manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Carrier
  6. •
  7. Heat Pump
  8. •
  9. Carrier Weathermaster 38HQ Dimensions and installation guide

Carrier Weathermaster 38HQ Dimensions and installation guide

Number
One
ArConditbning
Maker
r^rrie^
Division
of
^1^
Carrier
Corporation
f
—--
't
w
Weathermaster
III
Dual-Compressor
Heat
Pump
(Outdoor
Coil
Section;
Indoor
Compressor
Section)
INDEX
Page
SAFETY
CONSIDERATIONS
.1
INSTALLATION.3
Step
1
—
Check
Equipment
and
Jobsite
.
3
•
UNPACKAGE
UNITS
•
INSPECT
EQUIPMENT
•
COMPLETE
OR
CONSIDER
SYSTEM
REQUIREMENTS
Step
2
—
install
Outdoor
Coil
Section.4
•
ON
THE
GROUND
•
ON
THE
ROOF
Step
3
—
Install
Indoor
Compressor
Section.5
Step
4
—
install
Indoor
Fan-Coil
and
Electric
Heater.5
Step
5
—
Make
Piping
Connections.5
•
REPLACE
THE
ACCURATER^^
REFRIGERANT
CONTROL
PISTON(S)
•
CONNECT
REFRIGERANT
LINES
Step
6
—
Install
Fan
Control
Package
...
6
Page
Step
7
—
Install
Outdoor
Ambient
Switch.6
Step
8
—
Install
Room
Thermostat,
Outdoor
Thermostat(s)
and
Emergency
Heat
Relay.
8
Step
9
—
Make
Electrical
Connections
...
8
•
INSTALL
A
BRANCH
CIRCUIT
DISCONNECT
PER
N.E.C.
•
ROUTE
LINE
POWER
LEADS
INTO
COMPRESSOR
SECTION
•
CONNECT
GROUND
LEADS
AND
POWER
WIRES
•
CONNECT
POWER
LEADS
FROM
INDOOR
COMPRESSOR
SECTION
TO
OUTDOOR
COIL
SECTION
•
CONNECTCONTROL
WIRING
INITIAL
START-UP.9
SEQUENCE
OF
OPERATION.
9
SERVICE.
11
MAINTENANCE
.
15
SAFETY
CONSIDERATIONS
Installation
and
servicing
of
air
conditioning
equipment
can
be
hazardous
due
to
system
pressure
and
electrical
components.
Only
trained
and
quali¬
fied
service
personnel
should
install,
repair
or
service
air
conditioning
equipment.
Untrained
personnel
can
perform
basic
mainten¬
ance
functions
of
cleaning
coils
and
filters
and
re¬
placing
filters.
All
other
operations
should
be
per¬
formed
by
trained
service
personnel.
When
working
on
air
conditioning
equipment,
observe
precautions
in
the
literature,
tags
and
labels
attached
to
the
unit
and
other
safety
precautions
that
may
apply.
Follow
all
safety
codes.
Wear
safety
glasses
and
work
gloves.
Use
quenching
cloth
for
brazing
opera¬
tions,
Have
fire
extinguisher
available
for
all
brazing
operations.
WARNING:
Before
perforisaisag;
servsoe
or
oa
tant:
OSS'
ijsain
SEWstchfes
mdoor
tnataad
otJt^oor
axat
ITarn
accessory
heater
power
if
'
shod:
cooSd
cause
per-
©
Carrier
Corporation
1979
Form
38HQ-6SI
A
VAPOR
LINE
CONN
(ON
SERVICE
VALVE)
liquid
line
CONN.
(ON
SERVICE
VALVE)
MTG
SLOTS
(USE
ANY
2)
VDIAM
HOLE
FOR
CONTROL
WIRING
DRAINAGE
HOLES
WM
SPACE
RE(3UIRED
FOR
SERVICE
^AIRFLOW
Certified
dimension
drawings
available
on
request
Fig.
1
—
Dimensions
and
Connections,
38HQ
Outdoor
Coil
Section
(Table
2)
Table
1
—
Carrier-Approved
38HQ
Weathermaster
III
Dual-Compressor
Heat
Pump
Systems
INDOOR
1
COMPRESSOR
1
SECTION
OUTDOOR
COIL
SECTION
INDOOR
FAN/COIL
38HQ227
38HQ940
40FS160/28VQ036
38HQ234
38HQ960
40FS200/28VQ042
VAPOR
LINE
CONN
TO
OUTDOOR
COIL
VAPOR
LINE
CON
TO
INDOOR
COIL
14
DIAM
HOLE
FOR
COMPRESSOR
SECTION
LINE
POWER
yC&K;
38HQ
INDOOR
COMPRESSOR
SECTION
i
DIAM
HOLE
FOR
OUTDOOR
COIL
SECTION
LINE
POWER
WIRING
(SEE
ELECTRICAL
DATA
AND
WIRING)
t
DIAM
HOLE
FOR
CONTROL
WIRING
Pill
SPACE
REQUIRED
FOR
SERVICE
Certified
dimension
drawings
available
on
request
Fig.
2
—
Dimensions
and
Connections,
38HQ
Indoor
Compressor
Section
(Table
2)
Table
2
—
Physical
Data
INDOOR
COMPR
SECTION
38HQ227
38HQ234
Operating
Wt
(lbs)
205
225
Dimensions
(ft-in.)
Width
A
2-2-3/32
Depth
B
1-4-3/16
Height
C
1-11-1/8
(add
3/4-in
for
Refrigerant
Fittings
Compressor
no.
1
IV1D2713GM
(46)
MD3413GIVI
(46)
(Oil
Recharge,
oz)
no.
2
MD3413GMi
(46)
MD3413GM
(46)
AccuRater
Size
(in.)
Indoor
no
6
(
0670)
no
7(0760)
Outdoor
no
3
(.0550)*
no
5
(
0635)
Refrig
Conn
(in.)
3/4
3/4
OUTDOOR
COIL
SECTION
38HQ940
38HQ960
Operating
Wt
(lb)
107
125
Dimensions
(ft-in.)
Diameter
A
2-5-1/4
2-5-1/4
Unit
Height
B
2-
8
3-
8
Coil
Height
C
1-11
2-11
Refrig
Conn
Vapor
(in.,
ODF)
3/4,
Compatible
Fitting
Liquid
(in.,
ODF)
3/8,
Flare
Fitting
*Piston
size
shown
is
shipped
with
section
Remove
factory-
installed
piston;
replace
with
size
shown
per
text
2
Table
3
—
Heater
Airflow
Data
■
i
INDOOR
COMPRESSOR
SECTION
HEATER
MINIMUM
ALLOWABLE
SIZE
Airflow
(cfm)
\
Fan
Speed
38HQ227
8
thru
20
kw
(40FQ91
6010
thru
090)
1150
j
Low
38HQ234
10
thru
25
kw
(40FQ920060
thru
1
50)
1550
Low
Table
4
—
Accessories
PART
NO.
38CQ900102
38CQ900122
38CQ900132
38CQ900152
38CQ900172
38HQ900011
38HQ900002
38RQ900012
38CQ900072
38RQ900072
DESCRIPTION
Six
38CQ900081
Low-voltage
Honeywell
Thermostat
(HH07AT071)
and
Thermostat
Subbase
(HH93AZ073)
with
automatic
changeover
Six
38CQ900111
Low-voltage
Honeywell
Thermostat
(HH07AT071)
and
Thermostat
Subbase
(HH93AZ075)
with
manual
changeover
Six
38CQ900091
Liquid
Line
Filter-Drier
Six
38CQ900141
Solid
State
Time
Guard
(24
v)
SixHH22AG110
Optimizer
Control
Hot
Shot
Heat
Reclaim
Device
Six
38
H
Q900001
Outdoor
Thermostat
Six
38RQ900001
Emergency
Heat
Relay
Six
38CQ900061
two-packs.
Flare
(3/8-in
)
to
compatible
(3/8-in
)
couplings
Six
38RQ900061
Heat
Pump
Stand
for
Outdoor
Coil
Section
TUBING
PACKAGE
TUBING
Length
(ft)
Liquid
Suction*
COMPR
SECTION
O.D
(in.)
Tube
End
0
D
(in
)
0
D.
(in.)
Tube
End
O
D.
(in
)
Evap
Cond
38GC900071
10
3/8
3/8
3/4
3/4
3/4
38GC900081
18
3/8
3/8
3/4
3/4
3/4
38GC900091
25
3/8
3/8
3/4
3/4
3/4
38HQ227
38GC900101
35
3/8
3/8
3/4
3/4
3/4
38GC900111
50
3/8
3/8
3/4
3/4
3/4
1-1/8
in
OD
Suction
Tube,
Field
Supplied
38HQ234
‘Suction
line
is
insulated
and
has
a
90°
bend
at
one
end
INSTALLATION
Step
1
—
Check
Equipment
and
Jobsite
UNPACKAGE
UNITS
—
Move
units
to
final
loca¬
tion.
Slide
units
from
cartons
taking
special
care
not
to
damage
service
valves,
compatible
fittings
or
grilles.
Check
unit
model
numbers.
Use
only
Carrier-approved
unit
combinations
in
system.
See
Table
I.
INSPECT
EQUIPMENT
—
File
claim
with
ship¬
ping
company
if
shipment
is
damaged
or
incomplete.
COMPLETE
OR
CONSIDER
SYSTEM
RE¬
QUIREMENTS
before
installing
the
38HQ
units.
Consult
local
building
codes
and
National
Elec¬
trical
Code
(NEC)
for
special
installation
requirements.
When
installing
units,
allow
sufficient
space
for
airflow
clearance
(outdoor
unit),
wiring,
refrigerant
piping
and
servicing
unit.
Position
outdoor
unit
so
water
or
ice
from
roof
cannot
drop
directly
on
top
of
unit.
Maximum
allowable
vertical
distance
be¬
tween
indoor
and
outdoor
sections
is
50
feet.
It
is
strongly
recommended
that
38HQ
units
be
used
with
only
Carrier-approved
indoor
sections
(see
Table
1).
Outdoor
Coil
Section
—
Make
provision
for
con¬
densate
drainage
and
defrost
water
disposal
whether
unit
is
installed
on
ground,
roof
or
off-the-wall
platform.
Outdoor
unit
must
be
elevated
12
in.
to
18
in.
in
areas
of
heavy
snowfall.
(Ensure
unit
base-
pan
drainage
holes
are
not
blocked.
See
Fig.
1.)
See
Step
2,
Install
Outdoor
Coil
Section
for
details.
Roof
installation
method
for
38HQ
depends
on
building
construction
and
special
requirements
of
local
codes.
Make
sure
roof
can
support
unit
weight.
Indoor
Compressor
Section
—
Locate
unit
in
base¬
ment,
garage
or
utility
room.
Indoor
locations
with¬
in
the
living
space
