START-UP
Preliminary Checks
1. Check that all internal wiring connections are tight and
that all barriers, covers, and panels are in place.
2. Field electrical power source must agree with unit name-
plate rating.
3. All ._-_rvicevalves must be open.
4. Crankcase heater must be tight on compressor crankcase
(if equipped).
Leak Test -- Field piping and fan coil must be leak tested
by pressure method. Use R-410A at approximately 25 psig
backed up with an inert gas to a total pressure not to exceed
245 psig.
NOTE: Leak detectors should be designed to detect HFC
(hydrofluorocarbon) refrigeranL
Evacuate and Dehydrate -- Field piping and fan coil
must be evacuated and dehydrated following good refrigera-
tion practices.
Start Unit with Operating Test -- Turn power on to
the unit. Insert bar,ties in remote control. Press the A and
the %_ buttons on the remote conlrol for 5seconds. The
remote control will be cleared and the time segment will dis-
play the Src 1=service test mode.
Press the _ button to transmit the service test signal to the
mail After the test has completed press the (_) button to leave
the test menu.
NOTE: When 30 seconds have elapsed and no buttons have
been pressed, the remote conlxol will automatically exit the test
menu and resume its normal operation.
Configuring Two Indoor Unit Remote Con-
trois -- If two indoor units are being installed in the same
room, working independently, two remote controls need to be
configured for proper operation.
UNIT CONFIGURATION -- Turn the unit off by pressing
the (_. Press and hold the M and _'_. buttons of the re-
mote control for more than 5 seconds. The display will be
cleared and the time segments will display the first configura-
tion item (rAdr=remote address) and the temperature segments
will display the default value of this configuration item
(Ab=control of both indoor units). Press A and Vto
change the default value to the new value of (a) or (b). Press the
=-._ button to transmit the new configuration to the unit. Press
the (D button to leave the configuration menu.
REMOTE CONTROL CONFIGURATION -- Turn the unit
off by pressing the (_) button. Press and hold the V and
_ buttons for more than 5 seconds. The display will be
cleared and the time segments will display the first configura-
tion item (CH--remote address) and the temperature segments
will display the default value of this configuration item
(Ab=control of both indoor units). Press Aand V to
change the default value to the new value of (a) or (b). Press the
_ button to transmit the new configuration to the unit.
Press the (D button to leave the configuration menu.
NOTE: When 30 seconds have elapsed and no buttons have
been pressed, the remote control will automatically exit the test
menu and resume its normal operation.
SERVICE
Before performing recommended maintenance, be sure
unit main power switch is turned off. Failure to do so may
result in electrical shock or injury form rotating fan blade.
Pumpdown Procedure -- The system may be pumped
down in order to make repairs on the low side without losing
complete refrigerant charge.
1. Attach pressure gage to suction service valve gage port.
2. Frontseat the mixed phase line valve.
The unit coils hold only the factory-designated amount of
refrigerant. Additional refrigerant may cause units to
relieve pressure through the compressor internal pressure
relief valve (indicated by a sudden rise of suction pressure)
before suction pressure reaches 20 psig. If this occurs, shut
off unit immediately then frontseat the suction valve and
remove and recover excess refrigerant following accepted
practices. Equipment damage may result.
3. Start unit and run until suction pressure reaches 5 psig.
4. Shnt unit off and frontseat suction valve.
5. Depressurize low side of unit and recover refrigerant
following accepted practices.
Filter Drier (Field Supplied) --Whenever the filter
drier is exposed to the atmosphere it must be replaced. Only use
factory specified liquid-line filter driers with rated working pres-
sures less than 600 psig.
NOTE: Do not install a suction-line filter drier in the mixed
phase line.
Refrigerant Charging
To prevent personal injury, wear safety glasses and gloves
when handling refrigerant. Do not overcharge system --
this can cause compressor flooding.
All units are shipped with the refrigerant charge listed on
nameplate.
NOTE: Do not vent or depressurize unit refrigerant to atmo-
sphere. Remove and recover refrigerant following accepted
practices.
13