
Forced Defrost
On 25HNA6 models with non-conmmnicating (non-Infinity)
control, forced defrost can be initiated by manually shorting the
2-pin header labeled FORCED DEFROST (see Fig 6) on the
control board for 5 seconds then releasing.
On 25HNA6 and 25HNA9 with communicating (Infinity) control,
forced defrost is initiated with the User Interface.
On all models, during a Forced Defrost:
• If coil temperature is at defrost temperature of 32°F (0°C), and
outdoor air temperature is below 50°F (10°C), a full defrost
sequence will occur.
• If coil temperature or outdoor air temperature does not meet the
above requirements, an abbreviated 30 second defrost will occur.
Quiet Shift
Quiet Shift is a field-selectable defrost mode which may eliminate
occasional noise that could be heard at the start of the defrost cycle
and restarting of the heating cycle. On 25HNA6 models with
non-conmmnicating system, this feature nmst be enabled by
selecting the 3rd position of the 3-position dip switch. For
25HNA6 and 25HNA9 models with communicating (Infinity)
systems, it must be enabled at the User Interface. When activated,
the following sequence of operation will occur. Reversing valve
will energize and compressor will turn off for 30 seconds, then turn
back on to complete defrost. At the end of the defrost cycle, the
reversing valve de-energizes, compressor will turn off for another
30 seconds, and the fan will turn off for 40 seconds, before starting
in the heating mode.
Liquid-Line Solenoid Accessory
In heat pump long-line applications, a liquid-line solenoid is
required to control refrigerant migration in the heating mode. The
solenoid should be installed near the outdoor unit with the arrow
facing the outdoor unit. This is the direction of flow control. See
application manual for long-line application details.
Accessory Liquid Solenoid with Infinity Communicating
Control: When using the Infinity Control, the liquid-line solenoid
output is provided at the YI connection. Connect the solenoid as
shown in the wiring label diagram. This is a 24vac output that is
energized whenever the compressor is energized. It closes, in the
compressor off mode, to prevent refrigerant migration into the unit
through the liquid-line.
On 25HNA6 Models with Accessory Liquid Solenoid Using a
Non-Communicating Thermostat: The liquid solenoid is
connect to the YI and C terminal connections. The liquid solenoid
closes, in the compressor off mode, to prevent refrigerant migration
into the unit through the liquid-line.
Check Charge
All 25HNA6 units must be charged in high stage only.
Factory charge amount and desired subcooling are shown on unit
rating plate. Charging method is shown on information plate inside
unit. To properly check or adjust charge, conditions must be
favorable for subcooling charging. Favorable conditions exist
when the outdoor temperature is between 70°F and 100°F
(21.11°C and 37.78°C), and the indoor temperature is between
70°F and 80°F (21.11°C and 26.67°C). Follow the procedure
below:
Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge
by adding or removing 0.6 oz/ft of 3/8 liquid line above or below
15ft (4.57 m) respectively.
For standard refrigerant line lengths (80 ft/24.38 m or less), allow
system to operate in cooling mode at least 15 minutes. If conditions
are favorable, check system charge by subcooling method. If any
adjustment is necessary, adjust charge slowly and allow system to
operate for 15 minutes to stabilize before declaring a properly
charged system.
If the indoor temperature is above 80°F (26.67°C), and the
outdoor temperature is in the favorable range, adjust system charge
by weight based on line length and allow the indoor temperature to
drop to 80°F (26.67°C) before attempting to check system charge
by subcooling method as described above.
If the indoor temperature is below 70°F (21.11°C), or the outdoor
temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) only. Charge level should then
be appropriate for the system to achieve rated capacity. The charge
level could then be checked at another time when the both indoor
and outdoor temperatures are in a more favorable range.
NOTE: If line length is beyond 80 ft (24.38 m) or greater than 20
ft (6.10 m) vertical separation, See Long Line Guideline for
special charging requirements.
Heating Check Chart Procedure
To check system operation during heating cycle, refer to the Heat
Pump Charging Instructions label on outdoor unit. This chart
indicates whether a correct relationship exists between system
operating pressure and air temperature entering indoor and outdoor
units. If pressure and temperature do not match on chart, system
refrigerant charge may not be correct. Do not use chart to adjust
refrigerant charge.
NOTE: In heating mode, check refrigerant charge only when
pressures are stable. If in doubt, remove charge and weigh in
correct refrigerant charge.
NOTE: When charging is necessary during heating season, charge
must be weighed in accordance with unit rating plate, ---0.6 oz./ft.
of 3/8-in. liquid-line above or below 15 ft., respectively.
EXAMPLE:
To calculate additional charge required for a 25-ft. line set:
25 ft. - 15 ft. = 10 ft. X 0.6 oz./ft. = 6 oz. of additional charge.
MAJOR COMPONENTS
2-Stage Control Board
The HP control board controls the following flmctions:
• High and low stage compressor contactor operation
• Outdoor fan motor operation
• Reversing valve operation
• Defrost operation
•Low ambient cooling
• Crankcase heater operation
• Compressor external protection
• Pressure switch monitoring
• Time Delays
• On 25HNA6 models, high- and low-stage start relay and
capacitor operation (Bristol compressor only)
Field Connections
On 25HNA6 models with non-conmmnicating (non-Infinity)
system, the two-stage control receives 24vac low-voltage control
system inputs through the R, C, Y1, Y2 and O connections located
at the bottom of the control board (see Fig. 6.) On a
non-communicating system, output Wl is connected at the bottom
of the control board for auxiliary heat.
On 25HNA6 models with conmmnicating system and all 25HNA9
models, use the ABCD Infinity connections.
Two Stage Compressor
The two stage compressor contains motor windings that provide
2-pole (3500 RPM) operation. For two-stage compressor, refer to
Table 5 for correct winding resistance.
Compressor Internal Relief
The compressor is protected by an internal pressure relief (IPR)
which relieves discharge gas into the compressor shell when
differential between suction and discharge pressure exceeds
10