are
not
recommended.
Basement
installations
also
require
careful
planning
to
avoid
areas
directly
under
bedrooms,
living
rooms,
etc.
3
Insert
felt
isolation
pad
(factory
supplied)
be¬
tween
unit
and
a
level
rigid
mounting
base
to
absorb
vibration.
Isolate
interconnecting
tubing
from
framing
and
ductwork
or
where
tubing
runs
thru
stud
spaces,
enclosed
ceilings
or
pipe
chases.
Use
isolation
type
hanger,
Fig.
3,
since
rigid
fastening
will
transmit
pulsation
to
structure
creating
ob¬
jectionable
sound.
System
Refrigerant
Control
consists
of
factory-
installed
byp^s-type
AccuRateF”
devices
located
as
shown
in
Fig.
15.
These
metering
devices
include
a
replaceable
orifice
piston
that
is
calibrated
to
regulate
refrigerant
flow.
Piston
data
is
given
in
Table
2.
In
some
instances,
the
factory-installed
piston
must
be
replaced
by
a
factory-supplied
re¬
placement
piston.
Where
required,
substitute
pistons
as
described
in
Step
5
and
as
indicated
on
tags
attached
to
system
AccuRater
devices.
Step
2
—
Install
Outdoor
Coil
Section
ON
THE
GROUND
—
Use
a
solid,
level
concrete
pad
as
shown
in
Fig.
4.
Position
unit
so
that
coil
drainage
holes
in
basepan
overhang
the
pad.
(See
Fig.
1
for
drainage
hole
locations.)
Be
sure
pad
does
not
obstruct
drainage
holes
(water
drains
from
holes
during
heating
and
defrost
cycles).
Attach
unit
to
pad
with
1
/
4-in.
mounting
bolts.
Any
2
holes
in
unit
basepan
may
be
used
to
fasten
unit
to
pad.
Construct
round,
24-in.
diameter
6-in.
thick
pad
a
minimum
of
6
in.
above
grade
to
provide
clearance
under
holes
for
drainage
and
ice
build-up.
In
areas
where
prolonged
subfreezing
temperatures
or
snows
occur;
increase
clearance
by
using
accessory
heat
pump
stand
to
support
unit
12
to
18
in.
off
concrete
base.
See
Fig.
4.
Be
sure
stand
does
not
obstruct
coil
drainage
holes.
Avoid
mounting
unit
in
prevailing
Winds
to
minimize
effect
on
defrost
performance.
Construct
wind
break
if
necessary.
Extend
a
12-in.
gravel
apron
around
pad
for
condensate
and
defrost
water
drainage
field.
Provide
support
bracket
from
structure
or
other
solid
support
to
outdoor
unit
to
give
stability.
Since
it
is
lightweight,
the
outdoor
section
may
be
Fig.
4
—
Unit
Support
Details
mounted
on
a
platform
attached
to
or
built
out
from
structure.
Construct
platform
using
drainage
and
clearance
recommendations
above.
Locate
and
con¬
struct
platform
to
avoid
possible
transfer
of
unit
vibration
to
structure.
See
Table
2
for
unit
weight.
ON
THE
ROOF:
Install
a
level
platform
or
frame
to
support
unit.
Elevate
unit
for
proper
clearance
as
previously
described
for
on-the-ground
installation.
Plan
roof
design
and
water
drainage
to
prevent
unit
from
sitting
in
water.
Flash
all
roof
openings
to
prevent
leaks.
4
Step
3
—
Install
Indoor
Compressor
Section
on
a
level,
rigid,
solid
platform
or
concrete
floor.
Do
not
install
in
a
living
area.
Insert
1/4-in.
asphalt-impregnated
felt
pad
(supplied)
between
unit
basepan
and
mounting
surface
to
provide
full
unit
support
and
vibration
attenuation.
(Do
not
use
vibration
isolators
under
corners
of
basepan.)
Step
4
install
Indoor
Fan-Coil
and
Electric
Heater
as
described
in
Installation
Instructions
supplied
with
this
equipment.
Install
and
connect
thermostats
and
other
controls
as
described
in
the
steps
that
follow.
Step
5
—
Make
Piping
Connections
—
The
38HQ
sections
may
be
connected
to
indoor
fan-coil
using
Carrier
accessory
tubing
packages
or
field-
supplied
tubing
of
refrigerant
grade.
See
Table
2
for
unit
piping
connection
types,
sizes
and
line
size
recommendations
and
Table
4
for
accessory
tubing
sizes.
Maximum
allowable
system
liquid
line
length
is
100
feet.
Maximum
vapor
line
length
from
com¬
pressor
section
to
indoor
coil
is
50
feet.
Maximum
vapor
line
length
from
compressor
section
to
out¬
door
coil
is
50
feet.
When
other
than
25
ft
of
interconnecting
piping
!
is
used,
follow
special
requirements
described
in
^
Refrigerant
Charging.
Do
not
use
less
than
10
ft
of
vapor
or
liquid
line.
Do
not
use
damaged
or
contaminated
tubing.
Always
evacuate
or
purge
indoor
coil,
compressor
section
and
tubing
system.
When
purging,
use
field-
supplied
refrigerant,
not
unit
refrigerant.
When
making
tubing
connections,
be
sure
to
provide
clearance
at
unit
for
electrical
connections.
Follow
tubing
isolation
recommendations
described
previously.
REPLACE
THE
ACCURATER"”
REFRIG¬
ERANT
CONTROL
PISTON(S)
before
connect¬
ing
refrigerant
lines
as
applicable.
Refer
to
tags
attached
to
AccuRater
device.
Replacement
pistons
are
shipped
with
compressor
section
and
are
to
be
installed
as
directed
on
tag.
Replacement
procedure,
briefly
described
below,
is
detailed
on
tag.
Also,
see
AccuRater
Servicing
for
additional
information.
When
connecting
indoor
compressor
section
38HQ227
to
outdoor
coil
section
38HQ940,
remove
no.
4
piston
from
outdoor
coil
AccuRater
device;
replace
with
no.
3
piston.
Attach
AccuRater
identi¬
fication
sticker
to
unit
(replacing
existing
sticker,
if
any).
CONNECT
REFRIGERANT
LINES
to
fittings
on
indoor
and
outdoor
sections.
Fig.
1,
2
and
5.
Indoor
compressor
section
has
2
Compatible
Fitting
vapor
line
connections.
Outdoor
and
indoor
fan-coil
sections
have
Compatible
Fitting
vapor
line
connec¬
tion
and
liquid
line
flare
connection.
Flare
and
connect
liquid
line
from
outdoor
coil
section
to
indoor
fan-coil
unit.
It
is
not
necessary
to
flare
system
liquid
line
if
an
accessory
flare-to-
Fig.
5
—
Refrigerant
Piping
Connections
5
Compatible
Fitting
coupler
is
used
for
liquid
line
connection.
See
accessory
coupler,
Fig.
6.
Connect
vapor
line
from
outdoor
coil
section
to
indoor
compressor
section,
and
from
compressor
section
to
indoor
fan-coil.
Section
vapor
line
as
required
(Fig.
5).
Use
correct
compressor
section
vapor
line
connection
to
indoor
and
outdoor
coils.
Unit
Compatible
Fittings
permit
mechanical
or
sweat
connection
as
described
below.
When
a
1-1/8
in.
field-supplied
vapor
line
is
used
on
38HQ234,
four
field-supplied
3/4-in.
to
1-1/8
in.
vapor
line
adapters
must
be
provided.
Insulate
Refrigerant
Lines
—
After
making
tubing
connections,
the
compressor
section
fittings
must
be
insulated.
Butt
the
Armaflex
tubing
insulation
(pro¬
vided
in
tubing
package)
against
the
Compatible
Fittings.
Secure
the
insulation
with
Prestite
or
an
equivalent
material
which
provides
both
adhesion
and
insulation.
Also
wrap
the
Compatible
Fittings
with
Prestite
to
prevent
sweating.
Mechanical
Connection-to-Compatible
Fitting
(Mate
one
set
of
connections
at
a
time.)
1.
Loosen
nut
on
Compatible
Fitting
one
turn.
Do
not
remove.
2.
Remove
plug
and
be
sure
0-ring
is
in
the
groove
inside
the
Compatible
Fitting.
3.
Cut
tubing
to
correct
length.
4.
Insert
tube
into
Compatible
Fitting
until
it
bottoms.
5.
Tighten
nut
until
it
bottoms
on
back
coupler
flange.
Keep
tube
bottomed
in
Compatible
Fitting
while
tightening
nut.
Sweat
Connection-to-Compatible
Fitting
(Use
refrigerant
grade
tubing.)
1.
Remove
locking
nut,
rubber
O-ring
and
Schrader
core
from
valve.
2.
Cut
tubing
to
correct
length.
3.
Insert
tube
into
Compatible
Fitting.
Wrap
top
and
bottom
of
service
valves
in
wet
cloth
to
