CallerID Whozz Calling Deluxe 2 User manual

Caller .comID
ID
Whozz Calling?
Deluxe 2,4,8
Caller ID Interface
Product Manual
Caller .comID
ID
Revision 5.0 - 11/15/2015
(SMT Versions)
CALLING?
WHOZZ
8
CALLING?
WHOZZ
4
CALLING?
WHOZZ
4
CALLING?
WHOZZ
4
CALLING?
WHOZZ
4
CALLING?
WHOZZ

Whozz Calling? 2, 4, and 8 Line
Deluxe Units
Product Manual
Revision 6.1- 01/27/2020
(SMT Versions)

CONTENTS
Introduction ...................................................................................................................................................................1
Telephone Line and Serial Communication Requirements ...........................................................................................1
Connecting to Phone Lines .............................................................................................................................3
Connecting to Computer .................................................................................................................................3
Overview of Toggles, Commands, and Formats
Setup Toggles..................................................................................................................................................4
Operating Commands......................................................................................................................................5
Data Entry Commands ....................................................................................................................................5
Detail Mode Output.........................................................................................................................................5
Error Condition ...............................................................................................................................................5
Data Format.....................................................................................................................................................6
In-Depth Discussion of Toggles, Commands, and Formats
Setup Toggle Discussion.................................................................................................................................6
Operating Commands Discussion ...................................................................................................................7
Data Entry Commands Discussion..................................................................................................................8
Detail Mode Output Discussion ......................................................................................................................9
Error Condition Discussion.............................................................................................................................9
Format Discussion...........................................................................................................................................9
Inbound Calls....................................................................................................................................9
Outbound Calls ...............................................................................................................................10
Discussion of Private and Out-Of-Area Callers ..........................................................................................................12
Specifications ........................................................................................................................................................12
Manufacture’s Information..........................................................................................................................................13
Warranty Information..................................................................................................................................................13
Appendix A - International Caller ID formats and Internal Jumper Settings ..............................................................14
Appendix B - On and Off-Hook Detection (Voltage vs. Current) ..............................................................................16
Appendix C - RS232 Pin Outs.....................................................................................................................................19
Appendix D - Phone Line Compatibility.....................................................................................................................20
Appendix E - Serial Loop Diagnostic Tool .................................................................................................................21
Appendix F - Explanation Of Start Up Sequence And Front Panel Lights .................................................................22
Appendix G - Installation Directions...........................................................................................................................23
LIST OF FIGURES
Figure 1......... Front and Back Views of Whozz Calling? Deluxe 4 Line Model (Serial).............................................2
Figure 2......... Data Output Format..............................................................................................................................11
Figure A1...... Configuring Unit for Different Caller ID Signaling Formats...............................................................15
Figure B1
...... Voltage and Current Detection Configuration (4 Line Model -PCB Version 6,7,or 8) .......................
17
Figure B2...... Voltage and Current Detection Configuration (4 Line Model -PCB Version 10 or above).................18
Figure G1...... Front and Back Views of Deluxe 4 Line Model ..................................................................................24
Figure G2a.... Parallel Connection for 2-Wire (RJ11) system ....................................................................................26
Figure G2b.... Parallel Connection for 4-Wire (RJ14) system ....................................................................................26
Figure G3a.... Series Connection for 2-Wire (RJ11) system.......................................................................................27
Figure G3b.... Series Connection for 4-Wire (RJ14) system.......................................................................................27

INTRODUCTION
The Whozz Calling? Deluxe units capture all details of inbound and outbound calls and send this information to a
computer via RS232 serial port or Ethernet link depending on the model purchased. If Ethernet, also refer to the
Ethernet Link Supplement.
Deluxe units can be set to deliver only inbound Caller ID, ignoring all outbound dialed numbers. Or, both inbound
and outbound data can be sent for complete call accounting applications. Data records are sent just as the call
begins, just after the call ends, or both at the beginning and the end of the call depending upon the unit’s
configuration. Deluxe units are also capable of sending real-time, detailed events occurring on each telephone line
such as Ring, Off Hook, and On Hook.
Models equipped with relays are capable of blocking select incoming calls, based on the Caller ID number, from
passing through to the output jacks. This feature can be accomplished by dynamic control from the application
software or by pre-loading blocked phone numbers into the unit's memory. First ring suppression to the output jack
also can be performed with relay-equipped models. Selecting this option prevents office employees from answering
the telephone too quickly and thus preventing the Caller ID signal from being delivered.
The Whozz Calling? Deluxe unit uses setup toggles to determine how the unit will operate. The toggles are either
upper or lower case letters and are stored in non-volatile memory. For information on unit toggles, please refer to
page 4. Operating commands are used to list the setup parameters, see the phone number list used for call blocking,
and to reset the system. The Send Data commands are used to set line numbers, set the internal clock, and enter
phone numbers for call blocking.
The manual gives a brief discussion of the setup toggles, commands, and data formats. An in-depth discussion is
provided for all setup toggles, commands, and data formats, along with a discussion of Private and Out-Of-Area
Caller ID types.
TELEPHONE LINE AND SERIAL COMMUNICATION REQUIREMENTS
The Whozz Calling? POS is designed to collect call data from standard analog central office telephone lines. It will
not work properly when connected to extensions (or station) lines coming from a telephone switch. Connect the
unit only to analog phone lines or phone lines that have been converted to analog signaling (i.e. Cable box
converters, analog terminal adaptors, etc.).
If your unit connects to a computer through a serial port, the serial port must be functioning correctly and no other
software application can be accessing this same port. This unit will work with any serial port or COM number
setting that your software supports. If you do not have an available serial port on your computer, a USB-to-serial
adaptor cable can be used. These can be found at any computer store or most office supply outlets. The USB-to-
serial adaptor cable must be verified as, “correctly installed and operational” within the Windows device Manager
If you unit connects via Ethernet cable, plug it into any switch or router on your Local Area Network. Use the
Ethernet Configuration Tool located at www.CallerID.com/downloads/diagnostic-tools/ to set the unit to a static IP
address within your IP scheme and outside any DHCP range. Refer to the Ethernet Supplement for more details.

