Quick Start Guide
S-Series | S32, S41 & 11R
1. Wire Your Machine Control Unit
The MCU terminaland pin numberingof each relative to the OCU
buttons are identifiedin the system configurationdrawing provided
with your system.
1. The implementationof an appropriatemain line contactorpower
circuitis required using K18 and K19 to maintainthe machine
power and possibly K16 to reset the machine–can also be done
via local reset.
2. Connect power and ground (per system specification)to J1 via a
local disconnect switch.
3. If using an external antenna, make sure to turn the adjacent dip
switch on.
4. Check the wiring and turn on the MCU power. The MCU status
LEDs two power green, Heartbeat flashing red and status amber
will energize if all is OK , the relays K18 and K19 will energize
when the OCU is linked.
2. Install the Batteries
Rechargeable OCUs have tamperproof
screws on the battery cover. Disposable
battery (AA type) OCUs have cross head
screws on the battery cover.
3. Turn On the OCU
1. Press the ON button. The
OCU will wake from sleep to
a fully tested PASSIVE non-
transmittingmode.
2. You will see all LEDs flash
briefly.
3. The center status and right-
hand LEDs 1 and 2 will then
be illuminated.
ON
2nd
1st
4. Move to Active Mode
NB: S-Series OCUs must have completed the Association process with its target
MCU (this only needs to be done once, see next page)
From Passive Mode, the OCU can be moved into Active mode.
1. Press the stop switch and then press the on switch within 3 seconds.
2. The status E-stop LED will now flash showing it is transmitting.
3. The OCU is now operative, and the target machinewill be under direct control.
4. To shut the system down Press the Stop Switch.
5. If the OCU is left in Passive mode, it will power down after 3 minutes.
Nimble: 9M60-9061-A003-EN| May 2022
If using an external
antenna, connect here
and turn ON the adjacent
DIP switch
K18
K19 RF
Module
K16 FUSE