pre¬
vent
damage
by
heat.
Solder
with
low
tempera¬
ture
(430
F)
silver
alloy
solder.
4.
Replace
Schrader
core.
5.
Evacuate
or
purge
system
with
field-supplied
refrigerant.
Accessory
Flare-to-Compatible
Fitting
Coupler
is
shown
in
Fig.
6.
Attach
flare
nut
on
coupler
to
flare
fitting
on
unit
liquid
line
connection.
Connect
liquid
line
to
Compatible
Fitting
using
mechanical
or
sweat
connection.
When
mechanical
connection
is
made,
use
2
wrenches
to
tighten
Compatible
Fitting
nut
—
one
to
hold
coupler
and
one
to
tighten
nut.
Fig.
6
—
Accessory
Coupler
Step
6
—
Install
Fan
Control
Package
(factory
supplied;
packaged
separately
inside
indoor
com¬
pressor
section)
—
This
control,
consisting
of
a
transformer
and
a
relay,
provides
high-speed
fan
operation
when
both
compressors
are
energized.
Refer
to
connection
diagram
in
Fig.
7
for
wiring
details.
Install
control
as
follows:
1.
Remove
factory-installed
transformer
from
indoor
fan-coil
unit
electric
heater
package.
Refer
to
40FS
service
instructions
as
required.
2.
Install
fan
control
package
in
upper
right-hand
corner
of
the
40FS.
3.
Route
wires
from
controls
to
heater
package
thru
knockouts
provided.
Restore
transformer
wiring
connections
including
ground
wire.
4.
Connect
black
wire
from
indoor
fan
relay
(IFR)
terminal
no.
4
(or
no.
6)
to
black
wire
from
indoor
fan
relay
no.
2
(IFR-2)
terminal
no.
3.
(Cut
off
male
connector
from
IFR
wire;
supply
wire
nut
to
splice
wires.)
5.
Connect
black
wire
from
IFR-2
terminal
no.
6
to
fan
speed
selector
block
terminal
no.
1
(high
speed).
6.
Connect
blue
wire
from
IFR-2
terminal
no.
1
to
fan
speed
selector
block
terminal
no.
3
(low
speed).
7.
Connect
low-voltage
field
control
wires
between
indoor
compressor
section
and
indoor
fan
relay
(IFR-2)
orange
pigtails
(TB
OA
to
OFR-2,
ter¬
minal
no.
4;
contactor
C-2,
terminal
C
to
IFR-2,
terminal
no.
5).
Field-supplied,
24-gage,
NEC
Class
2
thermostat
wire
may
be
used.
Step
7
—
Install
Outdoor
Ambient
Switch
(OA)
(factory-supplied;
packaged
separately
inside
indoor
compressor
section)
—
This
switch
activates
compressor
no.
2
when
the
first
heating
thermal
balance
point
is
reached.
The
switch
is
installed
in
the
same
manner
as
the
outdoor
thermostat
(step
8),
except
refer
to
Fig.
7
for
correct
wiring.
FAN
CONTROL
PACKAGE
LEGEND
C-2
—
Contactor
IFR
—
Indoor
Fan
Relay
PL
—
Plug,
Fan
SEQ
—
Sequencer
TB
—
Terminal
Board
Tran
—
Transformer
#
Junction
o
Component
Connection
(Marked)
Field
Splice
HiW
Field
Power
Wiring
Field
Ground
Wiring
_Field
Control
Wiring
NOTES:
1
Use
copper
conductors
only.
2
May
be
terminal
board
or
fuse
block
depending
on
heater
model
used
3
Will
be
terminal
no
4
on
40FQ916
models,
and
terminal
no
6
on
40FQ920
models
THERMOSTAT
40FQ
SUBBASE
ELECTRIC
HEATER
HH93AZ073
0R
TERMINAL
HH93AZ075
BOARD
38HQ
COMPRESSOR
SECTION
TERMINAL
BOARD
THERMOSTAT
40FQ
SUBBASE
ELECTRIC
HEATER
HH93AZ0730R
TERMINAL
HH93AZ075
BOARD
38HQ
COMPRESSOR
SECTION
TERMINAL
BOARD
(38HQ
WITH
40FS/28HQ,VQ
EQUIPPED
WITH
ELECTRIC
HEATER;
EMERGENCY
HEAT,
ONE
OUTDOOR
THERMOSTAT)
THERMOSTAT
SUBBASE
HH93AZ073
OR
HH93AZ075
40FQ
ELECTRIC
HEATER
TERMINAL
BOARD
38HQ
COMPRESSOR
SECTION
TERMINAL
BOARD
COOLING
AND
TWO-STAGE
HEATING
(38HQ
WITH
40FS/28HQ,VQ
EQUIPPED
WITH
ELECTRIC
HEATER;
EMERGENCY
HEAT,
NO
OUTDOOR
THERMOSTATS)
THERMOSTAT
40FQ
38HQ
SUBBASE
ELECTRIC
HEATER
COMPRESSOR
HH93AZ0730R
TERMINAL
SECTION
HH93AZ075
BOARD
TERMINAL
BOARD
EQUIPPED
WITH
ELECTRIC
HEATER;
EMERGENCY
HEAT,
TWO
OUTDOOR
THERMOSTATS)
DFT
—
Defrost
Thermostat
EHR
—
Emergency
Heat
Relay
OA
—
Outdoor
Ambient
Switch
ODT
—
Outdoor
Thermostat
_
Factory
Wiring
_Field
Wiring
^Transformer
(75
va)
located
in
fan
control
package
tTerminal
L
is
identified
as
terminal
X
on
some
former
thermostats
(Required
for
system
malfunction
warning
indicator
on
compressor
section
)
^Remove
1
or
both
factory-installed
jumpers
(connection
B)
when
installing
outdoor
ther¬
mostats
(ODT)
shown
in
connections
C
and
D
Fig.
7
—
Control
Circuit
Connections
7
Attach
one
lead
to
compressor
terminal
board
connection
OA.
Connect
other
lead
to
line
side
of
defrost
thermostat.
Set
switch
at
temperature
of
first
thermal
balance
point
(heating).
This
balance
point
is
provided
by
CLIC
load
estimating
program.
Further
adjust¬
ments
can
be
made
following
operating
experience.
Step
8
—
Install
Room
Thermostat,
Outdoor
Thermostat(s)
and
Emergency
Heat
Relay
—
Follow
Installation
Instructions
shipped
with
these
accessories
plus
the
instructions
in
the
sections
that
follow.
Connect
as
described
in
step
9.
INDOOR
THERMOSTAT
—
Use
only
Carrier
indoor
thermostat
and
subbase
as
shown
in
Table
4.
Set
heat
anticipator
settings
according
to
Table
5.
These
settings
may
be
changed
slightly
to
provide
a
greater
degree
of
comfort
for
certain
installations.
Table
5
—
Thermostat
Heat
Anticipator
Settings
INDOOR
COM
PR
SECTION
OUTDOOR
COIL
SECTION
INDOOR
UNIT
WITH
ELECTRIC
HTR
HTR
KW
ANTICIPATOR
SETTINGS
First
Stage
Second
Stage
38HQ227
38HQ940
40FS160
with
40FQ916010
thru
090
8
thru
20
Fixed
16
38HQ234
38HQ960
40FS200
with
40FQ920060
thru
150
10
thru
25
Fixed
49
OUTDOOR
THERMOSTAT
ACCESSORY
pro¬
vides
adjustable
outdoor
control
of
accessory
electric
heater
(used
on
indoor
fan-coil).
This
ther¬
mostat
closes
on
a
drop
in
outdoor
temperature.
It
energizes
a
stage
of
electric
heat
when
the
out¬
door
temperature
setting
is
reached,
provided
the
room
thermostat
is
on
the
second
stage
of
heating.
One
outdoor
thermostat
is
recommended
for
each
stage
of
electric
heat
after
the
first
stage.
Connect
as
described
in
Step
9.
Set
the
outdoor
thermostats
progressively
lower
for
each
stage.
Refer
to
heat
load
of
building
and
unit
capacity
to
determine
the
correct
outdoor
thermostat
settings.
Locate
maxi¬
mum
of
2
outdoor
thermostats
in
control
voltage
section
of
outdoor
coil
section
junction
box.
Fasten
in
place
with
sheet
metal
screws.
EMERGENCY
HEAT
RELAY
—
This
accessory
is
required
when
2
or
more
outdoor
thermostats
are
used.
It
is
automatically
energized
by
the
manually-
operated
emergency
heat
switch
in
the
indoor
ther¬
mostat
subbase.
The
indoor
thermostat
locks
out
the
compressor
and
the
relay
bypasses
the
outdoor
thermostats
for
electric
heater
operation
during
heat
pump
shutdown.
When
one
outdoor
thermostat
is
used,
an
emergency
heat
relay
is
not
required.
The
emergency
heat
switch
in
the
indoor
thermostat
subbase
bypasses
the
outdoor
thermostat,
locks
out
the
compressor
and
activates
the
electric
heater.
Install
emergency
heat
relay
in
a
convenient
loca¬
tion
on
indoor
unit.
Attach
with
sheet
metal
screw.
Connect
relay
as
shown
in
Fig,
7.
Step
9
—
Make
Electrical
Connections
—
In¬
stall
field
wiring
in
accordance
with
local
and
national
fire,
safety
and
electrical
codes.
Be
sure
voltage
to
units
is
within
±
10%
of
voltage
indi¬
cated
on
nameplate.
Contact
local
power
company
for
correction
of
improper
line
voltage.
When
making
electrical
connections,
provide
clearance
at
unit
for
refrigerant
piping
connections.
See
Table
6
for
recommended
wire
and
fuse
sizes.
Line
power
connections
and
control
circuit
connec¬
tions
are
shown
in
Fig.
7
and
8.
Route
line
