manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Heat Pump
  8. •
  9. Carrier Weathermaster 38HQ Dimensions and installation guide

Carrier Weathermaster 38HQ Dimensions and installation guide

This manual suits for next models

2

Other Carrier Heat Pump manuals

Carrier Weathermaster III 38HQ Dimensions and installation guide

Carrier

Carrier Weathermaster III 38HQ Dimensions and installation guide

Carrier 19PV550 Manual

Carrier

Carrier 19PV550 Manual

Carrier Comfort 50VT-K User manual

Carrier

Carrier Comfort 50VT-K User manual

Carrier 50ZHK Instruction Manual

Carrier

Carrier 50ZHK Instruction Manual

Carrier 38YSA Instructions and recipes

Carrier

Carrier 38YSA Instructions and recipes

Carrier 50JZ 024-060 Assembly Instructions

Carrier

Carrier 50JZ 024-060 Assembly Instructions

Carrier 50HX Guide Instructions and recipes

Carrier

Carrier 50HX Guide Instructions and recipes

Carrier 38MARB User manual

Carrier

Carrier 38MARB User manual

Carrier CPCRKHTR003A00 User manual

Carrier

Carrier CPCRKHTR003A00 User manual

Carrier Infinity 25HNB6 User manual

Carrier

Carrier Infinity 25HNB6 User manual

Carrier 38BNE018-036 User manual

Carrier

Carrier 38BNE018-036 User manual

Carrier 38BYC Series Operation manual

Carrier

Carrier 38BYC Series Operation manual

Carrier 50DQ Operation manual

Carrier

Carrier 50DQ Operation manual

Carrier Weathermaster III 38HQ Dimensions and installation guide

Carrier

Carrier Weathermaster III 38HQ Dimensions and installation guide

Carrier 38QN Instructions and recipes

Carrier

Carrier 38QN Instructions and recipes

Carrier HRVXXLVU User manual

Carrier

Carrier HRVXXLVU User manual

Carrier GT-PX Quick start guide

Carrier

Carrier GT-PX Quick start guide

Carrier Aquazone 50HQL Dimensions and installation guide

Carrier

Carrier Aquazone 50HQL Dimensions and installation guide

Carrier 50SZ Series User manual

Carrier

Carrier 50SZ Series User manual

Carrier 38QW User manual

Carrier

Carrier 38QW User manual

Carrier 38EYG Instructions and recipes

Carrier

Carrier 38EYG Instructions and recipes

Carrier 38MURA User manual

Carrier

Carrier 38MURA User manual

Carrier 50RQ Operation manual

Carrier

Carrier 50RQ Operation manual

Carrier 51QC User manual

Carrier

Carrier 51QC User manual

Popular Heat Pump manuals by other brands

Daikin RXL12QMVJU Service manual

Daikin

Daikin RXL12QMVJU Service manual

AIREDALE BluCube CUR092V16-1CO-0 Installation and maintenance manual

AIREDALE

AIREDALE BluCube CUR092V16-1CO-0 Installation and maintenance manual

Calyenty RBH 125 Customer's manual

Calyenty

Calyenty RBH 125 Customer's manual

GRE HPGI50 owner's manual

GRE

GRE HPGI50 owner's manual

Hayward SUMHEAT HP5131DT3 Installation instructions manual

Hayward

Hayward SUMHEAT HP5131DT3 Installation instructions manual

REMKO SQW 400 Electrical wiring

REMKO

REMKO SQW 400 Electrical wiring

Sanyo SAP120FCH Service manual

Sanyo

Sanyo SAP120FCH Service manual

Daikin EHYHBH05AA Operation manual

Daikin

Daikin EHYHBH05AA Operation manual

Panasonic WH-SDF03E3E5 Design handbook

Panasonic

Panasonic WH-SDF03E3E5 Design handbook

Airxcel 45000 Series Installation, operation and maintenance instructions

Airxcel

Airxcel 45000 Series Installation, operation and maintenance instructions

Mitsubishi Electric PUZ-SWM60VAA Service manual

Mitsubishi Electric

Mitsubishi Electric PUZ-SWM60VAA Service manual

Dimplex LI 16I-TUR Installation and operating instruction

Dimplex

Dimplex LI 16I-TUR Installation and operating instruction

Mitsubishi Electric EHSE-YM9EC Service manual

Mitsubishi Electric

Mitsubishi Electric EHSE-YM9EC Service manual

TGM CTV14CN018A Technical manual

TGM

TGM CTV14CN018A Technical manual

Kokido K2O K880BX/EU Owner's manual & installation guide

Kokido

Kokido K2O K880BX/EU Owner's manual & installation guide

Viessmann VITOCAL 300-G PRO Type BW 2150 Installation and service instructions

Viessmann

Viessmann VITOCAL 300-G PRO Type BW 2150 Installation and service instructions

Viessmann KWT Vitocal 350-G Pro Series Installation and service instructions for contractors

Viessmann

Viessmann KWT Vitocal 350-G Pro Series Installation and service instructions for contractors

