Chino AL4000 series User manual

INST.No. INE-844E
AL4000 (Multi-point type)
Hybrid Memory Recorder
[ General ]

1. Introduction....................................................................................................................1
2. For Safe Use...................................................................................................................4
2-1. Preconditions for Use.........................................................................................................................................4
2-2. Symbol Mark.......................................................................................................................................................4
2-3. Label...................................................................................................................................................................4
2-4. Important Explanation.........................................................................................................................................5
3. Model Code List.............................................................................................................6
4. Mounting and Wiring.....................................................................................................7
4-1. External Dimensions...........................................................................................................................................7
4-2. Mounting.............................................................................................................................................................7
4-3. Wiring.................................................................................................................................................................9
5. Part Names...................................................................................................................26
5-1. Front Section of Internal Unit............................................................................................................................26
5-2. Operation/Set Keys ..........................................................................................................................................27
6. Operation......................................................................................................................28
6-1. Preparation for Operation.................................................................................................................................28
6-2. Basic Operation................................................................................................................................................30
6-3. Operation..........................................................................................................................................................33
7. Factory Default Settings..............................................................................................37
7-1. List of Factory Default Settings.........................................................................................................................37
8. Setting Method.............................................................................................................38
8-1. Basic Rules.......................................................................................................................................................38
8-2. Input Type Settings “Range”.............................................................................................................................40
8-3. Alarm Settings “Alarm” .....................................................................................................................................43
8-4. Calculation Settings “Calc” ...............................................................................................................................50
8-5. Formula Settings “Formula”..............................................................................................................................54
8-6. Broken Line Approximation Table Settings “Seg.Tbl”........................................................................................61
8-7. Chart Speed Settings “Chart” ...........................................................................................................................62
8-8. Dot Printing Settings “Dot”................................................................................................................................63
8-9. Subtract Printing Settings “Sub Prt”..................................................................................................................64
8-10. Dot Printing Interval Settings “Dot.Int” ..............................................................................................................66
8-11. Periodic (Data Interval) Data Printing Settings “DataInt”...................................................................................67
8-12. Periodic (Specified Time) Data Printing Settings “PrtTime”...............................................................................68
8-13. List Printing Settings “ListPrt” ...........................................................................................................................69
8-14. Message Printing 1 Settings “MsgPrt1” ............................................................................................................70
8-15. Message Printing 2 Settings “MsgPrt2” ............................................................................................................71
8-16. Recording Format Settings “PrtForm”...............................................................................................................72
8-17. Auto Range Settings “A.Range” .......................................................................................................................73
8-18. Compressed/Expanded Printing Settings “Cmp&Exp”......................................................................................75
8-19. Zone Printing Settings “ZonePrt” ......................................................................................................................77
8-20. SD Card “SD CARD” ........................................................................................................................................79
8-21. USB Engineering Port Settings “USB”..............................................................................................................85
8-22. Calendar Timer Settings “Timer”.......................................................................................................................86
8-23. Fail Output Settings “FailOut” ...........................................................................................................................87
8-24. Display Settings “Display”.................................................................................................................................89
8-25. Measured Value Display Order Settings “D.Order”...........................................................................................90
8-26. Date and Time Settings “Date” .........................................................................................................................91
8-27. System Settings “System” ................................................................................................................................92
8-28. System Information Display “SysInfo”...............................................................................................................93
Table of contents

9. Adjustment...................................................................................................................94
9-1. Trace Printing (Dot Printing) Position Adjustment “Rec Adj” .............................................................................94
9-2. Input Adjustment “Inp Adj” ................................................................................................................................95
9-3. Input Shift Adjustment.......................................................................................................................................96
9-4. Wiring and Environment for Input Adjustment...................................................................................................97
10. Engineering Port (Mini-USB Terminal).....................................................................98
11. Troubleshooting.........................................................................................................99
11-1. Problems and Remedies ..................................................................................................................................99
11-2. Abnormal Measured Value .............................................................................................................................100
12. Inspection and Maintenance...................................................................................101
12-1. Routine Inspection..........................................................................................................................................101
12-2. Consumable Parts and Replacement Guideline.............................................................................................101
12-3. Disposal..........................................................................................................................................................102
13. Option.......................................................................................................................104
13-1. External Operation Settings “Dig Inp” .............................................................................................................104
13-2. Operation Recording Settings “Ope.Rec” .......................................................................................................107
13-3. COM Port Settings “COM1” and “COM2” .......................................................................................................108
13-4. IP Address etc… Settings “Ether” ...................................................................................................................109
13-5. SNTP Settings “SNTP” ................................................................................................................................... 110
13-6. E-mail Settings “E-mail”...................................................................................................................................111
14. Specifications...........................................................................................................114