and
control
power
wiring
for
38HQ
outdoor
coil
from
connections
in
the
38HQ
in¬
door
compressor
section.
Use
14-ga
(minimum)
line
power
wire
size
to
outdoor
coil
section
when
total
wire
length
connecting
compressor
section
to
coil
is
under
25
feet.
If
over
25
ft,
use
same
wire
size
as
compressor
section
branch
circuit.
Table
6
—
Electrical
Data
INDOOR
COMPR
SECTION
OUTDOOR
COIL
SECTION
VOLTAGE
COMPR
1
COMPR
2
OFM
(FLA)
BRANCH
CIRCUIT
-
n
Nom
1-Ph
60-Hz
1
1
1
Operating*
Power
Wire
]
Gnd
Wire
Sizet
(AWG)
Min
Ckt
Amps
Max
Fuse
Amps**
_
Min
Size
(AWG)
Max
Ft
1
Max
Min
LRA
RLA
LRA
RLA
ICS
OCS
ICS
OCS
ICS
OCS
38
H0227
38HQ940
230
254
207
72
17
88
1
17
8
1
5
6
14t
55
25t
10
14t
40
8
38HQ234
38HQ960
230
254
207
88
20
94
S
__
1
21
2
2
3
4
14t
75
25t
10
14t
48
8
60
FLA
—
Full
Load
Amps
ICS
—
Indoor
Compressor
Section
LRA
—
Locked
Rotor
Amps
OCS
—
Outdoor
Coil
Section
OFM
—
Outdoor
Fan
Motor
RLA
—
Rated
Load
Amps
^Permissible
limits
of
the
voltage
range
(for
limited
period
of
time)
at
which
the
units
will
operate
satisfactorily
fOutdoor
coil
section
wiring
—
for
25
ft
wire
run
or
less,
use
minimum
14
AWG
size
wire
For
longer
wire
run
use
same
size
as
supply
to
compressor
section
^Required
when
using
nonmetallic
conduit
**Maximum
dual
element
fuse
size
NOTES;
1
All
units
have
24-v
control
circuit
which
requires
external
power
source
2
Copper
wire
size
table
based
on
60
C
Use
copper
or
copper-clad
aluminum
wire
to
indoor
section;
copper
wire
only
to
outdoor
section
Use
latest
National
Electrical
Code
for
wire
sizing
8
FACTORY
WIRING
Fig.
8
—
Line
Power
Connections
INSTALL
A
BRANCH
CIRCUIT
DISCONNECT
PER
N.E.C.
of
adequate
size
to
handle
compressor
section
starting
current.
Provide
a
separate
dis¬
connect
switch
for
outdoor
coil
section.
Provide
a
separate
disconnect
for
indoor
fan-coil
and
for
each
accessory
electric
heater
circuit
as
required,
(See
In¬
door
Unit
and
Electric
Heater
Installation,
Start-Up
and
Service
Instructions.)
Locate
disconnect(s)
within
sight
of
and
readily
accessible
to
the
units,
per
section
440-14
of
National
Electrical
Code
(NEC).
ROUTE
LINE
POWER
LEADS
INTO
COM¬
PRESSOR
SECTION
—
Extend
lead
from
discon¬
nect
per
N.E.C.
thru
1-1/8
in.
hole
provided
in
com¬
pressor
section
top
panel
(Fig.
2)
and
into
control
box.
Extend
line
power
leads
for
outdoor
coil
section
thru
7/8-in.
hole
provided
in
compressor
section
top
panel
and
into
control
box.
CONNECT
GROUND
LEADS
AND
POWER
WIRES
—
Connect
ground
leads
to
the
ground
lug
in
control
box
for
safety.
Splice
compressor
section
line
power
leads
to
yellow
and
black
pigtails,
and
outdoor
coil
section
power
leads
to
brown
and
blue
pigtails.
Use
wire
nuts
and
tape
at
each
splice
con¬
nection
as
shown
in
Fig.
8.
CONNECT
POWER
LEADS
FROM
INDOOR
COMPRESSOR
SECTION
TO
OUTDOOR
COIL
SECTION
thru
secondary
disconnect
switch.
From
this
disconnect
switch
extend
leads
thru
hole
provided
in
outdoor
coil
section
basepan
(Fig.
1)
and
into
line
voltage
section
of
junction
box.
Fig.
14.
Splice
leads
to
black
and
blue
pigtails
with
wire
nuts.
CONNECT
CONTROL
WIRING
(24-v)
—
Extend
wiring
thru
7
/
8-in.
grommeted
hole
in
compressor
section
top
panel
(Fig.
2),
and
to
control
wiring
terminal
board
on
side
of
control
box.
Connect
leads
to
terminal
board
as
shown
in
Fig.
7.
Extend
and
connect
control
wiring
from
compressor
section
to
outdoor
coil
section
as
required.
Make
splice
connections
in
low-voltage
section
of
coil
junction
box.
Use
indoor
fan-coil
transformer
as
24-v
supply
for
system.
Be
sure
fan
control
package
is
installed
as
described
in
Step
6.
Package
contains
75-va
trans¬
former
of
adequate
capacity
to
handle
system
current.
INITIAL
START-UP
The
compressors
in
the
indoor
compressor
section
are
equipped
with
crankcase
heaters.
It
is
recommended
that
the
heaters
be
energized
a
minimum
of
24
hours
before
starting
the
system.
To
energize
crankcase
heaters
only,
set
the
thermostat
at
OFF
position
and
turn
on
main
power
to
compressor
section.
To
Start
System
—
(Be
sure
crankcase
heaters
have
been
energized
for
24
hours.)
Adjust
the
ther¬
mostat
as
follows:
1.
Set
selector
switch
at
OFF.
2.
Turn
on
main
disconnect
switch(es)
to
indoor
and
outdoor
units.
3.
Set
fan
switch
as
desired
(ON
or
AUTO.).
4.
Set
thermostat
dial
at
desired
temperature.
5.
Set
selector
switch
at
HEAT
or
COOL.
Check
system
refrigerant
charge.
See
Service
—
Refrigerant
Charging.
SEQUENCE
OF
OPERATION
Fan
Switch
at
AUTO.
Position,
Thermostat
at
ON
Position
(Crankcase
heater
is
on
as
soon
as
the
field
power
supply
is
on.)
THERMOSTAT
CALLS
FOR
COOLING
1.
First-stage
cooling
thermostat
(Co)
closes
and
the
reversing
valve
solenoid
(RVS)
is
energized.
The
RVS
actuates
the
reversing
valve
and
switches
the
system
to
cooling.
2.
Second-stage
cooling
thermostat
(Cl)
closes.
If
the
low-pressure
switch
(LPS)
is
closed,
com¬
pressor
contactor
(C)
is
energized
and
compres-
9
sor
no.
1
starts.
At
the
same
time,
the
outdoor
fan
motor
(OFM)
starts
and
the
defrost
timer
(DT)
is
energized
although
it
is
not
functional
in
the
cooling
mode;
the
indoor
fan
relay
(IFR)
is
energized
and
the
indoor
fan
motor
(IFM)
starts.
Compressor
no.
2
does
not
run
in
COOL
mode.
When
the
second
stage
of
cooling
is
satisfied,
Cl
opens.
The
compressor
stops;
the
indoor
and
out¬
door
fans
stop;
DT
is
de-energized.
When
the
con¬
trolled
temperature
drops
approximately
1
F
below
the
cooling
set
point,
Co
opens.
RVS
is
de-energized
and
the
reversing
valve
switches
to
heating
(normal
position).
The
unit
is
shut
down
except
for
the
two
compressor
crankcase
heaters,
which
remain
on
as
long
as
the
field
power
supply
is
on.
THERMOSTAT
CALLS
FOR
HEATING
(The
reversing
valve
is
de-energized,
in
heating
position.)
1.
First
stage
heating
thermostat
(HI)
closes.
Com¬
pressor
contactor
no.
1
(Cl)
is
energized
and
compressor
starts;
outdoor
fan
motor
(OFM)
starts;
defrost
timer
(DT)
is
energized.
Indoor
fan
relay
(IFR)
is
energized
and
indoor
fan
motor
(IFM)
starts.
When
the
outdoor
ambient
switch
(OA)
closes
(at
first
thermal
balance
point),
compressor
contactor
no.
2
(C2)
is
ener¬
gized
and
compressor
no.
2
starts.
Compressor
no.
1
and
compressor
no.
2
operate
simul¬
taneously
as
long
as
OA
is
closed.
The
crankcase
heaters
are
de-energized
when
both
compressors
are
running.
2.
Second-stage
heating
thermostat
(H2)
closes
and
activates
the
first
accessory
heater
element
sequencer
thru
indoor
thermostat
terminal
W2.
The
first-stage
electric
heater
element
is
energized
immediately
and
the
other
heater
elements
are
energized
at
regular
intervals
thru
the
sequencers.
Separate
outdoor
thermostats
may
be
used
to
energize
the
second
sequencer
and
bring
on
addi¬
tional
heater
elements
if
more
incremental
heat
control
is
desired.
When
the
second
stage
of
heating
is
satisfied,
H2
opens
and
the
electric
heater(s)
shuts
off.
When
the
first
stage
of
heating
is
satisfied,
HI
opens
and
the
unit
shuts
down,
except
for
the
compressor
crank¬
case
heater,
which
remains
on
as
long
as
the
field
power
supply
is
on.
Unit
Controls
and
Safety
Devices
HIGH-PRESSURE
RELIEF
VALVE
is
located
in
compressor.
Relief
valve
opens