2
Fig. 1 Front / Back Views of Whozz Calling? 4 Deluxe (Serial Port Model)Fig. 1 Front / Back Views of Whozz Calling? 4 Deluxe (Serial Port Model)
Standard RS232
9600 Baud.
8 Bit, 1 Stop, No Parity.
Standard RS232
9600 Baud.
8 Bit, 1 Stop, No Parity.
L4 L3 or L3/L4 L2 L1 or L1/L2
OUT INOUT IN
OUT IN
OUT IN
Power Line 1 Line 2 Line 3 Line 4
LED will
be on during
normal operation.
LED will
be on during
normal operation.
LEDs that stay on
indicate "live" phone lines
connected. They go on
and off to follow on-hook
events, off-hook events,
ringing signals, and
DTMF digits dialed.
LEDs that stay on
indicate "live" phone lines
connected. They go on
and off to follow on-hook
events, off-hook events,
ringing signals, and
DTMF digits dialed.
LEDs for inactive
lines will flash dimly
LEDs for inactive
lines will flash dimly
9600 Baud,N,8,1
9VDC
Complies with FCC Part 68. FCC
Reg. No. 2EWUSA-73088-ND-N.
REN 0.5A, 1.6B, Jack (USOC) RJ11
Model: WHOZZ CALLING?
Complies with FCC Part 68. FCC
Reg. No. 2EWUSA-73088-ND-N.
REN 0.5A, 1.6B, Jack (USOC) RJ11
Model: WHOZZ CALLING?
2 conductor jacks connect
to a single phone line using
the center pair wires.
IN from Telephone Co.
OUT to phones or
phone switch (Series Conct.)
2 conductor jacks connect
to a single phone line using
the center pair wires.
IN from Telephone Co.
OUT to phones or
phone switch (Series Conct.)
4 conductor jacks connect
to two phone lines using
both pair of wires on cord.
IN from Telephone Co.
OUT to phones or
phone switch (Series Conct.)
4 conductor jacks connect
to two phone lines using
both pair of wires on cord.
IN from Telephone Co.
OUT to phones or
phone switch (Series Conct.)
Caller .comID
ID
4
Deluxe Caller ID Interface
CALLING?
WHOZZ

3
Connecting to Phone Lines
There are two methods of connecting the monitoring unit to your phone lines: the series (pass through) connection,
or the parallel (branch off) connection. The series connection uses both input and output modular jacks on the unit.
The parallel connection uses only the input jacks.
Parallel Connection (recommended)
A parallel phone line connection is recommended and often easier since the incoming lines to the building can
simply be "branched off" to the unit. This connection allows the unit to be removed from service for
troubleshooting or repair without affecting the telephone call path. With this connection only the input ports on the
unit are used.
Figures 2a & 2b (Pg. 26) show parallel connections. This involves branching off or "tapping" from each phone line
to be monitored and connecting them to their respective input jacks on the unit. If appropriate, bare wire to modular
adapters may be required.
Series Connection
Connecting the unit in series with the telephone lines is required only in special circumstances. Only if you need to
operate the unit in a loop current detection mode (Appendix B, pg. 16), require first ring suppression, or are
implementing call blocking would the unit need to be wired in series with the telephone lines. If the unit is
connected in series and then taken out of service, the input and output phone lines will have to be connected
together to resume normal telephone call flow.
Figures 3a & 3b (Pg. 27) show series connections. Each phone line to be monitored passes through the unit. Phone
lines coming into the building connect to the input jacks on the unit (through bare wire to modular adapters, if
needed). Lines connected to the output jacks continue to the desktop phones (through a phone switch, if present).
2-Wire (RJ11) or 4-Wire (RJ14) Phone Cord Connections
Most modular phone cords contain 4 wires which can handle two phone lines (2 wires for each line.) Your system
may have either 2 of the wires connected (RJ11 - 1 phone line) or four wires connected (RJ14 - 2 phone lines). The
modular connectors on the unit are equipped to handle either arrangement. They are marked similar to the modular
connectors on a 2 line phone. For example, Channel 1 is marked “L1 or L1/L2”. L1 is for a 2-wire phone cord and
L1/L2 is for a 4-wire phone cord. Please refer to Fig. 1, pg. 2.
For a 2-wire (RJ11) system one phone cord simply plugs into each channel on the unit. Caution must be observed
when connecting a 4-wire (RJ14) system. Phone cords must only be connected to channels 1 and 3. To prevent
crossed telephone lines, do not connect phone cords to channels 2 and 4 on a 4-wire, RJ14 system.
If you are unsure whether your system is 2 wire or 4 wire a quick check can be made using the unit. First, power on
the unit. Connect one cord to the input of channel 1. If only the Line 1 light comes on, you have a 2-wire (RJ11)
cord. If both Line 1 and Line 2 lights come on, you have a 4-wire (RJ14) cord. Continue checking the rest of your
cords in this manor.
Connecting to Computer (for Serial Port models only, else refer to the Ethernet Supplement)
You may have purchased a software package designed to work in conjunction with the Whozz Calling? Deluxe
unit. The software may have a built-in automatic search and find function. This routine will search all COM
numbers in an attempt to determine settings for the serial port with which the unit is connected. If no
communication can be established between your software and the Whozz Calling? unit, use our Serial Loop
diagnostic tool to help solve the issue For detailed instructions on working with the Serial Loop Tool refer to
Appendix E, pg. 21.

