – the operator is responsible for observing these regulations, also in relation to the instal-
lation personnel.
General hazardous situations.
To prevent injuries:
▶Do not make any internal or external changes on the product and do not subject it to mechanical stress.
▶Secure the system from unintentional actuation.
▶Only trained technicians may perform installation and maintenance work.
▶After an interruption in the power supply, ensure that the process is restarted in a controlled manner.
▶Observe the general rules of technology.
NOTE!
Electrostatic sensitive components or modules.
The product contains electronic components which react sensitively to electrostatic discharge (ESD). Contact
with electrostatically charged persons or objects are hazardous to these components. In the worst case scenario,
they will be destroyed immediately or will fail after start-up.
• Observe the requirements in accordance with EN 61340-5-1 to minimize or avoid the possibility of damage
caused by sudden electrostatic discharge.
• Do not touch electronic components while the supply voltage is switched on.
English

9
General information
Type ME24
4 GENERAL INFORMATION
4.1 Contact address
Germany
Bürkert Fluid Control Systems
Sales Center
Christian-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: [email protected]
International
Contact addresses can be found on the final pages of the printed operating instructions.
And also on the Internet at:
www.burkert.com
4.2 Warranty
The warranty is only valid if the Type ME24 is used as intended in accordance with the specified application conditions.
4.3 Information on the Internet
The operating instructions and data sheets for Type ME24 can be found on the Internet at:
www.burkert.com
English

10
Description of the device
Type ME24
5 DESCRIPTION OF THE DEVICE
The output module of Type ME24 receives the switching commands of büS participants via the büS interface, pro-
cesses them and relays this information to externally connected actuators.
The input module of Type ME24 receives the physical measurement data from external sensors. The input module
converts and compares this measurement data and communicates the values via the büS interface to büS participants.
The HMIU module Type ME25, in conjunction with the display Type ME21, can be used to configure the basic func-
tions. Alternatively, this can also be carried out via the “Bürkert Communicator”.
5.1 Possible combinations
The I/O module Type ME24 can only be operated within a system in combination with additional modules. For
setting up a system comprising several modules, please contact your Bürkert sales office.
Example of a system in minimum combination:
Connection variant:
Terminals for cable
gland
Connection variant:
Circular plug-in
connector M12
13
6 5 7
ME24
24
6 5 7
ME24
Figure 1: Example of a system: Minimum combination of Type ME24 with additional modules
Module Designation Types Order no.
1 Input module (connection variant: circular plug-in connector M12) ME29 00564825
2 Input module (connection variant: terminals) ME29 00564826
3 Output module (connection variant: socket M12) ME29 00564827
4 Output module (connection variant: terminals) ME29 00564828
5 Backplane for Type ME24 BEF1 00564841
6 Backplane, left BEF1 00564844
7 Backplane, right BEF1 00564846
Table 1: Modules of a possible combination with Type ME24
English

11
Technical data
Type ME24
6 TECHNICAL DATA
6.1 Conformity
The Type ME24 I/O module conforms to the EU directives according to the EU Declaration of Conformity (if applicable).
6.2 Standards
The applied standards, which verify conformity with the EU Directives, can be found on the EU-Type Examination
Certificate and / or the EU Declaration of Conformity (if applicable).
6.3 Operating conditions
WARNING!
Risk of injury.
▶Avoid heat sources which may cause the permissible temperature range to be exceeded.
Permitted temperatures
Ambient temperature: 0...+50 °C
English

12
Technical data
Type ME24
6.4 Mechanical data
Dimensions:
94
22
3,1
111
116
Figure 2: Dimensions
Housing material: Polycarbonate
English

13
Technical data
Type ME24
6.5 Electrical data
Supply voltage: 20...30 V via the backplane BEF1
UL devices: Power supply unit restricted to Class 2
Power consumption: < 3 W
If the outputs are supplied via büS, the total current is limited internally to 2 A: max.
48 W
Degree of protection: IP65 according to EN 60529 / IEC 60529
(only if cables, plugs and sockets have been connected correctly)
6.5.1 Electrical properties of the inputs and outputs
2AO, 2DO
Analog output AO • Current output: 4...20 mA
• Galvanic isolation
• Protection against DC reverse polarity
• Resolution: 6 µA
• Maximum loop impedance (at current output 22 mA)
1350 Ω at 35 V DC
850 Ω at 24 V DC
300 Ω at 12 V DC
• Detection of open loop
Digital output DO • Transistor output
• Galvanic isolation
• Max. 2500 Hz
• Max. 0.7 A per channel
Max. 1 A per module
• Operating mode (signals):
On-Off
Threshold value
PWM
PFM
• Overload detection
Table 2: Electrical properties 2AO, 2DO
English

14
Technical data
Type ME24
4DO PWM 20 kHz
Digital output DO • Transistor output: open drain output
• Max. 20,000 Hz
• Max. 0.7 A per channel
Max. 1.8 A per module
• Operating mode (signals):
On-Off
Threshold value
PWM
PFM
• Overload detection
Table 3: Electrical properties 4DO PWM 20 kHz
2AI, 2DI
Analog input AI • Current input or voltage input: 4 - 20 mA
0 - 20 mA
0 - 10 V
0 - 5 V
0 - 2 V
• Galvanic isolation
• Protection against DC reverse polarity
• Detection of open loop (at voltage input)
• Input impedance for
current measurement: 110 Ω
voltage measurement: 120 kΩ
Digital input DI • Voltage input: 0 - 35 V DC
• Galvanic isolation
• Protection against DC reverse polarity
• Frequency: 0.5...2500 Hz
• Input impedance approx. 3 - 5 kΩ at voltage of 5 - 35 V
• Switching threshold: VON = 5 - 35 V
VOFF < 2 V DC
Table 4: Electrical properties 2AI, 2DI
English