at
a
pressure
differential
of
approximately
500
psi
between
suction
(low
side)
and
discharge
(high
side)
to
allow
pressure
equalization.
INTERNAL
CURRENT
AND
TEMPERATURE
SENSITIVE
OVERLOAD
resets
automatically
when
internal
compressor
motor
temperature
drops
to
a
safe
level
(overloads
may
require
up
to
45
min¬
utes
to
reset).
When
an
internal
overload
is
suspected
of
being
open,
check
by
using
an
ohmmeter
or
con¬
tinuity
tester.
If
necessary,
refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
2,
Electrical,
for
complete
instructions.
LOW-PRESSURE
SWITCH
is
located
in
compres¬
sor
section
on
suction
line
between
reversing
valve
and
accumulator.
Provides
loss-of-charge
protec¬
tion
by
shutting
compressor
off
if
suction
pressure
drops
below
setting.
Low-pressure
switch
settings
are:
open,
5
±
3
psig;
close,
20
±
5
psig.
CRANKCASE
HEATERS
are
activated
by
a
relay.
Heaters
derive
power
from
contactor
no.
2
and
are
energized
when
compressors
are
off
or
when
only
one
compressor
is
functioning.
The
heater
keeps
the
crankcase
warm
during
the
off
cycle
and
thus
prevents
dilution
of
the
oil
with
the
refrigerant,
assures
good
lubrication,
and
pre¬
vents
loss
of
oil
from
crankcase
during
start-up.
If
the
electrical
disconnect
switch
to
the
compres¬
sor
section
has
been
off
for
an
extended
period
of
time,
the
crankcase
heater
should
be
energized
for
24
hours
before
starting
the
compressor.
SIGNAL-LOC
™
SYSTEM
MALFUNCTION
WARNING
INDICATOR
AND
LOCKOUT
^
Indoor
compressor
section
is
equipped
with
a
solid-
state
warning
logic
circuit
that
protects
the
system.
In
case
of
a
malfunction
(compressors
do
not
oper¬
ate
due
to
safety
device
cutout),
emergency
heat
light
on
thermostat
comes
on
and
compressors
are
pre¬
vented
from
restarting.
Compressors
can
be
re¬
started
after
resetting
thermostat
(turn
thermostat
off
then
on).
If
either
compressor
malfunctions,
both
will
be
locked
out
(prevented
from
restarting).
The
emergency
heat
light
goes
out
when
com¬
pressors
are
restarted
or
when
indoor
thermostat
is
satisfied.
If
the
light
does
not
stay
out
after
two
or
three
attempts
to
restart,
check
for
cause
of
malfunction.
DEFROST
CONTROL,
consisting
of
a
defrost
timer,
defrost
thermostat
and
defrost
relay,
inter¬
rupts
normal
system
heating
operation
every
90
minutes
to
defrost
outdoor
coil,
if
the
coil
saturated
suction
temperature
indicates
freezing
tempera¬
tures.
Defrost
control
simultaneously
stops
outdoor
fan,
energizes
reversing
valve
solenoid
to
return
system
to
cooling
cycle
(outdoor
coil
as
condenser,
indoor
fan-coil
unit
as
evaporator),
and
activates
accessory
electric
heater.
For
the
heat
pump
to
defrost,
2
conditions
are
necessary;
1.
Defrost
timer
contacts
must
be
closed.
2.
Refrigerant
temperature
from
outdoor
unit
must
be
cold
enough
to
cause
defrost
thermostat
contacts
to
close.
Contacts
close
at
27
(±
4)
F.
Every
90
minutes
of
elapsed
running
time,
the
de¬
frost
timer
contacts
close
for
10
seconds.
If
the
defrost
thermostat
contacts
are
closed,
the
unit
defrosts.
The
defrost
timer
limits
defrosting
period
to
10
minutes.
Normally
the
frost
is
removed
and
the
10
defrost
thermostat
contacts
will
open
to
terminate
defrosting
before
10
minutes
have
elapsed.
The
defrost
thermostat
contacts
open
at
80
(±
6)
F
liquid
refrigerant
temperature.
When
defrosting
is
ter¬
minated,
the
outdoor
fan
motor
is
energized
and
the
reversing
valve
solenoid
is
de-energized
returning
unit
to
heating
cycle.
If
the
defrost
thermostat
contacts
are
open,
(no
need
for
defrost
cycle),
system
operates
for
another
90-minute
interval
before
attempting
another
defrost
cycle.
SERVICE
Heat
Pump
Circuits
shown
in
Fig.
9
are
refrigerant
flow
diagrams
for
heating
and
cooling
cycles.
Refrigerant
Charging
—
Each
indoor
compressor
section
is
shipped
with
a
vapor
holding
charge;
out¬
door
coil
section
contains
partial
system
charge
as
shown
in
Table
7.
Add
refrigerant
to
system
so
that
total
required
charge
is
attained
as
described
below.
Refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Refrigerants
for
additional
information.
Adjust
system
charge
for
refrigerant
line
lengths
and
diameters
that
differ
from
25
ft
and
3/
8-in.
O.D.
(liquid
line),
respectively,
using
refrigerant
weights
Table
7
—
Service
Data
SYSTEM
Indoor
Compr
Section
38HQ227
38HQ234
Outdoor
Coil
Section
38HQ940
38HQ960
Fan
Propeller,
Direct
Drive
Cfm
3100
3600
Rpm
1015
1080
Diam
(in.)
20
20
Motor
Hp
1/5
1/4
Factory
Charge
(lbs,
R-22)
7
1
100
Total
Req'd
Charge
(lbs,
R-22)
92
11
0
Additional
Charge
Req'd
(lbs)
2
1
1
0
shown
in
table
below.
(Twenty-five
feet
of
3/8-in.
O.D.
tubing
contains
14.4
oz
of
R-22.)
Add
R-22
charge
to
system
if
liquid
line
is
over
25
ft;
remove
charge
if
liquid
line
is
shorter
than
25
feet.
LIQUID
LINE
OUNCES
OF
R-22/FT
LENGTH
DIAM
(in.)
OF
LIQUID
LINE
3/8
58
5/16
36
1/4
1
21
When
recharging
is
necessary
during
heating
or
cooling
season,
weigh
in
total
charge
indicated
in
Table
7.
(Charge
must
be
weighed
in
during
heating
season.)
Remove
any
refrigerant
remaining
in
sys¬
tem
before
recharging.
If
system
has
lost
complete
(COOLING
CYCLE)
BYPASS
ACCURATER
BYPASS
ACCURATER
STRAINER
SERVICE
VALVES
(HEATING
CYCLE)
BYPASS
-
ACCURATER
STRAINER
SERVICE
VALVES
Fig.
9
—
Refrigerant
Flow
Diagrams
charge,
evacuate
system
to
500
microns
(29.7
in.
vacuum)
before
recharging.
Service
port
connec¬
tions
are
provided
on
indoor
compressor
unit
suction
and
discharge
lines
for
evacuation
and
charging.
(See
Fig.
14
for
service
port
location.)
Dial-a-charge
charging
cylinder
is
an
accurate
de¬
vice
used
to
recharge
systems
by
weight.
The
cylinders
are
available
at
refrigeration
supply
firms.
TO
CHECK
AND/
OR
ADJUST
CHARGE
DUR¬
ING
COOLING
SEASON
—
Use
correct
Cooling
Cycle
Charging
Chart
(Fig.
10
and
11)
and
follow
charging
chart
usage
method
below.
TO
CHECK
SYSTEM
OPERATION
DURING
HEATING
CYCLE
—
Use
correct
Heating
Cycle
Operation
Check
Chart
(Fig.
12
and
13).
These
charts
indicate
whether
a
correct
relationship
exists
between
system
operating
pressures
and
air
temperatures
entering
indoor
and
outdoor
units.
If
pressure
and
temperature
lines
do
not
intersect
on
chart,
the
system
refrigerant
charge
may
not
be
correct
or
other
system
abnormalities
may
exist.
Do
not
use
Operation
Check
Charts
to
adjust
refrigerant
charge.
Weigh
charge
into
system.
USING
COOLING
CYCLE
CHARGING
CHARTS
1.
O
perate
unit
a
minimum
of
10
minutes
before
checking
charge,
and
after
each
charge
adjustment.
2.
Measure
suction
pressure
by
attaching
a
gage
to
indoor
unit
suction
service
port.
(See
Fig.
14
for
correct
service
port
location.)
3.
Measure
outdoor
air
dry-bulb
temperature
enter¬
ing
outdoor
coil.
Use
a
service
thermometer.
4.
Using
a
sling
psychrometer,
measure
wet-bulb
temperature
of
air
entering
indoor
fan-coil
unit.
5.
Refer
to
correct
Charging
Chart.
Locate
on
curves
where
outdoor
air
dry-bulb
and
indoor
air
wet-bulb
temperature
lines
intersect.
6.
From
intersect
point,
project
vertically
down¬
ward
to
chart
suction
pressure
line.
Compare
chart
suction
pressure
to
unit
suction
pressure
(Step
2).
7.
If
unit
suction
pressure
is
lower
than