4
OVERVIEW OF TOGGLES, COMMANDS, AND FORMATS
For simple Caller ID applications, we suggest the following default toggle setup:
ECXUDASOBKT
The combination of a lower case "A" and an upper case "S" instructs the unit to send call information at both the
start and end of each call. With upper case "O" set, the unit will not report call information on outbound calls. This
combination of toggles gives a simple configuration for Caller ID only applications. The toggles can be configured
in either upper or lower case and combinations set to support various applications such as Popup screens, Call
Accounting, Integrated Voice Response (IVR) applications and Telephony Diagnostics.
Application Notes: All toggles can be changed by simply sending the new toggle. The unit is designed to accept
one toggle at a time. If a software application sends an initialization string of toggles to the unit, a short pause of at
least 50 milliseconds should be inserted between each toggle so the unit it has enough time to write the entry to non-
volatile memory.
Setup Toggles
This is a quick listing of the setup toggles. A complete explanation of each toggle begins on page 6.
E Always E
C $ sign not sent as leading character in data stream & dashes inserted in phone number.
c $ sign is sent as leading character in data stream & dashes removed in phone number.
XAlways X
UInternal blocking/passing OFF. *Only available on select units.
u Internal blocking/passing ON. (Block or pass is determined by "K,k" toggle).
KPass calls until notified by Internal Memory routine ("u") or by Wcommand.
kBlock calls until notified by Internal Memory routine ("u") or by Wcommand.
AData sent BEFORE and AFTER call.
a Data sent as defined by "S,s" toggle.
SData sent at the Start of call only. (If "a" set above).
sData sent at the End of call only. (If "a" set above).
BBlock first ring to output jack. *Only available on select units.
bBlock first ring set to OFF.
DDetail information for call not sent.
dDetail information sent.
OInbound call information sent only.
o Outbound and Inbound information sent.
TAlways T

5
Operating Commands
@Send back #sign. (Used for establishing device communication).
VSend firmware Version number, date & time, toggle settings, line numbers.
v Send internal jumper settings (determining the Caller ID type captured and On/Off-Hook scheme used)
J List all phone numbers in memory. (Used for internal blocking/passing).
QDelete all phone numbers in memory.
RReset system. Toggles set to upper case default values.
Data Entry Commands
N000000770n<CR> Set starting line number count. When n=1 unit reports data as line 1 through line 4
on a four line unit. If n=5, unit reports L5-L8 on a four line unit.
Nnnnnnnnnnn <CR> Add phone number to memory for internal block/pass feature.
*Only available on select units.
Wnn <CR> Normal use (toggle "K" set) is to block call on line nn. Usually sent after the CID
string and before the 2nd ring. Or, pass call on line nn. ("k" set).
*Only available on select units.
Zmmddhhmm <CR> Set date and time on internal device clock.
Detail Mode Output
nn R Date & Time Ringing on line nn
nn F Date & Time Off Hook on line nn
nn N Date & Time On Hook on line nn
Additional Detail Information
nn Vxx Date & Time Firmware version of slave ROM (Displays on start up)
Error Condition
?Error (invalid command or could not interpret data)

6
Output Format
01 I S 0276 G B3 09/26 11:28 AM 800-240-4637 CallerID.com<CR/LF>
01 Line number field 2 char. (preset by user)
I Inbound/Outbound field 1 char. (or Ofor outbound)
S Start/End of call field 1 char. (or Efor end)
0276 Duration of call in seconds 4 char. (only sent at end of call)
G Good checksum for CID string 1 char. (or Bfor bad checksum)
B3 Number & Type*of Ring(s) 2 char. (only sent on end of call)
09/26 Date field 5 char.
11:28 Time field 5 char. (12 hour format)
AM AM/PM field 2 char.
Phone # Phone number field 14 char. (in some cases only 7 digits sent)
Name Name field 15 char. (sent only in some areas)
Note: Each data string is followed by a carriage return and a line feed.
1 space separates each field
*Type of Ring is valid only if distinctive ring service is ordered from telephone company.
IN-DEPTH DISCUSSION OF TOGGLES, COMMANDS, AND FORMATS
Setup Toggle Discussion
EAlways E
C,c Leading $character and dashes removed in phone number field
Some applications need to detect a certain character in order to perform an operation. When this toggle is set to "c",
the unit places a "$" character before each data string. This includes detail data strings such as Ring, Off hook, On
hook, and Hook flash (see toggle "D,d"). Also when cis set, the dashes are removed from the telephone number
field. The telephone number justification remains as set by the "X,x" toggle.
XAlways X
U,u Internal Block/Pass *Only available on select units.
The unit can block or pass incoming calls based on a match against phone numbers pre-loaded into the on-board
memory. The "u" toggle turns on the Block/Pass feature. The "K,k" toggle determines whether the unit blocks or
passes calls that match these numbers.
K,k Block or Pass Select *Only available on select units.
Set "K" to pass all calls until defeated. Set "k" to block all calls until defeated. These toggles can be defeated by
either the "W" command sent by the host computer or signal sent by the internal memory when a phone number
match is found.

