CHANNEL SAFETY SYSTEMS t: 0845 884 7000 | w: www.channelsafety.co.uk
INSTRUCTION MANUAL - Issue 1 - 02/2014 | 2
INSTALLATION
OPERATION
All Installations should be carried out by a competent electrician.
1. Remove the diuser.
2. Release gear tray –GENTLY pull on plastic clips and remove gear tray.
3. Fix base to wall or ceiling using appropriate xing method.
4. ISOLATE THE A.C. SUPPLY and connect unit. An unswitched 240 V A.C. supply must be connected to the Live (Lch), Earth and Neutral (N) terminals for
the emergency Non-Maintained circuit. For Maintained operation continuous illumination is achieved by adding a link between Lch & Lsw terminals. To
enable Maintained or Sustained Circuits to be switched, add a switch between Lch and Lsw or use a remote Switched supply directly into Lsw
5. Fit white battery plug onto the two protruding metal pins on edge of PCB. Then, replace and secure gear tray.
6. Ret diuser.
7. Operational Check - Restore the A.C. supply for 30 minutes and then isolate. The LED’s should illuminate for at least 10 seconds.
8. Restore the A.C. supply and check that the charge indicator LED is‘on’.
Non-Maintained
LED’s normally o and battery on automatic charge (Charge LED ‘on’) when A.C. supply is healthy. Solid state circuitry automatically switches LED’s on when
A.C. supply is interrupted.
Maintained
Emergency LED’s normally on, when the supply to Lsw is switched on. The battery is on automatic charge (Charge LED‘on’). LED’s will switch on or remain on
if A.C. supply is interrupted.
Night Light Function
A simple link is used to select between “Full brightness”or
“Night light 10%” for the Maintained function. This does not
aect the emergency output.
Monitoring
Green indicator LED (Charge LED) normally continuously ‘on’.
Indicator LED goes out if A.C. supply or charger fails.
Battery
Sealed Nickel - Cadmium rechargeable battery pack.
Temperature
Performance gures measured at 25C.
Fault Finding And Corrective Action
Monitoring Led Not Illuminated
A.C. supply not healthy. Battery not connected. Charger failed.
Unit Not Meeting Required Emergency Period
May need cycling: Discharge then recharge for 24 hours. Re-test, battery pack may need replacing if emergency duration still not met.
Ls
E
b
a
L
Nightlight function Full brightness
Jumper settings