Weishaupt WWP L 7 Installation and operating instruction

Weishaupt

Weishaupt WWP L 7 Installation and operating instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Number
One
ArConditbning
Maker
r^rrie^
Division
of
^1^
Carrier
Corporation
f
—--
't
w
Weathermaster
III
Dual-Compressor
Heat
Pump
(Outdoor
Coil
Section;
Indoor
Compressor
Section)
INDEX
Page
SAFETY
CONSIDERATIONS
.1
INSTALLATION.3
Step
1
—
Check
Equipment
and
Jobsite
.
3
•
UNPACKAGE
UNITS
•
INSPECT
EQUIPMENT
•
COMPLETE
OR
CONSIDER
SYSTEM
REQUIREMENTS
Step
2
—
install
Outdoor
Coil
Section.4
•
ON
THE
GROUND
•
ON
THE
ROOF
Step
3
—
Install
Indoor
Compressor
Section.5
Step
4
—
install
Indoor
Fan-Coil
and
Electric
Heater.5
Step
5
—
Make
Piping
Connections.5
•
REPLACE
THE
ACCURATER^^
REFRIGERANT
CONTROL
PISTON(S)
•
CONNECT
REFRIGERANT
LINES
Step
6
—
Install
Fan
Control
Package
...
6
Page
Step
7
—
Install
Outdoor
Ambient
Switch.6
Step
8
—
Install
Room
Thermostat,
Outdoor
Thermostat(s)
and
Emergency
Heat
Relay.
8
Step
9
—
Make
Electrical
Connections
...
8
•
INSTALL
A
BRANCH
CIRCUIT
DISCONNECT
PER
N.E.C.
•
ROUTE
LINE
POWER
LEADS
INTO
COMPRESSOR
SECTION
•
CONNECT
GROUND
LEADS
AND
POWER
WIRES
•
CONNECT
POWER
LEADS
FROM
INDOOR
COMPRESSOR
SECTION
TO
OUTDOOR
COIL
SECTION
•
CONNECTCONTROL
WIRING
INITIAL
START-UP.9
SEQUENCE
OF
OPERATION.
9
SERVICE.
11
MAINTENANCE
.
15
SAFETY
CONSIDERATIONS
Installation
and
servicing
of
air
conditioning
equipment
can
be
hazardous
due
to
system
pressure
and
electrical
components.
Only
trained
and
quali¬
fied
service
personnel
should
install,
repair
or
service
air
conditioning
equipment.
Untrained
personnel
can
perform
basic
mainten¬
ance
functions
of
cleaning
coils
and
filters
and
re¬
placing
filters.
All
other
operations
should
be
per¬
formed
by
trained
service
personnel.
When
working
on
air
conditioning
equipment,
observe
precautions
in
the
literature,
tags
and
labels
attached
to
the
unit
and
other
safety
precautions
that
may
apply.
Follow
all
safety
codes.
Wear
safety
glasses
and
work
gloves.
Use
quenching
cloth
for
brazing
opera¬
tions,
Have
fire
extinguisher
available
for
all
brazing
operations.
WARNING:
Before
perforisaisag;
servsoe
or
oa
tant:
OSS'
ijsain
SEWstchfes
mdoor
tnataad
otJt^oor
axat
ITarn
accessory
heater
power
if
'
shod:
cooSd
cause
per-
©
Carrier
Corporation
1979
Form
38HQ-6SI
A
VAPOR
LINE
CONN
(ON
SERVICE
VALVE)
liquid
line
CONN.
(ON
SERVICE
VALVE)
MTG
SLOTS
(USE
ANY
2)
VDIAM
HOLE
FOR
CONTROL
WIRING
DRAINAGE
HOLES
WM
SPACE
RE(3UIRED
FOR
SERVICE
^AIRFLOW
Certified
dimension
drawings
available
on
request
Fig.
1
—
Dimensions
and
Connections,
38HQ
Outdoor
Coil
Section
(Table
2)
Table
1
—
Carrier-Approved
38HQ
Weathermaster
III
Dual-Compressor
Heat
Pump
Systems
INDOOR
1
COMPRESSOR
1
SECTION
OUTDOOR
COIL
SECTION
INDOOR
FAN/COIL
38HQ227
38HQ940
40FS160/28VQ036
38HQ234
38HQ960
40FS200/28VQ042
VAPOR
LINE
CONN
TO
OUTDOOR
COIL
VAPOR
LINE
CON
TO
INDOOR
COIL
14
DIAM
HOLE
FOR
COMPRESSOR
SECTION
LINE
POWER
yC&K;
38HQ
INDOOR
COMPRESSOR
SECTION
i
DIAM
HOLE
FOR
OUTDOOR
COIL
SECTION
LINE
POWER
WIRING
(SEE
ELECTRICAL
DATA
AND
WIRING)
t
DIAM
HOLE
FOR
CONTROL
WIRING
Pill
SPACE
REQUIRED
FOR
SERVICE
Certified
dimension
drawings
available
on
request
Fig.
2
—
Dimensions
and
Connections,
38HQ
Indoor
Compressor
Section
(Table
2)
Table
2
—
Physical
Data
INDOOR
COMPR
SECTION
38HQ227
38HQ234
Operating
Wt
(lbs)
205
225
Dimensions
(ft-in.)
Width
A
2-2-3/32
Depth
B
1-4-3/16
Height
C
1-11-1/8
(add
3/4-in
for
Refrigerant
Fittings
Compressor
no.
1
IV1D2713GM
(46)
MD3413GIVI
(46)
(Oil
Recharge,
oz)
no.
2
MD3413GMi
(46)
MD3413GM
(46)
AccuRater
Size
(in.)
Indoor
no
6
(
0670)
no
7(0760)
Outdoor
no
3
(.0550)*
no
5
(
0635)
Refrig
Conn
(in.)
3/4
3/4
OUTDOOR
COIL
SECTION
38HQ940
38HQ960
Operating
Wt
(lb)
107
125
Dimensions
(ft-in.)
Diameter
A
2-5-1/4
2-5-1/4
Unit
Height
B
2-
8
3-
8
Coil
Height
C
1-11
2-11
Refrig
Conn
Vapor
(in.,
ODF)
3/4,
Compatible
Fitting
Liquid
(in.,
ODF)
3/8,
Flare
Fitting
*Piston
size
shown
is
shipped
with
section
Remove
factory-
installed
piston;
replace
with
size
shown
per
text
2
Table
3
—
Heater
Airflow
Data
■
i
INDOOR
COMPRESSOR
SECTION
HEATER
MINIMUM
ALLOWABLE
SIZE
Airflow
(cfm)
\
Fan
Speed
38HQ227
8
thru
20
kw
(40FQ91
6010
thru
090)
1150
j
Low
38HQ234
10
thru
25
kw
(40FQ920060
thru
1
50)
1550
Low
Table
4
—
Accessories
PART
NO.
38CQ900102
38CQ900122
38CQ900132
38CQ900152
38CQ900172
38HQ900011
38HQ900002
38RQ900012
38CQ900072
38RQ900072
DESCRIPTION
Six
38CQ900081
Low-voltage
Honeywell
Thermostat
(HH07AT071)
and
Thermostat