7
A,a Data Delivery Option (Start & End or Start/End)
The unit is capable of delivering a data stream to the host computer immediately as the call arrives, when the call
terminates, or both. For an inbound call, immediate data delivery allows the Caller ID information to be utilized
before the call is answered for purposes of database queries, call routing, etc. Delivering the data stream after the
call ends provides additional information about the call to the application program such as, the duration of the call
and the number of rings before the call was answered. If lower case "a" is set, data is sent as defined by the "S,s"
toggle.
S,s Data Delivery Option (Start/End)
For this toggle to affect operation "a" must be set. If call data is to be sent before the call is answered, set toggle to
"S". If call data is to be sent only after call terminates, set toggle to "s". If call data is to be sent before and after the
call, set toggle "A".
B,b First Ring Suppression *Only available on select units.
When this toggle is set to "B", the first ring to the output jack on each line is suppressed. Since the Caller ID stream
is sent between the first and second rings on the telephone line, this prevents the call from being answered before
the information is sent. However, in some cases, hearing the first ring might be essential for the user to respond to
the call in a timely manner. If this is true, set this toggle to "b".
D,d Detail Information
Some software applications may need additional call data. When the lower case "d" toggle is selected, the unit can
provide an indication for Ring, Off hook, On hook, and Hook flash. The format is as follows: line number (nn);
space; and either a R(Ring), F(ofFhook), N(oNhook), or H(Hook flash). The date and time (HH:MM:SS)
follow at the same offset as the date/time field in the comprehensive format. In the detail mode, the time is
delivered in a 24 hour format. (Please note: If the "c" toggle is selected, a leading "$" will be added to the above
data string). For more information see the section on Detail Mode on page 9.
O,o Inbound/Outbound Select
For basic Caller ID applications, use the upper case "O". If complete call accounting is required, use lower case
"o". The lower case "o" instructs the unit to deliver for both inbound and outbound calls.
TAlways T
Operating Commands Discussion
@Handshaking character when sent
The unit will return "#" when "@"is sent. This can be used to establish communication between the computer and
the unit. One application for this command is a software setup routine that automatically searches for the unit by
sending an "@" character on each COM port and IRQ until a "#" is returned. The corresponding COM port and
IRQ number then can be set automatically in the application.
VFirmware version and all settings
This command returns the firmware version, all toggle and line number settings, and date & time (in military
format) on the internal time clock. On start-up, toggles will be defaulted to all upper case values; the line number
will be set to "L=01"; and date & time will be set to zero. All toggles and line number settings are stored in non-
volatile memory and will remain saved even if the unit loses power. The internal clock does not run while the unit
is off, and therefore, it must be reset when power is restored. The clock can be reset by the software using the "Z"
command or will be reset on the first good Caller ID signal. Subsequent Caller ID signals with good checksums
will continue to reset the internal time clock with the telephone company's time.

8
vFirmware version and all settings
This command returns the configuration of the internal jumper settings. Jumpers on the circuit board configure the
unit to capture either of the 4 types of Caller ID signaling formats used around the world (refer to Appendix A, page
14) as well as the On/Off scheme used by the device. In most cases, the Caller ID signaling format is factory set to
FSK (US type). If the Caller ID signaling type is pre-determined for your area before being shipped, these jumpers
may be set to the pre-determined format. The On/Off-Hook scheme is also set using internal jumpers to either
Voltage or Current Detection (Appendix B, page 16). Below are examples of lower case "v" outputs.
v-VFU (Voltage Detection, FSK, US Type)
v-CFB (Current Detection, FSK, BT/ETSI Type)
JList all phone numbers in memory
This command lists all telephone numbers stored in non-volatile memory. These numbers can be used to either
block or pass calls to the output phone jacks. (Refer to the section on use of toggles "U,u" and "K,k"). The non-
volatile memory can store up to fifty, 10 digit or 7 digit phone numbers. Phone numbers are entered using the
"Nnnnnnnnnnn" command discussed in Data Entry Command section, see section below.
QDelete all phone numbers in memory
This command deletes all telephone numbers stored in non-volatile memory.
RReset System
This command resets the operating system and resets all toggles to upper case values. It does not reset the line
number or the baud rate. The time clock can be reset by using the "Zmmddhhmm" command (see details below),
or by capturing a good Caller ID signal.
Data Entry Commands Discussion
N000000770n<CR> Set starting line number count of unit.
When multiple units are used on the same system, units can be set to report the matching phone line numbers they
represent. For example, when 2 four line units are connected to monitor 8 total lines. The second unit needs to be
set to report lines 5,6,7, and 8. Connect to the second unit and send N0000007705<CR>. The last digit, 5 tells the
first line to report data as line 05. Consequently, the second channel will report as line 6, the third as line 7, and so
on. If you set an eight line unit to line 5, it would report data on lines 5-12.
Nnnnnnnnnnn <CR> Add phone number to memory *Only available on select units.
This command allows telephone numbers to be entered into non-volatile memory. These numbers can be used to
either block or pass calls to the output phone jacks. See section on use of toggles "U,u" and "K,k". The on-board
memory can store as many as thirty, phone numbers. Phone numbers entered into memory must be between 7 and
12 digits in length. Any attempt to enter a number less than 7 or more than 12 digits long will cause the unit to send
back a question mark and the number will not be accepted by the memory. Ten digit numbers are common for the
US and Canada. Less than and more than 10 digit numbers are common in other countries.
If you want to add “Private” and “Out-of-Area” and callers to the memory list, refer to the following:
For Private Callers, enter: N77<CR>
For Out-of Area Callers, enter: N66<CR>