chart
pres¬
sure,
add
refrigerant
to
system
until
chart
pres¬
sure
is
reached.
If
unit
suction
pressure
is
higher
than
chart
pressure,
remove
refrigerant
until
chart
pressure
is
reached.
Temporary
Capacitance
Boost
—
If
necessary,
see
Carrier
Standard
Service
Techniques
Manual,
Chapter
2,
Electrical,
for
details.
Fig.
10
—
38HQ227/38HQ940
with
28VQ036/40FS160
Cooling
Cycle
Charging
Chart
12
Fig.
11
—
38HQ234/38HQ960
with
28VQ042/40FS200
Cooling
Cycle
Charging
Chart
DISCHARGE
PRESSURE
(PSIG)
AT
SERVICE
PORT
DISCHARGE
PRESSURE
(PSIG)AT
SERVICE
PORT
38HQ234/38HQ960
with
28VQ042/40FS200
Heating
Cycle
Operation
Check
Charts
Compressor
Removal
—
See
Table
2
for
com¬
pressor
information;
Fig.
14
for
component
loca¬
tion.
Shut
off
power
to
unit.
Remove
refrigerant
from
system
using
refrigerant
removal
methods
described
in
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Refrigerants.
Follow
safety
codes,
and
wear
safety
glasses
and
work
gloves.
Have
quenching
cloth
available.
If
either
compressor
fails
due
to
motor
burnout,
it
is
necessary
to
replace
both
compressors.
Since
both
compressors
use
common
oil,
one
compressor
burnout
contaminates
both
compressors.
1.
Remove
unit
top
cover
and
front
access
wrapper.
2.
Remove
compressor
terminal
box
cover,
dis¬
connect
and
remove
compressor
power
leads.
3.
Using
a
tubing
cutter,
cut
suction
and
discharge
lines
at
convenient
place
near
compressor
for
easy
reassembly
to
new
compressor
with
copper
slip
couplings.
4.
Disconnect
equalizer
tube
from
compressor
shell.
5.
Remove
crankcase
heater
from
compressor
base.
6.
Remove
compressor
hold-down
bolts.
Lift
out
compressor.
7.
Carefully
unbraze
suction
and
discharge
line
piping
stubs
from
compressor.
If
oil
vapor
in
piping
stubs
ignites,
use
quenching
cloth.
8.
Braze
piping
stubs
(removed
in
step
7)
onto
new
compressor.
9.
Clean
system.
Add
new
liquid
line
heat
pump
filter-drier
as
described
below.
10.
Install
new
compressor
in
unit.
Braze
suction
and
discharge
lines
to
compressor
piping
stubs
(at
points
where
cut,
step
3)
using
field-supplied
copper
couplings.
Reconnect
equalizer
tube.
Teflon
O-ring
in
fitting
is
reusable.
Torque
fitting
to
30-40
ft-lb.
Ensure
compressor
hold¬
down
bolts
are
in
place.
Connect
wiring.
11.
Evacuate
and
recharge
system.
Lubrication
—
Compressor
contains
factory
oil
charge.
Replace
oil
when
lost.
See
Table
2
for
oil
recharge.
If
necessary,
refer
to
Carrier
Standard
Service
Techniques
Manual,
Chapter
1,
Refrig¬
erants,
pages
1-21,
for
oil
recharging
procedure.
Use
Carrier
PP33-1,
Texaco
Capella
B
or
Suniso
3G
oil.
Filter-Drier
—
Install
accessory
heat
pump
filter-
drier
(Table
4)
in
system
liquid
line
when
refrig¬
erant
system
is
opened
for
service
as
described
under
Compressor
Removal.
Position
drier
in
liquid
line
at
convenient
location.
Pumpdown
Procedure
(Cooling
Cycle)
—
The
38HQ
units
may
be
pumped
down
in
order
to
make
repairs
on
low
side
of
system
without
losing
com¬
plete
refrigerant
charge.
VAPOR
LINE
CONNECTIONS'
.COMPRESSOR
NO
1
REVERSIN)
VALVE
DISCHARGE
LINE
COMPRESSOR
■
SCHRADER
FITTING
SUCTION
LINE
ACCUMULATOR
LOW
PRESSURE
SWTCH
COMPRESSOR
NO
TERMINAL
BOX
CRANKCASE
HEATER
INDOOR
COMPRESSOR
SECTION
RUN|
CAPACITOR
^‘^^ER
CONTROL
'run
■
CAPACITOR
N0.2
CONTROL
WIRE
TERMINAL
BOARD
CONTROL
BOX
MUFFLER
SCHRADER
FITTING
DEFROST
START
TIMER
CAPACITORS
NO
2
SIGNAL-LOG"
NOI
NO
2
COMPRESSOR
'CONTACTOR
NO.
I
NO.
2
INDOOR
COMPRESSOR
SECTION-TOP
VIEW
ACCESSORY
OUTDOOR
THERMOSTAT
LOCATION
CONTROL
VOLTAGE
SECTION
DEFROST
THERMOSTAT'
LIQUID
LINE
SERVICE
VALVE
(WITH
SERVICE
PORT)
VAPOR
LINE
SERVICE
VALVE
(WITH
SERVICE
PORT)
38HQ
OUTDOOR
COIL
SECTION
Fig.
14
—
Component
Location
14
1.
Attach
pressure
gage
to
suction
service
port.
2.
Frontseat
the
liquid
line
valve
on
the
outdoor
coil
section.
3.
Start
system
and
run
until
suction
pressure
reaches
5
psig
(see
Caution)
or
low-pressure
switch
opens.
4.
Shut
off
system.
Frontseat
vapor
line
valve
on
outdoor
coil
section.
5.
Vent
remaining
pressure.
AccuRateF“
(Bypass
Type)
Servicing
—
See
Fig.
15
for
bypass-type
AccuRater
components.
The
piston
has
a
refrigerant
metering
orifice
thru
it.
The
retainer
forms
a
stop
for
the
piston
in
the
refrigerant
bypass
mode,
and
a
sealing
surface
for
liquid
line
flare
connection.
To
check,
clean
or
replace
piston:
1.
Shut
off
power
to
unit.
2.
Pump
unit
down
using
Pumpdown
Procedure
described
previously.
3.
Remove
liquid
line
flare
connection
from
AccuRater.
4.
Pull
retainer
out
of
body
being
careful
not
to
scratch
flare
sealing
surface.
If
retainer
does
not
pull
out
easily,
carefully
use
locking
pliers
to
remove
retainer.
5.
Slide
piston
out
by
inserting
a
small,
soft
wire
thru
metering
orifice
(18-gage
thermostat
wire).
See
that
metering
orifice,
sealing
surface
around
piston
cones
and
fluted
portion
of
piston
are
not
damaged.
6.
Clean
piston
refrigerant
metering
orifice.
Fig.
15
—
AccuRater
™
(Bypass
Type)
Components
7.
R
eplace
retainer
O-ring
before
reassembling
bypass-type
AccuRater.
Carrier
O-ring
part
no.
is
99CC501052.
Liquid
Line
Strainer
(protects
AccuRater)
made
of
wire
mesh
is
located
in
the
liquid
line
inside
indoor
fan-coil
unit
behind
liquid
line
service
valve
(Fig.
9).
Liquid
line
is
belled
and
sweat
con¬
nected
where
strainer
is
located.
If
strainer
is
plugged,
unsweat
belled
liquid
line
connection
and
replace
strainer.
Compatible
Fitting
Repair
LEAKING
MECHANICAL
CONNECTION
—
Frontseat
outdoor
section
service
valves
and
relieve
refrigerant
pressure
in
tubing
and
compressor
section.
Back
off
locknut
from
Carrier
Compatible
Fitting
onto
tube.
Cut
fitting
between
threads
and
seal
ring
bead
as
shown
in
Fig.
17.
Remove
tubing
section
remaining
in
threaded
portion
of
fitting.
Discard
locknut.
Clean,
flux
and
insert
new
tube
end
into
remain¬
ing
portion
of
Carrier
Compatible
Fitting,
Wrap
valve
base
(outdoor
unit)
in
wet
cloth.
Heat
and
apply
low-temperature
solder
(430
F).
LEAKING
SWEAT
CONNECTION
—
Frontseat
service
valves
and
relieve
refrigerant
pressure
in
tubing.
Clean
and
flux
area
around
leak
and
apply
low-temperature
solder
(430
F).
Evacuate
or
purge
indoor
fan-coil,
compressor
section
and
tubing
system.
Add
refrigerant
charge
as
described
in
Service,
Refrigerant
Charging.
LEAKING
FLARE
CONNECTION
—
Cut
and
reflare
3/8-in.
system
liquid
line.
MAINTENANCE
OUTDOOR
FAN
MOTOR
BEARINGS
are
pre¬
lubricated
for
3
years
heavy
duty
or
5
years
normal
duty.
When
lubrication
is
necessary,
it
should
be
lubricated
in
a
motor
repair
shop.
Outdoor
Coil
Cleaning
—
Ensure
power
to
unit
is
shut
off.
Clean
the
outdoor
unit
coil
with
water
at
the
beginning
of
every
cooling
season
or
more
often
if
required.
Use
ordinary
garden
hose
at
a
pressure
high
enough
to
clean
efficiently.
For
best
results,
unscrew
and
remove
unit
top
cover
(grille).
Insert
hose
nozzle
between
fan
blades
and
spray
coil
fins
from
inside-to-outside
the
unit.
If
unit
has
a
double-row
coil,
loosen
screws
to
separate
coils,
carefully
pull
outer
row
of
coils
away
slightly
from
inner
row.
Do
not
strain
coil
tubing
connections.
Flush
dirt
toward
outside
of
both
coils.
Flush
dirt
from
basepan
by