Subbase
(HH93AZ073)
with
automatic
changeover
Six
38CQ900111
Low-voltage
Honeywell
Thermostat
(HH07AT071)
and
Thermostat
Subbase
(HH93AZ075)
with
manual
changeover
Six
38CQ900091
Liquid
Line
Filter-Drier
Six
38CQ900141
Solid
State
Time
Guard
(24
v)
SixHH22AG110
Optimizer
Control
Hot
Shot
Heat
Reclaim
Device
Six
38
H
Q900001
Outdoor
Thermostat
Six
38RQ900001
Emergency
Heat
Relay
Six
38CQ900061
two-packs.
Flare
(3/8-in
)
to
compatible
(3/8-in
)
couplings
Six
38RQ900061
Heat
Pump
Stand
for
Outdoor
Coil
Section
TUBING
PACKAGE
TUBING
Length
(ft)
Liquid
Suction*
COMPR
SECTION
O.D
(in.)
Tube
End
0
D
(in
)
0
D.
(in.)
Tube
End
O
D.
(in
)
Evap
Cond
38GC900071
10
3/8
3/8
3/4
3/4
3/4
38GC900081
18
3/8
3/8
3/4
3/4
3/4
38GC900091
25
3/8
3/8
3/4
3/4
3/4
38HQ227
38GC900101
35
3/8
3/8
3/4
3/4
3/4
38GC900111
50
3/8
3/8
3/4
3/4
3/4
1-1/8
in
OD
Suction
Tube,
Field
Supplied
38HQ234
‘Suction
line
is
insulated
and
has
a
90°
bend
at
one
end
INSTALLATION
Step
1
—
Check
Equipment
and
Jobsite
UNPACKAGE
UNITS
—
Move
units
to
final
loca¬
tion.
Slide
units
from
cartons
taking
special
care
not
to
damage
service
valves,
compatible
fittings
or
grilles.
Check
unit
model
numbers.
Use
only
Carrier-approved
unit
combinations
in
system.
See
Table
I.
INSPECT
EQUIPMENT
—
File
claim
with
ship¬
ping
company
if
shipment
is
damaged
or
incomplete.
COMPLETE
OR
CONSIDER
SYSTEM
RE¬
QUIREMENTS
before
installing
the
38HQ
units.
Consult
local
building
codes
and
National
Elec¬
trical
Code
(NEC)
for
special
installation
requirements.
When
installing
units,
allow
sufficient
space
for
airflow
clearance
(outdoor
unit),
wiring,
refrigerant
piping
and
servicing
unit.
Position
outdoor
unit
so
water
or
ice
from
roof
cannot
drop
directly
on
top
of
unit.
Maximum
allowable
vertical
distance
be¬
tween
indoor
and
outdoor
sections
is
50
feet.
It
is
strongly
recommended
that
38HQ
units
be
used
with
only
Carrier-approved
indoor
sections
(see
Table
1).
Outdoor
Coil
Section
—
Make
provision
for
con¬
densate
drainage
and
defrost
water
disposal
whether
unit
is
installed
on
ground,
roof
or
off-the-wall
platform.
Outdoor
unit
must
be
elevated
12
in.
to
18
in.
in
areas
of
heavy
snowfall.
(Ensure
unit
base-
pan
drainage
holes
are
not
blocked.
See
Fig.
1.)
See
Step
2,
Install
Outdoor
Coil
Section
for
details.
Roof
installation
method
for
38HQ
depends
on
building
construction
and
special
requirements
of
local
codes.
Make
sure
roof
can
support
unit
weight.
Indoor
Compressor
Section
—
Locate
unit
in
base¬
ment,
garage
or
utility
room.
Indoor
locations
with¬
in
the
living
space
are
not
recommended.
Basement
installations
also
require
careful
planning
to
avoid
areas
directly
under
bedrooms,
living
rooms,
etc.
3
Insert
felt
isolation
pad
(factory
supplied)
be¬
tween
unit
and
a
level
rigid
mounting
base
to
absorb
vibration.
Isolate
interconnecting
tubing
from
framing
and
ductwork
or
where
tubing
runs
thru
stud
spaces,
enclosed
ceilings
or
pipe
chases.
Use
isolation
type
hanger,
Fig.
3,
since
rigid
fastening
will
transmit
pulsation
to
structure
creating
ob¬
jectionable
sound.
System
Refrigerant
Control
consists
of
factory-
installed
byp^s-type
AccuRateF”
devices
located
as
shown
in
Fig.
15.
These
metering
devices
include
a
replaceable
orifice
piston
that
is
calibrated
to
regulate
refrigerant
flow.
Piston
data
is
given
in
Table
2.
In
some
instances,
the
factory-installed
piston
must
be
replaced
by
a
factory-supplied
re¬
placement
piston.
Where
required,
substitute
pistons
as
described
in
Step
5
and
as
indicated
on
tags
attached
to
system
AccuRater
devices.
Step
2
—
Install
Outdoor
Coil
Section
ON
THE
GROUND
—
Use
a
solid,
level
concrete
pad
as
shown
in
Fig.
4.
Position
unit
so
that
coil
drainage
holes
in
basepan
overhang
the
pad.
(See
Fig.
1
for
drainage
hole
locations.)
Be
sure
pad
does
not
obstruct
drainage
holes
(water
drains
from
holes
during
heating
and
defrost
cycles).
Attach
unit
to
pad
with
1
/
4-in.
mounting
bolts.
Any
2
holes
in
unit
basepan
may
be
used
to
fasten
unit
to
pad.
Construct
round,
24-in.
diameter
6-in.
thick
pad
a
minimum
of
6
in.
above
grade
to
provide
clearance
under
holes
for
drainage
and
ice
build-up.
In
areas
where
prolonged
subfreezing
temperatures
or
snows
occur;
increase
clearance
by
using
accessory
heat
pump
stand
to
support
unit
12
to
18
in.
off
concrete
base.
See
Fig.
4.
Be
sure
stand
does
not
obstruct
coil
drainage
holes.
Avoid
mounting
unit
in
prevailing
Winds
to
minimize
effect
on
defrost
performance.
Construct
wind
break
if
necessary.
Extend
a