9
Wnn <CR> Block (or pass) call on line nn *Only available on select units.
This command should be sent after the Caller ID signal and before the second ring. This way the call can be
blocked (or passed) based on the Caller ID information. If toggle "B" is set, the first ring will be blocked. The
application program determines whether the remaining rings should be blocked or passed. Please note: Normally,
toggle "K" is set. This allows all calls to pass until a "W" is sent by the application (or an internal command is sent
by the hardware memory). In a secure phone line application, the toggle "k" might be set in order to block all calls
until the "W" command is sent (or the internal command is sent by the hardware memory).
Zmmddhhmm <CR> Set date and time on internal clock
This allows the programmer to set the internal clock on the unit. Since there is no battery backup on board, once
power is removed from the unit, the internal clock resets to "00/00 00:00:00". This command may never have to be
used, due to the following: On the first incoming call with Caller ID and a good checksum, the internal time clock
will be set to the time sent in the Caller ID signal. On every call thereafter, the internal clock is reset to the Caller
ID time. The format for time entry using the "Z" command is mm (month), dd (day), hh (hour), and mm (minute).
Detail Mode Output Discussion
If the toggle "d" is set, all detail information on each call is sent immediately. The detail events include Ring, On
Hook, Off Hook, and Hook Flash. Each event reported by the unit starts with the line number, followed by the
abbreviation of the event, and finally, the date and time. The date and time is offset 13 characters to the right so that
it will appear in the same offset position as the date and time in the comprehensive format. Also, the time is
displayed in a military format so that the time of the event can be determined exactly. An example is shown below.
01 R 11/07 07:43:52 Ringing on line 1 at 7:43 AM
01 F 11/07 17:45:04 Off Hook on line 1 at 5:45 PM
04 N 11/07 10:46:23 On Hook on line 4 at 10:46 AM
Error Condition Discussion
A question mark (?) is returned on most any input that is not valid. Also, any non-interpretable characters contained
within a Caller ID string will be sent as a question mark. Most likely the checksum will be calculated as "bad".
Format Discussion
Inbound Calls
The format for an inbound call is shown in Fig. 2a. The data string can be, 63 characters in length, including the
leading $sign (if the "c" toggle is set), spaces, the carriage return, and line feed characters at the end of the data.
The line number always precedes the data string. In this example, data from line 3 is discussed.
The Inbound/Outbound and Start/End of Call Indicators use I/O and S/E respectively. Remember that the unit can
be set to send data on inbound and outbound calls or only on inbound calls (toggle "O,o"). Also, the data stream
can be sent at the start of the call, end of the call, or both (see toggles "A,a" and "S,s").
Since the duration of the call is sent only after the call is complete, toggles "O,o" and "S,s" must be set so the unit
will send data at the end of the call.
The Caller ID string sent by the telephone company always contains a checksum. The unit compares its checksum
with the checksum sent by the phone company and displays the either "G" (Good) if the two match or "B" (Bad) if
they do not match. The application programmer may elect to ignore this indicator and determine the validity of the
data after reading in the data stream.
The next field contains both the number of rings delivered by the telephone company before the call was answered
and the type of ring. A service called Distinctive Ring or Ring Master is offered to customers in many areas. It
allows up to 4 telephone numbers to be routed to one phone line. Each phone number dialed causes the telephone to

10
ring differently. The unit will determine which ring pattern is delivered and mark it as A,B,C, or D. Please note the
number of rings is always zero except when the data is delivered at the end of an incoming call.
The date and time information is sent by the phone company as part of the Caller ID signal on each incoming call.
For each incoming call with a good checksum, the time and date information will be used to reset the internal real
time clock to match the telephone company's clock.
The phone number field for the comprehensive format is 12 characters and left justified. Dashes are inserted when
the "C" toggle is set. If the "c" toggle is set the dashes are removed (and a leading $sign is inserted in front of the
data string). In some areas of the US and Canada, no area code is sent for calls within the local calling area. In this
case, the unit will send the 7 digit phone number, left justified. If the application software will be used in different
areas of the country, it is suggested that the local area code reside in the software to be appended to any 7 digit
number delivery to make it a 10 digit number.
In many areas, the name of the caller will be delivered along with the number. This service is sometimes referred to
as Caller ID Plus, Caller ID Deluxe, or Enhanced Caller ID. If delivered by the local telephone company, the name
will reside in a left justified, 15 character field, following the number field. Names for private residences are
usually sent last name first, space, first name, space, and then middle initial. Business names are most often sent as
they are listed, but if they over 15 characters, truncation will occur. Caller ID specifications allow for the delivery
any characters or symbols.
Outbound Calls
Figure 2b shows the format for outbound calls. Unlike Fig. 2a,toggle "c" is set. (Remember toggle "c" places a $
sign before the data stream and removes dashes in the phone number field.)
The outbound indicator displays Oand the Start/End indicators are the same as inbound calls. The duration of the
call is only sent at the end of the call and is displayed in seconds. The checksum indicator is always "good" and the
number of rings remains "zero" at all times. The date/time displayed is the date/time that the call was initiated and
does not change at the end of the call. The unit tries to be as "smart" as possible in determining where to place
outbound dialed digits. Digits dialed are placed in either the number or name field. The algorithm below explains
where the unit places digits.
All digits dialed within 2 seconds of each other will be displayed beginning in the number field. If more than 10
digits are dialed, the additional digits will be displayed in the name field. The "Start" data string for outbound calls
will be sent immediately after a period of 2 seconds when no digits are dialed. Any digits dialed after this 2 second
interval will be displayed in the name field and will be displayed only at the end of the call. In the example in Fig.
2a, second data string, the 800 number was originally dialed. After a few rings, an automated answering device
answered the call. The caller then dialed additional digits responding to voice menu selections.
An exception to this 2 second rule provides for 7 and 10 digit numbers to be reported in the number field on the end
record, regardless of the interval between dialed digits.

