USHIBAYRxxxWPL (300W-480W) Series LED Highbays Installation Guide
MICROWAVE OCCUPANCY DETECTION
INSTALLATION STEPS
PART NO. IMAGE DESCRIPTION QTY
ACHUMO Microwave occupancy sensor with
J-Box
1
ACHUMO-MB4 Mounting Bracket for the ACHUMO
occupancy sensor
1
10-00032 #4-40 Pan Head Machine Screw 2
10-00033 #4-40 Hex Nut 2
2) Refer to the wiring diagram provided to
connect the ACHUMO to the Dimmable LED
Driver. Try to aim the sensor toward the
desired detectable area.
3) Make sure all wiring connections are
made inside the J-Box provided and are
properly sealed by an authorized electrician.
4) Remove the screw and cap of the sensor
and adjust the DIP switches to get the
desired settings. Sensor data can be
precisely set for each specific application.
Once the program is set, close and fasten
the cap.
(1) DETECTION AREA
Detection area can be reduced by selecting
the combination on the DIP switches to fit
precisely each application
(2-4) HOLD TIME
Refer to the time period the lamp remains at
100% illumination after
no motion detected
(8-9) STAND-BY DIMMING LEVEL
The low light level you would
like to have after the hold
time in the long absence of people
(5-7) STAND-BY PERIOD
Refer to the time period the lamp
remains at 100% illumination after
no motion detected
(10-12) DAYLIGHT SENSOR
The sensor can be set to only allow
the lamp to illuminate below a defined
ambient brightness threshold.
When set to Disable mode, the daylight
sensor will switch on the lamp when motion is
detected regardless of ambient light level.
Note that daylight sensor
is active only when lamp totally switches off.
ONON
ONON
ONON
11
223344
8899
II
IIII
II
IIII
IIIIII
IVIV
VV
VIVI
II
IIII
IIIIII
IVIV
ONON
--
100%100%
50%50%
ONON ONON ONON
ONON ONON
ONON
ONON
ONON ONON
--
--
ONON
--
--
--
--
----
5 s5 s
30 s30 s
90 s90 s
3min3min
20min20min
30min30min
ONON ONON
ONON
--
ONON
--
50%50%
30%30%
-- 20%20%
-- 10%10%
ON
ON
56 7
10 11 12
I
II
III
IV
V
VI
I
II
III
IV
ON ON ON
ON ON
ON
ON
ON ON
-
-
ON
-
-
-
-
--5 s
10min
5 min
30min
60min
60m+
ON ON ON
ON
ON
--
-
-
---
Disable
20 lux
10 lux
5 lux
1) Remove the two [2] #4-40 PHMS from
the mounting bracket. Using a Phillips
screw driver, fasten the bracket onto the
luminaire and use the hexnuts provided to
lock it in place.
CAUTION: PLEASE FOLLOW THIS
INSTRUCTION MANUAL CAREFULLY
TO PREVENT ANY INJURIES OR
COMPLICATIONS THAT MAY ARISE.
WARNING: Before installing or
maintaining
the luminary, make sure all powers are
TURNED OFF.
Verify that supply voltage is correct by
comparing it with the label information
on all fixtures. Make all connections in
accordance with the NEC requirements,
and make sure all luminaries are
properly secured to prevent any wire
complications.
DIMMING
INPUT
WHITE (-)
/BLACK (-)
BLUE(+)
/GRAY(+)
ACL (BROWN)
ACN (BLUE)
AC POWER SUPPLY
DIMMABLE LED DRIVER
G N L
DIM (+) [RED]
DIM (-) [BLACK]
L out[YELLOW]
LUE]
L in [BRON [BWN]
WIRING DIAGRAM