spraying
water
thru
top
of
unit.
Avoid
splashing
mud
on
coil
or
water
on
fan
motor.
Make
sure
that
water
drainage
holes
under
outdoor
coil
are
not
obstructed.
15
Outdoor
Fan
Adjustment
—
Required
fan
posi¬
tion
is
shown
in
Fig.
16.
Adjust
fan
by
loosening
set¬
screws
and
moving
fan
blades
up
or
down.
FAN
MOTOR
REMOVAL
1.
Shut
off
power
to
outdoor
coil.
2.
Remove
top
cover
(grille).
Open
or
remove
service
door.
Remove
junction
box
cover.
3.
Disconnect
fan
motor
leads
in
line-voltage
sec¬
tion
of
junction
box.
See
Fig.
14.
4.
Remove
fan
from
motor
shaft
by
loosening
setscrews
and
pulling
upward
on
fan
hub.
5.
Remove
bolt
holding
fan
motor
to
motor
mount¬
ing
bracket.
Remove
motor
with
wiring
thru
top
of
unit.
To
replace
motor:
place
motor
on
motor
mount¬
ing
bracket
and
retighten
bolt.
Before
replacing
metal
fan,
be
sure
rain
shield
(Fig.
16)
is
in
place
on
motor
shaft.
Fig.
17
—
Carrier
Compatible
Fitting
16
TROUBLESHOOTING
GUIDE
—
COOLING
SYMPTOM
AND
PROBABLE
CAUSE
PROBABLE
REMEDY
COMPRESSOR
WILL
NOT
RUN
OR
SHUTS
OFF
—
WILL
NOT
RESTART
Contactor
open
1.
Burned
out
transformer,
open
thermostat
circuit,
open
overload.
2.
Power
supply
interrupted.
3.
Power
circuit
is
open
due
to
loose
electrical
connection,
open
compressor
safety
device.
Contactor
or
coil
defective.
4.
Signal-Loc
™
malfunction.
1.
Check
control
circuit
component
and
wiring.
Refer
to
unit
label
diagram,
check
all
safety
devices.
Refer
to
Standard
Service
Techniques
Manual,
Chapter
2,
Electrical.
2.
Check
for
blown
fuses
or
tripped
circuit
breakers.
3.
Check
power
wire
connection
for
tightness.
Check
compressor
internal
thermostat,
overloads
(see
label
diagram).
Check
contactor,
replace
if
defective.
4.
Check
wire
connections.
Check
continuity
thru
terminals
2
and
3.
Check
to
see
if
power
wire
has
been
routed
thru
current
loop.
Contactor
Closed,
or
Closes
then
Opens
1.
Compressor
power
is
out,
compressor
motor
is
burned
out
or
internal
overloads
are
open.
Timer
circuit
(clock
or
switch)
is
faulty.
2.
Compressor
stuck.
3.
Control
circuit
open
due
to
faulty
low-voltage
transformer
or
defective
control
circuit
compartment.
1.
Check
main
power
supply
and
wiring.
Refer
to
Electrical
Data
table
and
label
diagram.
Check
defrost
timer
circuit
relay.
Check
defrost
control
contacts.
Replace
defective
controls.
2.
Check
start
capacitor.
Check
compressor
motor
windings.
3.
Review
label
diagrams.
Check
control
power
wires,
connections.
Check
control
transformer
power
output
(24
v).
Check
remote
control
center
contacts
and
temperature
settings.
COMPRESSOR
RUNS
BUT
COOLING
IS
INSUFFICIENT
1.
Low
suction
pressure
or
incorrect
superheat.
2.
Restricted
airflow
due
to
dirty
filters,
duct
obstruction
or
indoor
coil
icing.
Refrigerant
system
obstructed.
Filter-drier
obstructed
or
refrigerant
flow
is
insufficient.
3.
High
suction
pressure/low
head
pressure
due
to
open
internal
pressure
relief,
defective
com¬
pressor
valves
or
faulty
reversing
valve.
4.
High
suction
pressure/low
superheat
(com¬
pressor
may
be
flooding).
1
Check
Refrigerant
Charging
procedure,
charging
charts.
Check
AccuRater
™
for
proper
piston.
2.
Check
indoor
air
system
for
obstructions
—
dirty
filters,
ductwork
debris,
improper
fan
speed.
Expansion
valve
or
AccuRater
improperly
sized.
3.
Check
Carrier
Compressor
Service
Manual
for
compressor
repair
procedures.
See
Compressor
Removal.
Check
reversing
valve
solenoid
opera¬
tion
and
valve
seats.
4.
Check
refrigerant
flow
device
Check
that
maxi¬
mum
elevation
between
indoor
and
outdoor
units
is
not
too
great
Check
refrigerant
charge
COMPRESSOR
CYCLES
ON
AND
OFF
1.
Internal
overloads
are
opening
or
refrigerant
system
is
dirty.
High
or
low
pressure
switch
is
opening.
2.
Faulty
timer
or
defrost
control
operation.
Run
capacitor
faulty.
3.
Fan
motors
operate
intermittently.
4.
Reversing
valve
in
mid-position.
1.
Check
refrigerant
system
for
noncondensables,
or
improper
charge.
See
Refrigerant
Charging.
Check
for
airflow
obstructions
See
Coil
Cleaning.
2.
Check
timer
or
defrost
control
relays
and
con¬
tacts.
Replace
fun
capacitor.
3.
Check
motor
leads
and
overloads.
4.
Check
reversing
valve
solenoid.
See
label
diagram.
Check
that
dirt
in
refrigerant
system
does
not
cause
valve
to
"hang
up."
17
TROUBLESHOOTING
GUIDE
—
HEATING
SYMPTOM
AND
PROBABLE
CAUSE
NO
HEATING
(Compressor
Will
Not
Run)
1.
Main
power
circuit
open
due
to
faulty
power
supply.
2.
Control
power
circuit
open
or
faulty.
3.
Defrost
control
malfunctioning.
4.
Signal-Loc
™
malfunction.
INSUFFICIENT
HEATING
(Compressor
Runs
or
Cycles)
1.
L
ow
suction
and
low
head
pressure
due
to
coil
obstruction
in
airflow
or
refrigerant
circuit.
2.
H
i
gh
suction,
low
superheat.
3.
Frozen
outdoor
coil.
4.
Accessory
electric
resistance
heaters
not
operating.
5.
High
suction,
low
head
pressures
(caused
by
refrigerant
system
or
indoor
fan
problem).
6.
Low
suction,
high
head
pressures
(may
be
accompanied
by
low
airflow
at
air
outlets).
7.
Compressor
no.
2
falls
to
start
due
to
failure
of
outdoor
thermostat.
Check
power
supply,
main
power
wire
connec¬
tions,
fuses.
See
Electrical
Data.
Check
low
voltage
transformer,
remote
control
center,
control
relay
and
contacts,
timer
relay
and
motor,
compressor
overloads
and
pressurestats
for
faulty
operation.
Review
component
headings
in
Service
section.
Check
unit
label
diagram(s).
3.
Check
Defrost
control
procedure
to
be
sure
defrost
thermostat
and
relay
are
operational.
4.
Check
wire
connections.
Check
continuity
thru
terminals
2
and
3
Check
to
see
if
power
wire
has
been
routed
thru
current
loop.
1
Check
coil
for
obstruction
(dirt,
debris).
Check
that
outdoor
air
fan
is
correctly
positioned
and
turns
freely.
Review
fan
clearance
requirements
and
coil
cleaning
procedure.
Check
liquid
line
drier,
AccuRater.
2.
Check
refrigerant
flow
device
Check
refrigerant
charge.
3.
Check
fan
operation,
coil
cleanliness.
Check
defrost
control
circuit.
Check
refrigerant
charge
(use
Charging
Charts
and/or
Operational
Check
Charts).
4.
Check
heater
power
supply,
outdoor
thermostats
and
their
settings
Check
that
heater
elements
are
not
broken.
5.
Reversing
valve
may
be
leaking
or
"hung-up
"
Check
valve
and
its
solenoid
for
correct
operation
Replace
if
suspect
Indoor
fan
motor
capacitor
may
be
defective
Replace
capacitor
Fan
may
be
cycling
on
over¬
loads.
Check
overloads,
loose
terminal
connec¬
tions
Fan
motor
may
be
burned
out.
Check
and
replace
or
lubricate
See
Fan
Adjustment.
Replace
or
repair
motor
or
fan
as
necessary.
6.
Check
for
restricted
refrigerant
system
com¬
ponent.
Check
Heating
Operational
Check
charts
to
detect
even
charge.
Check
system
for
non¬
condensables.
Refer
to
Standard
Service
Tech¬
niques
Manual,
Chapter
1,
Refrigerants.
7
Check
outdoor
ambient
switch.
Switch
should
be
closed
when
ambient
is
below
switch
set
point.
PROBABLE
REMEDY
1
.
2
.
18
For
replacement
items
use
Carrier
Specified
Parts.
Manufacturer
reserves
the
right
to
discontinue,
or
change
at
any
time,
specifications
or
designs
without
notice
and
without
incurring
obligations.
Book
1
4
Tab
5a
5a
Form
38HQ-6SI
New
Printed
in
U
S
A
8-79
PC
101
Catalog
No
533-892