12-in.
gravel
apron
around
pad
for
condensate
and
defrost
water
drainage
field.
Provide
support
bracket
from
structure
or
other
solid
support
to
outdoor
unit
to
give
stability.
Since
it
is
lightweight,
the
outdoor
section
may
be
Fig.
4
—
Unit
Support
Details
mounted
on
a
platform
attached
to
or
built
out
from
structure.
Construct
platform
using
drainage
and
clearance
recommendations
above.
Locate
and
con¬
struct
platform
to
avoid
possible
transfer
of
unit
vibration
to
structure.
See
Table
2
for
unit
weight.
ON
THE
ROOF:
Install
a
level
platform
or
frame
to
support
unit.
Elevate
unit
for
proper
clearance
as
previously
described
for
on-the-ground
installation.
Plan
roof
design
and
water
drainage
to
prevent
unit
from
sitting
in
water.
Flash
all
roof
openings
to
prevent
leaks.
4
Step
3
—
Install
Indoor
Compressor
Section
on
a
level,
rigid,
solid
platform
or
concrete
floor.
Do
not
install
in
a
living
area.
Insert
1/4-in.
asphalt-impregnated
felt
pad
(supplied)
between
unit
basepan
and
mounting
surface
to
provide
full
unit
support
and
vibration
attenuation.
(Do
not
use
vibration
isolators
under
corners
of
basepan.)
Step
4
install
Indoor
Fan-Coil
and
Electric
Heater
as
described
in
Installation
Instructions
supplied
with
this
equipment.
Install
and
connect
thermostats
and
other
controls
as
described
in
the
steps
that
follow.
Step
5
—
Make
Piping
Connections
—
The
38HQ
sections
may
be
connected
to
indoor
fan-coil
using
Carrier
accessory
tubing
packages
or
field-
supplied
tubing
of
refrigerant
grade.
See
Table
2
for
unit
piping
connection
types,
sizes
and
line
size
recommendations
and
Table
4
for
accessory
tubing
sizes.
Maximum
allowable
system
liquid
line
length
is
100
feet.
Maximum
vapor
line
length
from
com¬
pressor
section
to
indoor
coil
is
50
feet.
Maximum
vapor
line
length
from
compressor
section
to
out¬
door
coil
is
50
feet.
When
other
than
25
ft
of
interconnecting
piping
!
is
used,
follow
special
requirements
described
in
^
Refrigerant
Charging.
Do
not
use
less
than
10
ft
of
vapor
or
liquid
line.
Do
not
use
damaged
or
contaminated
tubing.
Always
evacuate
or
purge
indoor
coil,
compressor
section
and
tubing
system.
When
purging,
use
field-
supplied
refrigerant,
not
unit
refrigerant.
When
making
tubing
connections,
be
sure
to
provide
clearance
at
unit
for
electrical
connections.
Follow
tubing
isolation
recommendations
described
previously.
REPLACE
THE
ACCURATER"”
REFRIG¬
ERANT
CONTROL
PISTON(S)
before
connect¬
ing
refrigerant
lines
as
applicable.
Refer
to
tags
attached
to
AccuRater
device.
Replacement
pistons
are
shipped
with
compressor
section
and
are
to
be
installed
as
directed
on
tag.
Replacement
procedure,
briefly
described
below,
is
detailed
on
tag.
Also,
see
AccuRater
Servicing
for
additional
information.
When
connecting
indoor
compressor
section
38HQ227
to
outdoor
coil
section
38HQ940,
remove
no.
4
piston
from
outdoor
coil
AccuRater
device;
replace
with
no.
3
piston.
Attach
AccuRater
identi¬
fication
sticker
to
unit
(replacing
existing
sticker,
if
any).
CONNECT
REFRIGERANT
LINES
to
fittings
on
indoor
and
outdoor
sections.
Fig.
1,
2
and
5.
Indoor
compressor
section
has
2
Compatible
Fitting
vapor
line
connections.
Outdoor
and
indoor
fan-coil
sections
have
Compatible
Fitting
vapor
line
connec¬
tion
and
liquid
line
flare
connection.
Flare
and
connect
liquid
line
from
outdoor
coil
section
to
indoor
fan-coil
unit.
It
is
not
necessary
to
flare
system
liquid
line
if
an
accessory
flare-to-
Fig.
5
—
Refrigerant
Piping
Connections
5
Compatible
Fitting
coupler
is
used
for
liquid
line
connection.
See
accessory
coupler,
Fig.
6.
Connect
vapor
line
from
outdoor
coil
section
to
indoor
compressor
section,
and
from
compressor
section
to
indoor
fan-coil.
Section
vapor
line
as
required
(Fig.
5).
Use
correct
compressor
section
vapor
line
connection
to
indoor
and
outdoor
coils.
Unit
Compatible
Fittings
permit
mechanical
or
sweat
connection
as
described
below.
When
a
1-1/8
in.
field-supplied
vapor
line
is
used
on
38HQ234,
four
field-supplied
3/4-in.
to
1-1/8
in.
vapor
line
adapters
must
be
provided.
Insulate
Refrigerant
Lines
—
After
making
tubing
connections,
the
compressor
section
fittings
must
be
insulated.
Butt
the
Armaflex
tubing
insulation
(pro¬
vided
in
tubing
package)
against
the
Compatible
Fittings.
Secure
the
insulation
with
Prestite
or
an
equivalent
material
which
provides
both
adhesion
and
insulation.
Also
wrap
the
Compatible
Fittings
with
Prestite
to
prevent
sweating.
Mechanical
Connection-to-Compatible
Fitting