15
Installation
Type ME24
7 INSTALLATION
7.1 Safety instructions
WARNING!
Risk of injury from improper installation.
▶Installation may be carried out only by trained technicians and with the appropriate tools.
▶Secure system against unintentional activation.
▶Following installation, ensure a controlled restart.
7.2 Mount Type ME24 on backplane Type BEF1
A
A 1 : 1
I/O module
Type ME24
Fastening screw
(hexagon socket 2.5 mm)
Backplane
Type BEF1
Hinge
Figure 3: Mount I/O module Type ME24 on backplane Type BEF1
→Insert hinge part of Type ME24 in counter piece of backplane Type BEF1.
→Press Type ME24 fully on the backplane.
→Tighten fastening screw (hexagon socket 2.5 mm). Max. torque 1 Nm.
The Type ME 24 is now connected to the supply voltage on the backplane Type BEF1.
NOTE!
▶Use power supply with adequate power.
English

16
Installation
Type ME24
7.3 Connect external sensors and actuators
Fastening screw
(hexagon socket 2.5 mm)
Cover
opened
Recess for securing
the cables
Cover
closed
Opening for cable
Connection terminals
Figure 4: Connect external sensors and actuators
→Unscrew fastening screw at the cover of Type ME24 (hexagon socket 2.5 mm).
→Open and remove cover.
→Pull out connection terminals.
→Insert cables of the external sensors and actuators through the opening on the back of the cover.
→Connect wires of the external sensors and actuators to the connection terminals (plug configuration see
chapter “7.3.1 Plug configuration and wiring”).
→Reconnect connection terminal.
→Close cover and tighten fastening screw. Max. torque 1 Nm.
Fixing the cables for external sensors and actuators (strain relief):
To relieve the strain, fix the cables to the recess with a cable clip.
English

17
Installation
Type ME24
7.3.1 Plug configuration and wiring
ME24 models 2AO, 2DO, f(x)
1 2 34 5 6 7 8 9 10 11 12
2AO/2DO/f(x)
Figure 5: Configuration 2AO, 2DO, f(x)
2AO, 2DO, f(x)
Pin Plug configuration External circuit
1 + 20 - 30 V / 2 A max. OUTPUT
no galvanic isolation
2 –
3 AO1+ + (4 - 20 mA) output galvanically isolated
4 AO1– – (4 - 20 mA) output galvanically isolated
5 FE Shielding
6 AO2+ + (4 - 20 mA) output galvanically isolated
7 AO2– – (4 - 20 mA) output galvanically isolated
8 DO1+ + NPN galvanically isolated
9 DO1– – NPN galvanically isolated
10 FE Shielding
11 DO2+ + NPN galvanically isolated
12 DO2– – NPN galvanically isolated
Table 5: Configuration 2AO, 2DO, f(x)
English

18
Installation
Type ME24
20...30 V
0 V
20...30 V
20...30 V
0 V
0 V
20...30 V
0 V
+
–
+
–
+
–
+
–
1
Digital input
(on the external instrument
or external load)
4 - 20 mA input
(on the external
instrument)
Digital input
(on the external
instrument or external
load)
4 - 20 mA input
(on the external
instrument)
+
–
AO1+
AO1–
FE
AO2+
AO2–
DO1+
DO1–
FE
DO2+
DO2–
2AO, 2DO, f(x): 2-wire
2 3 4 5 6 7 8 9 10 11 12
Figure 6: External circuit 2AO, 2DO, f(x), 2-wire
0 V
20...30 V
20...30 V
0 V
20...30 V
20...30 V
0 V
0 V
+
S
–
+
S
–
+
S
–
+
S
–
1
Digital input
(on the external
instrument)
4 - 20 mA input
(on the external
instrument)
Digital input
(on the external
instrument)
4 - 20 mA input
(on the external
instrument)
+
–
AO1+
AO1–
FE
AO2+
AO2–
DO1+
DO1–
FE
DO2+
DO2–
2AO, 2DO, f(x): 3-wire
2 3 4 5 6 7 8 9 10 11 12
Figure 7: External circuit 2AO, 2DO, f(x), 3-wire
English

19
Installation
Type ME24
ME24 models 4DO PWM 20 kHz
123456789
4DO/f(x)
Figure 8: Configuration 4DO PWM 20 kHz
4DO PWM 20 kHz
Pin Plug configuration External circuit
1 + 20 - 30 V / 2 A max. total current
no galvanic isolation
2 DO1– Open drain
3 + 20 - 30 V / 2 A max. total current
no galvanic isolation
4 DO2– Open drain
5 + 20 - 30 V / 2 A max. total current
no galvanic isolation
6 DO3– Open drain
7 + 20 - 30 V / 2 A max. total current
no galvanic isolation
8 DO4– Open drain
9 FE Shielding
Table 6: Configuration 4DO PWM 20 kHz
English

20
Installation
Type ME24
123456789
FE
+
–
+
–
Digital input
(on the external
instrument)
Digital input
(on the external
instrument)
+
DO1–
+
DO2–
+
DO3–
+
DO4–
FE
4DO, f(x)
External load
(e.g. valve)
External load
(e.g. valve)
Figure 9: External circuit 4DO PWM 20 kHz
English
Other manuals for ME24
1
Table of contents
Other Burkert I/O System manuals