
10
Wiring Instructions:
WARNING: Alarm and relay module wiring installation must comply with the current
edition of AS3000, Wiring Regulations and all appropriate prevailing local/national building
regulations and codes of practice.
Product must be installed by a qualified electrician. Failure to install this product correctly
may expose the user to electric shock or fire risk hazards. This relay module is not rated as
waterproof and must not be exposed to dripping or splashing water. The relay module must
be installed correctly to function. The electrical circuit used to power the relay module must
be 240 volt AC 50Hz.
WARNING: This product cannot be operated from power derived from a square wave,
modified square wave or modified sine wave inverter. These type of inverters are sometimes
used to supply power to the structure in ‘off grid’ installations, such as solar or wind derived
power sources. These power sources produce high peak voltages that can damage the
device.
IMPORTANT: It is recommended that the module and alarms are connected to a
dedicated circuit that is separately electrically protected. This helps minimise interference
(EMI) on alarm interconnect line from CFL’s, dimmers, LV transformers etc.
Make sure that AC power is turned off before starting the installation.
This 9005 CAVRI Relay Interface will not detect smoke or heat. This wireless module can only
interconnect with compatible smoke alarms or relay. Interconnection with other brands may
cause damage, result in electric shock, fire risk and void warranty.
The earth terminal connection provided is for termination purposes only and is NOT
electrically connected within the sealed alarm / base units.