(Mate
one
set
of
connections
at
a
time.)
1.
Loosen
nut
on
Compatible
Fitting
one
turn.
Do
not
remove.
2.
Remove
plug
and
be
sure
0-ring
is
in
the
groove
inside
the
Compatible
Fitting.
3.
Cut
tubing
to
correct
length.
4.
Insert
tube
into
Compatible
Fitting
until
it
bottoms.
5.
Tighten
nut
until
it
bottoms
on
back
coupler
flange.
Keep
tube
bottomed
in
Compatible
Fitting
while
tightening
nut.
Sweat
Connection-to-Compatible
Fitting
(Use
refrigerant
grade
tubing.)
1.
Remove
locking
nut,
rubber
O-ring
and
Schrader
core
from
valve.
2.
Cut
tubing
to
correct
length.
3.
Insert
tube
into
Compatible
Fitting.
Wrap
top
and
bottom
of
service
valves
in
wet
cloth
to
pre¬
vent
damage
by
heat.
Solder
with
low
tempera¬
ture
(430
F)
silver
alloy
solder.
4.
Replace
Schrader
core.
5.
Evacuate
or
purge
system
with
field-supplied
refrigerant.
Accessory
Flare-to-Compatible
Fitting
Coupler
is
shown
in
Fig.
6.
Attach
flare
nut
on
coupler
to
flare
fitting
on
unit
liquid
line
connection.
Connect
liquid
line
to
Compatible
Fitting
using
mechanical
or
sweat
connection.
When
mechanical
connection
is
made,
use
2
wrenches
to
tighten
Compatible
Fitting
nut
—
one
to
hold
coupler
and
one
to
tighten
nut.
Fig.
6
—
Accessory
Coupler
Step
6
—
Install
Fan
Control
Package
(factory
supplied;
packaged
separately
inside
indoor
com¬
pressor
section)
—
This
control,
consisting
of
a
transformer
and
a
relay,
provides
high-speed
fan
operation
when
both
compressors
are
energized.
Refer
to
connection
diagram
in
Fig.
7
for
wiring
details.
Install
control
as
follows:
1.
Remove
factory-installed
transformer
from
indoor
fan-coil
unit
electric
heater
package.
Refer
to
40FS
service
instructions
as
required.
2.
Install
fan
control
package
in
upper
right-hand
corner
of
the
40FS.
3.
Route
wires
from
controls
to
heater
package
thru
knockouts
provided.
Restore
transformer
wiring
connections
including
ground
wire.
4.
Connect
black
wire
from
indoor
fan
relay
(IFR)
terminal
no.
4
(or
no.
6)
to
black
wire
from
indoor
fan
relay
no.
2
(IFR-2)
terminal
no.
3.
(Cut
off
male
connector
from
IFR
wire;
supply
wire
nut
to
splice
wires.)
5.
Connect
black
wire
from
IFR-2
terminal
no.
6
to
fan
speed
selector
block
terminal
no.
1
(high
speed).
6.
Connect
blue
wire
from
IFR-2
terminal
no.
1
to
fan
speed
selector
block
terminal
no.
3
(low
speed).
7.
Connect
low-voltage
field
control
wires
between
indoor
compressor
section
and
indoor
fan
relay
(IFR-2)
orange
pigtails
(TB
OA
to
OFR-2,
ter¬
minal
no.
4;
contactor
C-2,
terminal
C
to
IFR-2,
terminal
no.
5).
Field-supplied,
24-gage,
NEC
Class
2
thermostat
wire
may
be
used.
Step
7
—
Install
Outdoor
Ambient
Switch
(OA)
(factory-supplied;
packaged
separately
inside
indoor
compressor
section)
—
This
switch
activates
compressor
no.
2
when
the
first
heating
thermal
balance
point
is
reached.
The
switch
is
installed
in
the
same
manner
as
the
outdoor
thermostat
(step
8),
except
refer
to
Fig.
7
for
correct
wiring.
FAN
CONTROL
PACKAGE
LEGEND
C-2
—
Contactor
IFR
—
Indoor
Fan
Relay
PL
—
Plug,
Fan
SEQ
—
Sequencer
TB
—
Terminal
Board
Tran
—
Transformer
#
Junction
o
Component
Connection
(Marked)
Field
Splice
HiW
Field
Power
Wiring
Field
Ground
Wiring
_Field
Control
Wiring
NOTES:
1
Use
copper
conductors
only.
2
May
be
terminal
board
or
fuse
block
depending
on
heater
model
used
3
Will
be
terminal
no
4
on
40FQ916
models,
and
terminal
no
6
on
40FQ920
models
THERMOSTAT
40FQ
SUBBASE
ELECTRIC
HEATER
HH93AZ073
0R
TERMINAL
HH93AZ075
BOARD
38HQ
COMPRESSOR
SECTION
TERMINAL
BOARD
THERMOSTAT
40FQ
SUBBASE
ELECTRIC
HEATER
HH93AZ0730R
TERMINAL
HH93AZ075
BOARD
38HQ
COMPRESSOR
SECTION
TERMINAL
BOARD
(38HQ
WITH
40FS/28HQ,VQ
EQUIPPED
WITH
ELECTRIC
HEATER;
EMERGENCY
HEAT,
ONE
OUTDOOR
THERMOSTAT)
THERMOSTAT
SUBBASE
HH93AZ073
OR
HH93AZ075
40FQ
ELECTRIC
HEATER
TERMINAL
BOARD
38HQ
COMPRESSOR
SECTION
TERMINAL
BOARD
COOLING
AND
TWO-STAGE
HEATING
(38HQ
WITH
40FS/28HQ,VQ
EQUIPPED
WITH
ELECTRIC
HEATER;
EMERGENCY
HEAT,
NO
OUTDOOR
THERMOSTATS)
THERMOSTAT
40FQ
38HQ
SUBBASE
ELECTRIC
HEATER
COMPRESSOR
HH93AZ0730R
TERMINAL
SECTION
HH93AZ075
BOARD
TERMINAL
BOARD
EQUIPPED
WITH
ELECTRIC
HEATER;
EMERGENCY
HEAT,
TWO
OUTDOOR
THERMOSTATS)
DFT
—
Defrost
Thermostat
EHR
—
Emergency
Heat
Relay
OA
—
Outdoor
Ambient
Switch
ODT
—
Outdoor
Thermostat
_
Factory
Wiring
_Field
Wiring
^Transformer
(75
va)
located
in
fan
control
package
tTerminal
L
is
identified
as
terminal
X
on
some
former
thermostats
(Required
for
system
malfunction
warning
indicator
on
compressor
section
)
^Remove
1
or
both
factory-installed
