The fields of the string in Figure 5 are as follows:
151241092: YYMMTTDDD, where YYMM is the year and month of manufacture, TT is the type where the first
digit is the number of anchors + 1 (e.g. 4 = 3 anchors), and DDD is a manufacturing ID.
D3EXTO: Type of instrument where the numeric value indicates the number of positions.
41: First digit is number of channels + 1, second digit is type where 1=displacement, 5=load.
23.0: Head temperature in degrees C.
155.00: Absolute displacement in millimeters. (First value is sensor closest to head.)
mm: Units of displacement.
MultiLogger Configuration
Several gage types were added to support reading the d-Exto. Contact Canary Systemsif your installation of
software does not list the required gage types.
Note: The d-Exto communicates via RS-485, however it does not support any networking, so multiple d-Exto nodes
cannot use the same cable for communications. Separate RS-485/RS-232 adaptors and separate COM port
connections are required for each d-Exto. This limits the number of sensors that can be supported be each datalogger.
For the Campbell CR1000 MCU the maximum would be 5, utilizing COM1-COM4 and the RS232 port. For the
Campbell CR800 MCU the maximum would be 3, utilizing COM1-COM2 and the RS232 port.
Direct Connect Channel Configuration
Typically, the Direct Connect Channel Configuration would be used for configuring the d-Exto’s. However,
since Direct Connect channels are limited to 16, and each position requires a channel, if the system must read
more than 2 d-Exto’s with 6 positions each, there are insufficient channels. In that case, use a multiplexer
configuration, the following section will detail that configuration.
Add a Campbell CR1000 MCU to the network, double-click to load the Logger form. Then, select the Direct
Connect option on the Program tab, as shown in Figure 6.
(Figure 6)
Canary Systems
is a registered trademark of Canary Systems, Inc.