Page 4
Advanced Setup Table
*Not applicable for use with Duct-Free Split Heat Pump systems.
• CLOCK BACKUP — In the event of a power loss,
the thermostat internal clock will continue to keep
proper time for a minimum of 48hours without
external power or batteries.
• MINIMUM HEAT/COOL SETPOINT DIFFERENCE
— The Heat and Cool set points will not be allowed
to come any closer to each other than the value set
in Advanced Setup
Step 6, on this page
. This mini-
mum difference is enforced during Auto changeover
and Program On operation.
• ENERGY SAVING SMART FAN — If a manual fan
speed is selected, the fan will run continuously at all
times. If mode is Off, the fan will only run if there is a
heating or cooling demand in Unoccupied periods.
• OVERRIDE — As explained on
page 2
,pressing
the Override button during a programmed, Unoccu-
pied period will force the thermostat into Occupied
1, temporarily, for up to 4 hours. If the Override but-
tonispressedduringanOccupiedperiod,thether-
mostat will be forced into Unoccupied and the
occupied period
(1,2 or 3)
,itwasforcedoutofwill
be turned off, only for that day.
During Override periods the set points may be
adjusted, but they will not be remembered after
Override ends.
• KEYPAD LOCK — To prevent unauthorized use of
the thermostat, the front panel buttons may be dis-
abled. To disable or ‘lock’ the keypad, press and
hold the Mode button. While holding the Mode but-
ton, simultaneously press the Up and Down but-
tons. The Locked icon will appear on the display.
To
unlock
the buttons, again press and hold the
Mode button. While holding the Mode button, simul-
taneously press the Up and Down buttons. Locked
will disappear from the display.
• DISPLAY BLANKING — The thermostat display
may be configured in advanced setup, this page,
Step 3, to always be visible as normally expected,
or may be selected Off. When selected Off, only the
time of day will appear until a button is pressed.
When a button is pressed the full, normal display
will appear and then revert to the time of day only,
after roughly 10 seconds.
Advanced Setup
STEP NO. DESCRIPTION RANGE FACTORY
DEFAULT
1 Time of day clock set 24 hour 12:00 Am
2 Day of the week Su - Sa Mo
3 Display Blanking Off /On On
4 Fan Operation Auto /On Auto
5 Heat Pump*Off /On On
6Deadband or Temperature swing 1 - 6F2F
7Forced minimum difference
heat/cool 0-6F2F
8Cycles per hour d, d1, 2 - 66
9Thermoglow™ backlight Off /On On
10 Fahrenheit or Celsius F /CF
About Advanced Features and Operation
Pm
Setup
Setup
Setup
Su
ON
Setup
:
Setup
Setup
Setup
OFF
Setup
Setup
ON
Setup
IMPORTANT: Be sure to press and hold the override button
with the Mode button for full ten seconds.
NOTE: Step 5 is not applicable for use with Duct-Free Split Heat Pump
Systems.
ress the Mode button. WhileholdingtheMode,presstheOverridebuttonto
eave the Setup screens. If no buttons are pressed, the display will leave the
etup screens after 60 seconds.
Pm
Mo
Locked
unoccupied
:
Cool
Heat
ProgramOn
o