jumpers
(connection
B)
when
installing
outdoor
ther¬
mostats
(ODT)
shown
in
connections
C
and
D
Fig.
7
—
Control
Circuit
Connections
7
Attach
one
lead
to
compressor
terminal
board
connection
OA.
Connect
other
lead
to
line
side
of
defrost
thermostat.
Set
switch
at
temperature
of
first
thermal
balance
point
(heating).
This
balance
point
is
provided
by
CLIC
load
estimating
program.
Further
adjust¬
ments
can
be
made
following
operating
experience.
Step
8
—
Install
Room
Thermostat,
Outdoor
Thermostat(s)
and
Emergency
Heat
Relay
—
Follow
Installation
Instructions
shipped
with
these
accessories
plus
the
instructions
in
the
sections
that
follow.
Connect
as
described
in
step
9.
INDOOR
THERMOSTAT
—
Use
only
Carrier
indoor
thermostat
and
subbase
as
shown
in
Table
4.
Set
heat
anticipator
settings
according
to
Table
5.
These
settings
may
be
changed
slightly
to
provide
a
greater
degree
of
comfort
for
certain
installations.
Table
5
—
Thermostat
Heat
Anticipator
Settings
INDOOR
COM
PR
SECTION
OUTDOOR
COIL
SECTION
INDOOR
UNIT
WITH
ELECTRIC
HTR
HTR
KW
ANTICIPATOR
SETTINGS
First
Stage
Second
Stage
38HQ227
38HQ940
40FS160
with
40FQ916010
thru
090
8
thru
20
Fixed
16
38HQ234
38HQ960
40FS200
with
40FQ920060
thru
150
10
thru
25
Fixed
49
OUTDOOR
THERMOSTAT
ACCESSORY
pro¬
vides
adjustable
outdoor
control
of
accessory
electric
heater
(used
on
indoor
fan-coil).
This
ther¬
mostat
closes
on
a
drop
in
outdoor
temperature.
It
energizes
a
stage
of
electric
heat
when
the
out¬
door
temperature
setting
is
reached,
provided
the
room
thermostat
is
on
the
second
stage
of
heating.
One
outdoor
thermostat
is
recommended
for
each
stage
of
electric
heat
after
the
first
stage.
Connect
as
described
in
Step
9.
Set
the
outdoor
thermostats
progressively
lower
for
each
stage.
Refer
to
heat
load
of
building
and
unit
capacity
to
determine
the
correct
outdoor
thermostat
settings.
Locate
maxi¬
mum
of
2
outdoor
thermostats
in
control
voltage
section
of
outdoor
coil
section
junction
box.
Fasten
in
place
with
sheet
metal
screws.
EMERGENCY
HEAT
RELAY
—
This
accessory
is
required
when
2
or
more
outdoor
thermostats
are
used.
It
is
automatically
energized
by
the
manually-
operated
emergency
heat
switch
in
the
indoor
ther¬
mostat
subbase.
The
indoor
thermostat
locks
out
the
compressor
and
the
relay
bypasses
the
outdoor
thermostats
for
electric
heater
operation
during
heat
pump
shutdown.
When
one
outdoor
thermostat
is
used,
an
emergency
heat
relay
is
not
required.
The
emergency
heat
switch
in
the
indoor
thermostat
subbase
bypasses
the
outdoor
thermostat,
locks
out
the
compressor
and
activates
the
electric
heater.
Install
emergency
heat
relay
in
a
convenient
loca¬
tion
on
indoor
unit.
Attach
with
sheet
metal
screw.
Connect
relay
as
shown
in
Fig,
7.
Step
9
—
Make
Electrical
Connections
—
In¬
stall
field
wiring
in
accordance
with
local
and
national
fire,
safety
and
electrical
codes.
Be
sure
voltage
to
units
is
within
±
10%
of
voltage
indi¬
cated
on
nameplate.
Contact
local
power
company
for
correction
of
improper
line
voltage.
When
making
electrical
connections,
provide
clearance
at
unit
for
refrigerant
piping
connections.
See
Table
6
for
recommended
wire
and
fuse
sizes.
Line
power
connections
and
control
circuit
connec¬
tions
are
shown
in
Fig.
7
and
8.
Route
line
and
control
power
wiring
for
38HQ
outdoor
coil
from
connections
in
the
38HQ
in¬
door
compressor
section.
Use
14-ga
(minimum)
line
power
wire
size
to
outdoor
coil
section
when
total
wire
length
connecting
compressor
section
to
coil
is
under
25
feet.
If
over
25
ft,
use
same
wire
size
as
compressor
section
branch
circuit.
Table
6
—
Electrical
Data
INDOOR
COMPR
SECTION
OUTDOOR
COIL
SECTION
VOLTAGE
COMPR
1
COMPR
2
OFM
(FLA)
BRANCH
CIRCUIT
-
n
Nom
1-Ph
60-Hz
1
1
1
Operating*
Power
Wire
]
Gnd
Wire
Sizet
(AWG)
Min
Ckt
Amps
Max
Fuse
Amps**
_
Min
Size
(AWG)
Max
Ft
1
Max
Min
LRA
RLA
LRA
RLA
ICS
OCS
ICS
OCS
ICS
OCS
38
H0227
38HQ940
230
254
207
72
17
88
1
17
8
1
5
6
14t
55
25t
10
14t
40
8
38HQ234
38HQ960
230
254
207
88
20
94
S
__
1
21
2
2
3
4
14t
75
25t
10
14t
48
8
60
FLA
—
Full
Load
Amps
ICS
—
Indoor
Compressor
Section
LRA
—
Locked
Rotor
Amps
OCS
—
Outdoor
Coil
Section
OFM
—
Outdoor
Fan
Motor
RLA
—
Rated
Load
Amps
^Permissible
limits
of
the
voltage
range
(for
limited
period
of
time)
at
which
the
units
will
operate
satisfactorily
fOutdoor
coil
section
wiring
—
for
25
ft
wire
run
or
less,
use
minimum
14
AWG
size
wire
For
longer
wire
run
use
same
size
as
supply
to
compressor
section
^Required
when
using
nonmetallic
conduit