This manual suits for next models

2

Other Carrier Heat Pump manuals

Carrier COMFORT SERIES 25HCB3 User manual

Carrier

Carrier COMFORT SERIES 25HCB3 User manual

Carrier 38QB Dimensional drawing

Carrier

Carrier 38QB Dimensional drawing

Carrier Infinity 48CE030 Instruction Manual

Carrier

Carrier Infinity 48CE030 Instruction Manual

Carrier 48VR Instruction Manual

Carrier

Carrier 48VR Instruction Manual

Carrier XCT 7 40VD072H-7S-QEE Installation instructions

Carrier

Carrier XCT 7 40VD072H-7S-QEE Installation instructions

Carrier 38QW User manual

Carrier

Carrier 38QW User manual

Carrier 38BYW Instructions and recipes

Carrier

Carrier 38BYW Instructions and recipes

Carrier 38EYA Operation manual

Carrier

Carrier 38EYA Operation manual

Carrier Aquasnap 30RQ Manual

Carrier

Carrier Aquasnap 30RQ Manual

Carrier Gemini 38AU07 Series User manual

Carrier

Carrier Gemini 38AU07 Series User manual

Carrier COMFORT 50EZ-A Instruction Manual

Carrier

Carrier COMFORT 50EZ-A Instruction Manual

Carrier OMNIZONE 50BV020-064 Quick guide

Carrier

Carrier OMNIZONE 50BV020-064 Quick guide

Carrier 40FKA Manual

Carrier

Carrier 40FKA Manual

Carrier 38AB Dimensions and installation guide

Carrier

Carrier 38AB Dimensions and installation guide

Carrier WeatherExpert 50LC14 User manual

Carrier

Carrier WeatherExpert 50LC14 User manual

Carrier 25VNA8 infinity 18VS User manual

Carrier

Carrier 25VNA8 infinity 18VS User manual

Carrier 50YQ Dimensions and installation guide

Carrier

Carrier 50YQ Dimensions and installation guide

Carrier 38AUQ 16 Series Dimensions and installation guide

Carrier

Carrier 38AUQ 16 Series Dimensions and installation guide

Carrier 25HNB5 User manual

Carrier

Carrier 25HNB5 User manual

Carrier 50CP Dimensions and installation guide

Carrier

Carrier 50CP Dimensions and installation guide

Carrier 50ZH Series Assembly Instructions

Carrier

Carrier 50ZH Series Assembly Instructions

Carrier DHMVHA User manual

Carrier

Carrier DHMVHA User manual

Carrier Omnizone 09XC06 Dimensions and installation guide

Carrier

Carrier Omnizone 09XC06 Dimensions and installation guide

Carrier Performance 50VR Instruction Manual

Carrier

Carrier Performance 50VR Instruction Manual

Popular Heat Pump manuals by other brands

Unitary products group HF-25 - 25 Ton installation manual

Unitary products group

Unitary products group HF-25 - 25 Ton installation manual

Glen Dimplex HPL 9S-TUW2 Installation and operating instruction

Glen Dimplex

Glen Dimplex HPL 9S-TUW2 Installation and operating instruction

evoheat Advanced DHP-R Series Installation & operation manual

evoheat

evoheat Advanced DHP-R Series Installation & operation manual

Trane Voyager PKGP-PRC001-EN user manual

Trane

Trane Voyager PKGP-PRC001-EN user manual

Lennox XP16 Unit information

Lennox

Lennox XP16 Unit information

CLIVET WBAN Series Installation, use & maintenance manual

CLIVET

CLIVET WBAN Series Installation, use & maintenance manual

ClimateMaster TYH/V 024 - 060 60Hz - HFC-410A Installation, operation, &  maintenance instruction

ClimateMaster

ClimateMaster TYH/V 024 - 060 60Hz - HFC-410A Installation, operation, & maintenance instruction

Pentair XLHP Installation and user guide

Pentair

Pentair XLHP Installation and user guide

Bryant LEGACY 607C C Series Owner's information manual

Bryant

Bryant LEGACY 607C C Series Owner's information manual

Danfoss OPTYMA Plus OP-LPQM instructions

Danfoss

Danfoss OPTYMA Plus OP-LPQM instructions

W'eau WMIP-003 Installation & operation manual

W'eau

W'eau WMIP-003 Installation & operation manual

York E*FH018 installation instructions

York

York E*FH018 installation instructions

AERMEC ANK030 H Technical manual

AERMEC

AERMEC ANK030 H Technical manual

Ecodan PUHZ-W50VHA-BS User instructions

Ecodan

Ecodan PUHZ-W50VHA-BS User instructions

McQuay MHC Standard Range Installation & maintenance data

McQuay

McQuay MHC Standard Range Installation & maintenance data

elco AEROTOP T user manual

elco

elco AEROTOP T user manual

Nibe S1156 Installer manual

Nibe

Nibe S1156 Installer manual

Dimplex WI 120TU Installation and operating instruction

Dimplex

Dimplex WI 120TU Installation and operating instruction

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.