NOTE: All fields left justified. 1 space separates each field.
NOTE: All fields left justified. 1 space separates each field.
11
Phone Number Field, 14 Characters,
Left Justified. First 10 digits of
phone number dialed are displayed.
Phone Number Field, 14 Characters,
Left Justified. First 10 digits of
phone number dialed are displayed.
(Note: No dashes separate phone
number in this example since
lower case "c" toggle is set.)
(Note: No dashes separate phone
number in this example since
lower case "c" toggle is set.)
Checksum
Indicator
Always
Good for
Outbound
Calls
Checksum
Indicator
Always
Good for
Outbound
Calls
Date Field
(Day, Month)
Date Field
(Day, Month)
Inbound/
Outbound
& Start or
End of call
Indicators
Inbound/
Outbound
&Start or
End of call
Indicators
Preceding
$ sign for
"key on"
Character
(Toggle "c")
Preceding
$sign for
"key on"
Character
(Toggle "c")
If digits are dialed after
>2 second pause, they will
be displayed in this field.
Field is 15 characters
long and is left justified.
If digits are dialed after
>2 second pause, they will
be displayed in this field.
Field is 15 characters
long and is left justified.
Type &
Number
of rings
is always
zero for
outbound
calls
Type &
Number
of rings
is always
zero for
outbound
calls
Duration
of call in
seconds
(always
zero at
start
of call)
Duration
of call in
seconds
(always
zero at
start
of call)
Line
Number
Preset
by user.
Line
Number
Preset
by user.
Time including
AM/PM Indicator
(Note: This is the time
that the call began. It
does not change when
delivered at the end
of the call.)
Time including
AM/PM Indicator
(Note: This is the time
that the call began. It
does not change when
delivered at the end
of the call.)
Name Field, 15 Characters, Left
Justified. Carriage Return &
Line Feed are sent after field
Name Field, 15 Characters, Left
Justified. Carriage Return &
Line Feed are sent after field
Type of
ring and
number
of rings.
(always
zero at
start
of call)
Type of
ring and
number
of rings.
(always
zero at
start
of call)
Duration
of call in
seconds
(always
zero at
start
of call)
Duration
of call in
seconds
(always
zero at
start
of call)
Line
Number
Preset
by user.
Line
Number
Preset
by user.
Carriage Return
& Line Feed
2 Characters
Carriage Return
& Line Feed
2 Characters
Inbound/
Outbound
& Start or
End of call
Indicators
Inbound/
Outbound
&Start or
End of call
Indicators
Checksum
Indicator
G (Good)
or B (Bad)
Checksum
Indicator
G(Good)
or B (Bad)
Date Field
(Day, Month)
Date Field
(Day, Month)
Phone Number Field, 14 Characters,
Left Justified. (Note: Some areas in
US & Canada deliver only a 7 digit
number. No area code is sent for
calls within local area code)
Phone Number Field, 14 Characters,
Left Justified. (Note: Some areas in
US & Canada deliver only a 7 digit
number. No area code is sent for
calls within local area code)
Time including
AM/PM Indicator
(Note: This is the time
that the call began. It
does not change when
delivered at the end
of the call.)
Time including
AM/PM Indicator
(Note: This is the time
that the call began. It
does not change when
delivered at the end
of the call.)
Figure 2aFigure 2a
Figure 2bFigure 2b
Data Output FormatData Output Format
Outbound Call:
R
C
F
L
R
CF
L
$03 O S 0000 G 00 09/26 11:28 AM 8002404637$03 O S 0000 G 00 09/26 11:28 AM 8002404637
$03 O E 0276 G 00 09/26 11:28 AM 8002404637 3456$03 O E 0276 G 00 09/26 11:28 AM 8002404637 3456
Inbound Call:
R
CF
L
R
CF
L
03 I S 0000 G 00 09/26 11:28 AM 770-263-7111 CALLERID.COM03 I S 0000 G 00 09/26 11:28 AM 770-263-7111 CALLERID.COM
03 I E 0276 G B3 09/26 11:28 AM 770-263-7111 CALLERID.COM03 I E 0276 G B3 09/26 11:28 AM 770-263-7111 CALLERID.COM
Carriage Return
& Line Feed
2 Characters
Carriage Return
& Line Feed
2Characters