**Maximum
dual
element
fuse
size
NOTES;
1
All
units
have
24-v
control
circuit
which
requires
external
power
source
2
Copper
wire
size
table
based
on
60
C
Use
copper
or
copper-clad
aluminum
wire
to
indoor
section;
copper
wire
only
to
outdoor
section
Use
latest
National
Electrical
Code
for
wire
sizing
8
FACTORY
WIRING
Fig.
8
—
Line
Power
Connections
INSTALL
A
BRANCH
CIRCUIT
DISCONNECT
PER
N.E.C.
of
adequate
size
to
handle
compressor
section
starting
current.
Provide
a
separate
dis¬
connect
switch
for
outdoor
coil
section.
Provide
a
separate
disconnect
for
indoor
fan-coil
and
for
each
accessory
electric
heater
circuit
as
required,
(See
In¬
door
Unit
and
Electric
Heater
Installation,
Start-Up
and
Service
Instructions.)
Locate
disconnect(s)
within
sight
of
and
readily
accessible
to
the
units,
per
section
440-14
of
National
Electrical
Code
(NEC).
ROUTE
LINE
POWER
LEADS
INTO
COM¬
PRESSOR
SECTION
—
Extend
lead
from
discon¬
nect
per
N.E.C.
thru
1-1/8
in.
hole
provided
in
com¬
pressor
section
top
panel
(Fig.
2)
and
into
control
box.
Extend
line
power
leads
for
outdoor
coil
section
thru
7/8-in.
hole
provided
in
compressor
section
top
panel
and
into
control
box.
CONNECT
GROUND
LEADS
AND
POWER
WIRES
—
Connect
ground
leads
to
the
ground
lug
in
control
box
for
safety.
Splice
compressor
section
line
power
leads
to
yellow
and
black
pigtails,
and
outdoor
coil
section
power
leads
to
brown
and
blue
pigtails.
Use
wire
nuts
and
tape
at
each
splice
con¬
nection
as
shown
in
Fig.
8.
CONNECT
POWER
LEADS
FROM
INDOOR
COMPRESSOR
SECTION
TO
OUTDOOR
COIL
SECTION
thru
secondary
disconnect
switch.
From
this
disconnect
switch
extend
leads
thru
hole
provided
in
outdoor
coil
section
basepan
(Fig.
1)
and
into
line
voltage
section
of
junction
box.
Fig.
14.
Splice
leads
to
black
and
blue
pigtails
with
wire
nuts.
CONNECT
CONTROL
WIRING
(24-v)
—
Extend
wiring
thru
7
/
8-in.
grommeted
hole
in
compressor
section
top
panel
(Fig.
2),
and
to
control
wiring
terminal
board
on
side
of
control
box.
Connect
leads
to
terminal
board
as
shown
in
Fig.
7.
Extend
and
connect
control
wiring
from
compressor
section
to
outdoor
coil
section
as
required.
Make
splice
connections
in
low-voltage
section
of
coil
junction
box.
Use
indoor
fan-coil
transformer
as
24-v
supply
for
system.
Be
sure
fan
control
package
is
installed
as
described
in
Step
6.
Package
contains
75-va
trans¬
former
of
adequate
capacity
to
handle
system
current.
INITIAL
START-UP
The
compressors
in
the
indoor
compressor
section
are
equipped
with
crankcase
heaters.
It
is
recommended
that
the
heaters
be
energized
a
minimum
of
24
hours
before
starting
the
system.
To
energize
crankcase
heaters
only,
set
the
thermostat
at
OFF
position
and
turn
on
main
power
to
compressor
section.
To
Start
System
—
(Be
sure
crankcase
heaters
have
been
energized
for
24
hours.)
Adjust
the
ther¬
mostat
as
follows:
1.
Set
selector
switch
at
OFF.
2.
Turn
on
main
disconnect
switch(es)
to
indoor
and
outdoor
units.
3.
Set
fan
switch
as
desired
(ON
or
AUTO.).
4.
Set
thermostat
dial
at
desired
temperature.
5.
Set
selector
switch
at
HEAT
or
COOL.
Check
system
refrigerant
charge.
See
Service
—
Refrigerant
Charging.
SEQUENCE
OF
OPERATION
Fan
Switch
at
AUTO.
Position,
Thermostat
at
ON
Position
(Crankcase
heater
is
on
as
soon
as
the
field
power
supply
is
on.)
THERMOSTAT
CALLS
FOR
COOLING
1.
First-stage
cooling
thermostat
(Co)
closes
and
the
reversing
valve
solenoid
(RVS)
is
energized.
The
RVS
actuates
the
reversing
valve
and
switches
the
system
to
cooling.
2.
Second-stage
cooling
thermostat
(Cl)
closes.
If
the
low-pressure
switch
(LPS)
is
closed,
com¬
pressor
contactor
(C)
is
energized
and
compres-
9
sor
no.
1
starts.
At
the
same
time,
the
outdoor
fan
motor
(OFM)
starts
and
the
defrost
timer
(DT)
is
energized
although
it
is
not
functional
in
the
cooling
mode;
the
indoor
fan
relay
(IFR)
is
energized
and
the
indoor
fan
motor
(IFM)
starts.
Compressor
no.
2
does
not
run
in
COOL
mode.
When
the
second
stage
of
cooling
is
satisfied,
Cl
opens.
The
compressor
stops;
the
indoor
and
out¬
door
fans
stop;
DT
is
de-energized.
When
the
con¬
trolled
temperature
drops
approximately
1
F
below
the
cooling
set
point,
Co
opens.
RVS
is
de-energized
and
the
reversing
valve
switches
to
heating
(normal
position).
The
unit
is
shut
down
except
for
the
two
compressor
crankcase
heaters,
which
remain
on
as
long
as
the
field
power
supply
is
on.
THERMOSTAT
CALLS
FOR
HEATING
(The
reversing
valve
is
de-energized,
in
heating
position.)
1.
First
stage
heating
thermostat
