Table 8 — Fan Rpm at Motor Pulley Settings* (Factory-Supplied Drives)
UNIT
50HJQ MOTOR PULLEY TURNS OPEN
0
1
⁄
2
11
1
⁄
2
22
1
⁄
2
33
1
⁄
2
44
1
⁄
2
55
1
⁄
2
6
014
(208/230, 460 v) † † 1132 1105 1078 1051 1024 997 970 943 916 889 862
014
(575 v) 1462 1436 1410 1384 1358 1332 1305 1279 1253 1227 1201 — —
016 † † 1010 989 968 947 926 905 883 862 841 820 799
*Approximate fan rpm shown.
†Due to belt and pulley size, pulley cannot be set to this number of
turns open.
NOTE: To run units at speeds not listed, field-supplied drives are
required.
HEATING, UNITS WITHOUT ECONOMIZER — With unit
main power on, set thermostat at HEAT position and desired
room temperature. Set fan switch at AUTO. (on demand) or
ON (continuous) position.
On a drop in room temperature, heating contact no. 1 in
the thermostat closes, energizing heat relay (HR), reversing
valve relay (RVR), reversing valve solenoids (RVS1 and RVS2)
and compressor no. 2 contactor. Compressor (50HJQ014) or
compressor no. 2 (50HJQ016) and indoor and outdoor fan
motors start. If the 5-minute CTD on the DB is satisfied,
then compressor no. 1 contactor is energized and compres-
sor no. 1 will start.
On units equipped with electric heat, when additional heat
is needed, heating contactor no. 2 in the thermostat closes,
energizing W2.
HEATING, UNITS WITH ECONOMIZER — With unit main
power on, set thermostat at HEAT position and desired room
temperature. Set fan switch at AUTO. (on demand) or ON
(continuous) position.
On a drop in room temperature, heating contact no. 1 in
the thermostat closes, energizing heat relay (HR), reversing
valve relay (RVR), reversing valve solenoids (RVS1 and RVS2)
and compressor no. 2 (50HJQ016) contactor. Compressor
no. 2 (50HJQ016) and indoor and outdoor fan motors start.
If the 5-minute compressor time delay (CTD) on the defrost
board (DB) is satisfied, then compressor (50HJQ014) or com-
pressor no. 1 (50HJQ016) contactor is energized and com-
pressor will start. The outdoor-air damper stays at vent po-
sition while the indoor fan is operating.
On units equipped with electric heat, when additional heat
is needed, heating contactor no. 2 in the thermostat closes,
energizing W2.
DEFROST CYCLE — When the temperature of the out-
door coil drops below 28 F as sensed by the defrost ther-
mostat (DFT1 or DFT2), the defrost timer starts. At the end
of a timed period (factory set at 30 minutes, field set at 50
or 90 minutes), the defrost cycle will begin. The defrost board
energizes terminals O and W2, energizes the defrost relay
(DR), deenergizes the reversing valve solenoids (RVS1 and
RVS2), and energizes the electric heat. The outdoor-fan mo-
tor will stop.
The unit continues to defrost either until the coil tempera-
ture as measured by DFT1 or DFT2 reaches 65 F, or until
unit completes a 10-minute defrost cycle.
During the defrost mode, when a circuit defrosts, RVS will
oscillate between heating and cooling modes until defrost
mode is complete. This will prevent the head pressure from
getting too high.
At the end of the defrost cycle, the electric heaters (if ap-
plicable) will be deenergized, the reversing valve solenoids
will be energized, and the outdoor fans will start.
A freeze protection thermostat (FPT) is located on the in-
door coil. It detects frost build-up and turns off the com-
pressor(s), allowing the coil to clear. Once frost has melted,
the compressor can be reenergized.
AUTOMATIC CHANGEOVER — When the system selec-
tion switch is set atAUTO. position, unit automatically changes
from heating operation to cooling operation when the tem-
perature of the conditioned space rises to the cooling lever
setting. When the temperature of the conditioned space falls
to the heating lever setting, unit automatically changes from
cooling to heating operation (witha3Fdeadband in
between).
CONTINUOUS AIR CIRCULATION — Turn unit power
on. Set system control at OFF position. Set fan switch at ON
position. The indoor-fan contactor is energized through the
thermostat switch and the indoor fan runs continuously.
CYCLE-LOC™ PROTECTION — If unit operation is in-
terrupted by an open high-pressure switch, low-pressure switch,
indoor coil freezestat, or by compressor internal line-break
device (overcurrent or overtemperature), and compressor is
calling for either cooling or heating, Cycle-LOC protection
device simultaneously locks out unit and lights a warning
light on the thermostat. Restart the unit by manually turning
thermostat to OFF and then to ON position. If any of the
protective devices opens again, the unit continues to lock
out until corrective action is taken.
NOTE: If the unit fails to operate due to compressor over-
current condition, restart by manually resetting circuit break-
ers at the unit. Restart cannot be accomplished at the room
thermostat.
EMERGENCY HEAT — If compressor is inoperative due
to a tripped safety device (high or low pressure, indoor coil
freezestat, overcurrent, or overtemperature), the Cycle-LOC
device locks out the compressor and lights a warning light
on the room thermostat. When the switch is on (thermostat
is set to the EM HT position), compressor circuit and out-
door thermostats are bypassed, and the second stage of ther-
mostat energizes the indoor blower and the electric resistance
heaters.
16