12
DISCUSSION OF PRIVATE AND OUT-OF-AREA CALLERS
Two unique messages can be delivered as designated by Caller ID specifications. An "Out-of-Area" message
occurs if the information on a caller is unavailable. This is true for most cellular calls and is sometimes the case
when the call originates outside the telephone company's Local Access Transmission Area (LATA). This loosely
translates to long distance calls.
A "Private" message is sent for callers who have blocked their Caller ID number from being transmitted to the
called party. Blocking can occur either on a per call or on a per line basis. For per call Caller ID blocking, a code
(*67) can be dialed before each call is made. In some areas, customers can request that all calls from their line be
permanently blocked. In either case, the recipient of calls from these numbers will receive a "Private" or
"Anonymous" indication from their Caller ID device.
Private and Out-of-Area messages can occur in either the number or name fields if number and name service is
being delivered. For example, some telephone companies allow customers to have private numbers, but names are
sent. In another case, the number might be sent, but the name of the customer is Out-of-Area. This would most
likely happen if the customer had just received new service and the telephone company's database had not been
recently updated. It is best that your application software handles any combination of number, name, private, and
out-of-area messages in both the number and name fields.
SPECIFICATIONS
Supply Voltage: 9 VDC, center negative
Supply Current: Less than 250 mA
Loop Current Draw: Less than 1 mA
Loop Voltage: 30 to 105 VDC
Ringing Voltage: 60 to 130 VAC
Insertion Loss: Less than 0.3 dB
Voltage Drop: 2.7 VDC at 20 mA loop current
Dimensions: 8.0” W x 2.0” H x 6.25” D
Ringer Equivalence: (REN) 0.1 B

13
MANUFACTURE’S INFORMATION
CallerID.com
5680 Oakbrook Parkway, Suite 150
Norcross, GA 30093
Sales (800) 240-4637
Customer Service (770) 263-7111
Web Site www.callerid.com
WARRANTY INFORMATION
CallerID.com will repair this product with new or rebuilt parts, free of charge, when returned postage prepaid to the
CallerID.com repair facility in Norcross, GA within 1year from the date of original purchase.
This warranty is extended only to the original purchaser. A purchase receipt or other acceptable proof of purchase
date will be required before warranty service is rendered.
This warranty covers failures due only to defects in materials or workmanship occurring during normal use. It does
not cover damage which occurs in shipment; failures which are caused by products not manufactured by
CallerID.com; failures which result from accident, misuse, abuse, neglect, mishandling, misapplication, alteration,
modification or unintended use of product; service by anyone other than an authorized CallerID.com repair facility;
or damage attributed to an act of God. Lightning is considered an act of God.
CallerID.com makes no other warranty, either expressed or implied, with respect to this product.
If a problem develops concerning this product, contact your local dealer or CallerID.com directly for a Return
Material Authorization (RMA) number. A RMA number is required for all returns.

14
Appendix A - International Caller ID formats and Internal Jumper Settings
Caller ID is a data signal generated by the phone company's central office (CO). The type of Caller ID signal that
will be sent by a phone company will depend on the type of equipment in use at their CO.
Caller ID signaling formats vary throughout the world. At present, there is four basic formats with local variations
of each format type. By setting the proper combination of internal jumpers (shunts), the Whozz Calling? unit can
capture any of these four basic Caller ID signaling formats. The four basis formats are:
1. Bellcore 202 - USA Type. Sent in many countries. FSK sent between the 1st and 2nd ring cycle.
2. British Telecom – Only sent in United Kingdom. FSK sent before the 1st ring cycle.
3. ETSI - Sent primarily in Western Europe. FSK sent after very short 1st ring.
4. DTMF - Sent in regions that use older CO equipment. DTMF (touch-tones) sent before the 1st ring.
NOTE: Refer to the table in Fig. A1 for more information on known formats in particular countries.
The standard factory setting for Whozz Calling? Deluxe units is to capture Bellcore 202 type Caller ID. If the
signaling format was determined in advance of the unit being shipped, the unit may be set for an alternate format.
In order to configure the unit to a different Caller ID signaling format, the top of the enclosure must be removed and
shorting jumpers moved on the circuit board. Use the following steps and refer to Fig. A1 on the next page.
1. Remove power to the unit.
2. Remove the top of the enclosure by first removing the two Phillips head screws on the bottom of the unit.
3. Slide the top of the enclosure off.
4. Locate the shorting jumpers on the circuit board used for Caller ID signaling formats using Fig. A1.
5. Slide off the appropriate jumper(s) and reconnect as per the table below the diagram.
6. Replace the top of the enclosure and replace the two screws.