(HI)
closes.
Com¬
pressor
contactor
no.
1
(Cl)
is
energized
and
compressor
starts;
outdoor
fan
motor
(OFM)
starts;
defrost
timer
(DT)
is
energized.
Indoor
fan
relay
(IFR)
is
energized
and
indoor
fan
motor
(IFM)
starts.
When
the
outdoor
ambient
switch
(OA)
closes
(at
first
thermal
balance
point),
compressor
contactor
no.
2
(C2)
is
ener¬
gized
and
compressor
no.
2
starts.
Compressor
no.
1
and
compressor
no.
2
operate
simul¬
taneously
as
long
as
OA
is
closed.
The
crankcase
heaters
are
de-energized
when
both
compressors
are
running.
2.
Second-stage
heating
thermostat
(H2)
closes
and
activates
the
first
accessory
heater
element
sequencer
thru
indoor
thermostat
terminal
W2.
The
first-stage
electric
heater
element
is
energized
immediately
and
the
other
heater
elements
are
energized
at
regular
intervals
thru
the
sequencers.
Separate
outdoor
thermostats
may
be
used
to
energize
the
second
sequencer
and
bring
on
addi¬
tional
heater
elements
if
more
incremental
heat
control
is
desired.
When
the
second
stage
of
heating
is
satisfied,
H2
opens
and
the
electric
heater(s)
shuts
off.
When
the
first
stage
of
heating
is
satisfied,
HI
opens
and
the
unit
shuts
down,
except
for
the
compressor
crank¬
case
heater,
which
remains
on
as
long
as
the
field
power
supply
is
on.
Unit
Controls
and
Safety
Devices
HIGH-PRESSURE
RELIEF
VALVE
is
located
in
compressor.
Relief
valve
opens
at
a
pressure
differential
of
approximately
500
psi
between
suction
(low
side)
and
discharge
(high
side)
to
allow
pressure
equalization.
INTERNAL
CURRENT
AND
TEMPERATURE
SENSITIVE
OVERLOAD
resets
automatically
when
internal
compressor
motor
temperature
drops
to
a
safe
level
(overloads
may
require
up
to
45
min¬
utes
to
reset).
When
an
internal
overload
is
suspected
of
being
open,
check
by
using
an
ohmmeter
or
con¬
tinuity
tester.
If
necessary,
refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
2,
Electrical,
for
complete
instructions.
LOW-PRESSURE
SWITCH
is
located
in
compres¬
sor
section
on
suction
line
between
reversing
valve
and
accumulator.
Provides
loss-of-charge
protec¬
tion
by
shutting
compressor
off
if
suction
pressure
drops
below
setting.
Low-pressure
switch
settings
are:
open,
5
±
3
psig;
close,
20
±
5
psig.
CRANKCASE
HEATERS
are
activated
by
a
relay.
Heaters
derive
power
from
contactor
no.
2
and
are
energized
when
compressors
are
off
or
when
only
one
compressor
is
functioning.
The
heater
keeps
the
crankcase
warm
during
the
off
cycle
and
thus
prevents
dilution
of
the
oil
with
the
refrigerant,
assures
good
lubrication,
and
pre¬
vents
loss
of
oil
from
crankcase
during
start-up.
If
the
electrical
disconnect
switch
to
the
compres¬
sor
section
has
been
off
for
an
extended
period
of
time,
the
crankcase
heater
should
be
energized
for
24
hours
before
starting
the
compressor.
SIGNAL-LOC
™
SYSTEM
MALFUNCTION
WARNING
INDICATOR
AND
LOCKOUT
^
Indoor
compressor
section
is
equipped
with
a
solid-
state
warning
logic
circuit
that
protects
the
system.
In
case
of
a
malfunction
(compressors
do
not
oper¬
ate
due
to
safety
device
cutout),
emergency
heat
light
on
thermostat
comes
on
and
compressors
are
pre¬
vented
from
restarting.
Compressors
can
be
re¬
started
after
resetting
thermostat
(turn
thermostat
off
then
on).
If
either
compressor
malfunctions,
both
will
be
locked
out
(prevented
from
restarting).
The
emergency
heat
light
goes
out
when
com¬
pressors
are
restarted
or
when
indoor
thermostat
is
satisfied.
If
the
light
does
not
stay
out
after
two
or
three
attempts
to
restart,
check
for
cause
of
malfunction.
DEFROST
CONTROL,
consisting
of
a
defrost
timer,
defrost
thermostat
and
defrost
relay,
inter¬
rupts
normal
system
heating
operation
every
90
minutes
to
defrost
outdoor
coil,
if
the
coil
saturated
suction
temperature
indicates
freezing
tempera¬
tures.
Defrost
control
simultaneously
stops
outdoor
fan,
energizes
reversing
valve
solenoid
to
return
system
to
cooling
cycle
(outdoor
coil
as
condenser,
indoor
fan-coil
unit
as
evaporator),
and
activates
accessory
electric
heater.
For
the
heat
pump
to
defrost,
2
conditions
are
necessary;
1.
Defrost
timer
contacts
must
be
closed.
2.
Refrigerant
temperature
from
outdoor
unit
must
be
cold
enough
to
cause
defrost
thermostat
contacts
to
close.
Contacts
close
at
27
(±
4)
F.
Every
90
minutes
of
elapsed
running
time,
the
de¬
frost
timer
contacts
close
for
10
seconds.
If
the
defrost
thermostat
contacts
are
closed,
the
unit
defrosts.
The
defrost
timer
limits
defrosting
period
to
10
minutes.
Normally
the
frost
is
removed
and
the
10