Fig. A1 - Configuring Unit for Different Caller ID Signaling FormatsFig. A1 - Configuring Unit for Different Caller ID Signaling Formats
15
Configuration Table for Caller ID Signaling Formats
JP11 JP10
FU
DB
JP11 JP10
FU
DB
JP11 JP10
FU
DB
USA, Canada, most of Mexico, most of the Caribbean,
Panama, Argentina, Australia, New Zealand, Hong Kong,
Singapore, , Israel, Malta and other areas using
CLASS compatible central office switches
China
FSK signal between the
1st and 2nd ring. Time
& date sent, Caller ID
name optional.
FSK signal before 1st
ring or after very short 1st
ring. Time & date sent,
Caller ID name optional.
DTMF tones sent before
1st ring. No time & date,
no Caller ID name, only
Caller ID number sent.
Brazil, Uruguay, Guatemala, and many other Central and
South American countries. Denmark, Holland, Iceland,
Sweden, India, Saudi Arabia, Kuwait, and other Middle
Eastern countries.
United Kingdom, France, Germany, Spain, Italy,
Norway,
U.A.E.,
South Africa, Turkey, Japan and any other countries
that adopted the ETSI standard.
Belcore 202
DTMF
(touch-tone)
British
Telecom
and ETSI
Jumper
Positions
Caller ID
Signaling Characteristics Countries/Regions Known
Jumpers on JP11 and JP10
configure the unit for various
Caller ID signaling formats
around the world.
(The jumper positions shown
here configure the unit to the
Belcore 202 type Caller ID
signaling delivered in
North America, and other
countries where CLASS
compatible central office
switches are installed).
TM

16
Appendix B - On and Off-Hook Detection (Voltage vs. Current)
The Whozz Calling? Deluxe detects when the phone is on-hook and off-hook. This allows the unit to determine the
length of each phone call and report this detailed information to the software. Telephone monitoring equipment can
detect the occurrence of the On Hook and Off Hook status of the phone line by two methods. It can either sense the
voltage on the phone line itself or sense current flow on a phone line passed through the equipment.
Voltages on incoming central office (CO) phone lines are consistent among all branches throughout a physical
location (building). If the voltage levels are in standard range, a Deluxe unit functioning in a voltage detection
mode is able to sense On and Off Hook on any branch in the building. The obvious advantage to this detection
scheme is that the monitoring equipment can be connected in parallel to the CO lines. Your unit comes from the
factory set to voltage detection mode because, in most locations, this detection scheme works properly.
Current on phone lines only flows to the telephone device that is Off Hook. Monitoring equipment that senses On
and Off Hook by means of current flow must be connected between the phone company’s incoming line and the
device(s) that goes Off Hook. The current will flow through the monitoring equipment to the Off Hook device.
With this detection scheme, any telephone device that makes or receives phone calls must be attached in series (i.e
to the output jacks) “behind” the monitoring equipment.
VOLTAGE DETECTION CIRCUITRY AND TELEPHONE LINES
In order to sense the voltage on the phone line, the unit’s circuitry must draw a small amount of current from the
phone line. The current draw is very small (70 μA, similar to a voltmeter), and is drawn when the phone line is On
Hook. The telephone company’s amplifier supplying the power to your location may not be able to supply this
current and still keep the On Hook voltage level within the standard range. This occurs primarily in older
residential and commercial locations. An unsophisticated telephone company repair technician may diagnose this
small current draw by the unit as a “short” on the line. Therefore, the telephone company will not address the
shortcoming of their supply amplifier. If this situation occurs, the unit cannot be used in the voltage detection
mode, it must be reconfigured to the current detection mode.
RECONFIGURING UNIT TO CURRENT DETECTION MODE
In order to configure the unit to a different Caller ID signaling format, the top of the enclosure must be removed and
shorting jumpers moved on the circuit board. Use the following steps and refer to Fig. B1 or Fig. B2 following.
1. Remove power to the unit.
2. Remove the top of the enclosure by first removing the two Phillips head screws on the bottom of the unit.
3. Slide the top of the enclosure off.
4. Locate the shorting jumpers on the circuit board (2 per channel and 1 main jumper) used for configuring
the unit to Current Detection using Fig. B1
5. Slide off the appropriate jumper(s) and reconnect as per lower diagrams based on the Version number of
the Printed Circuit Board (PCB).
- Use Diagram B1 for PCB Version 6,7,or8.
- Use Diagram B2 for PCB Version 10 and above.
6. Replace the top of the enclosure and replace the two screws.

Voltage Detection - 8 Channel Shunts to the Rear of Unit, Main shunt to Right
Current Detection 8 Channel Shunts to the Front of Unit, Main shunt to Left
Fig. B1 - Voltage and Current Detection Configuration (4 Line Model -PCB Version 6,7,or 8)
17
Callerid.com / 4-Line WC V-7 Callerid.com / 4-Line WC V-7
Unit is configured for
Voltage Detection when
all 9 shunts are
connected as shown.
Unit is configured for
Current Detection when
all 9 shunts are
connected as shown.
Other manuals for Whozz Calling Deluxe 2
1
This manual suits for next models
2
Table of contents
Popular Recording Equipment manuals by other brands

Lorex
Lorex LW2300 SERIES quick start guide

pigtronix
pigtronix Infinity looper user guide

Solid State Logic
Solid State Logic VHD+ user guide

Car Solutions
Car Solutions IW03C-SB instruction manual

Sennheiser
Sennheiser EW 112 G2 operating instructions

Universal Audio
Universal Audio Apollo x4 Hardware manual

Panasonic
Panasonic SVSR100 - SD AUDIO RECORDER operating instructions

auto maskin
auto maskin Marine Pro. 400 Series installation manual

Fostex
Fostex 8333 owner's manual

Opvimus
Opvimus COMPACT-E operating instructions

Harman
Harman BSS Soundweb London BLU-USB installation guide

JBL
JBL SDR-35 quick start guide