- 1 -
1. Introduction
Thank you for purchasing AL4000 series (Multi-point Type) with 100mm recording width.
This industrial use instrument records input signals to the chart paper and stores data into the SD card.
Mount this instrument on the indoor instrumentation panel etc. and record signals of temperature sensor, pressure gauge,
hygrometer and flow meter. Reading signals of the recorder are thermocouple, resistance thermometer, DCmV and DCV.
Make sure to read this instruction manual in advance to understand this unit well and prevent troubles from occurring. This
manual is a “General” Instruction manual. For specifications with communications, read the “Communications” instruction
manual separately.
- To the persons doing instrumentation, installation, and sales -
Make sure to provide this instruction manual to the person who uses the unit.
- To the users of this unit -
Store this instruction manual with care until you scrap the unit.
Also, write down the parameter contents set in the product and keep it for your record.
Perchlorate Material
This instrument uses battery with Perchlorate Material.
Special handling may apply, see
http://www. dtsc.ca.gov/hazardouswaste/perchiorate
Warning
Request
1. Microsoft, Windows, Windows XP, Windows Vista, Windows 7, and NET Framework are trademarks of Microsoft
Corporation and the related company.
2. SD Memory Card is the trademark of Panasonic Corporation, SanDisk Corporation in USA, and TOSHIBA
CORPORATION.
3. Other described company names and product names are trademarks and registered products of the respective
companies.
4. Please note that the marks “TM”and “®”are omitted throughout this manual.
Trademark
1. No part of this manual can be reproduced or copied in any form without permission.
2. The contents of this manual may be altered without prior notice.
3. This manual has been documented by making assurance doubly sure. However, if any question arises or if any
error, an omission, or other deficiencies are found, please contact your nearest our sales office.
4. CHINO is not responsible for any operation results of this software.
Notice
This product is warranted for one year from the date of delivery. If it is damaged during the warranty period, when
used normally based on the cautions in the instruction manual labels attached to the product, etc., it will be repaired
without any charge (only in Japan). In the case, we are sorry to trouble you, but please contact your dealer or
nearest our sales office.
However, in cases of the followings, it will be repaired at your expense even during warranty period.
1. Failure or damage caused by improper use or connection, or invalid repair or modification.
2. Failure or damage caused by fire, earthquake, wind or flood, thunderbolt, or other extraordinary natural
phenomena, or pollution, salt, harmful gas, abnormal voltage, or use of unspecified power.
3. Replacement of parts or accessories that have reached the end of their life.
Furthermore, the term ‘warranty’in this sense covers only a CHINO’s product itself. Therefore, we are not
responsible for compensation for whatever the damage that is triggered by failure of our product.
Product warranty scope

- 2 -
Before use
Make sure to check the following before use after unpacking the unit. If you have any question, please contact your dealer
or our nearest office.
1. Exterior check
Check that the appearance of the product has no damage.
2. Model code check
Check that the model code of the purchased product is correct.
Model code label and application place
The label as follows is attached on the upper surface of the product case and the chassis.
A L 4 7 -- ←Model code
R 3 ←Serial number
M A D E I N J A P A N
3. Accessories check
Check the following accessories attached to the product.
Item
Q'ty
Remarks
Instruction manual
1
CD-R
Instruction manual [Wiring/Installation]
1
Booklet
Bracket
2 (1 set)
For panel mounting, 22025-029001
Terminal screw
5
M3.5, for input terminal (spares for missing)
Chart paper
1
The type depends on the specifications.
Ribbon cassette
1
84-0044
In addition, if accessories are purchased additionally, those products may be attached.
1. Do not drop the product while take it out of the box
2. When transporting the unit, pack in the dedicated package box, and put the box in an outer case with a bed of
cushion.
With the consideration to the case above, it is recommended that the dedicated package box for the unit is
stored.
3. When the unit is removed from the panel and not used for a long time, put it in the dedicated package box, and
store it in a place with normal ambient temperature and less dust.
Request

- 3 -
4. About attached chart paper
For the unit, the chart paper No.EM001 (50 equal divisions) is available and delivered. For the case that the chart
paper is to be specified, various scales are available as follows.
Chart Paper for Standard Scale
Standard scale (linear)
Chart paper No.
Standard scale (linear)
Chart paper No.
0 to 50C
0 to 100C
0 to 150C
0 to 200C
0 to 250C
0 to 300C
0 to 400C
0 to 500C
0 to 600C
0 to 800C
0 to 1000C
0 to 1200C
0 to 1400C
0 to 1600C
EL05014
EL05052
EL05034
EL05047
EL05096
EL05124
EL05009
EL05048
EL05168
EL05121
EL05157
EL05116
EL05137
EL05147
-20 to 80C
-50 to 50C
-50 to 150C
0 to 10mV
0 to 20mV
0 to 50mV
-5 to 5mV
-10 to 10mV
1 to 5V
Double to triple scale
Nonstandard scale
EL05035
EL05006
EL05019
EM001*
(Scale with 50-equal
divisions)
* Scale marks
without numeric
values and unit
* The chart paper has the same printed linear scale as the standard scale.
Therefore, it can be shared in regardless of input types (thermocouple, resistance thermometer, or others).
5. Restriction of digital recording/printing function
(1) Data printing requires approximately two minutes. Note that when data printing is executed, the trace printing
stops until the printing is finished.
(2) When the chart speed is set to 251mm/H or more, power-on printing, data printing, list printing, and printing
function for other than time line are disabled.
(3) The trace printing executes dot printing with five seconds interval (standard); however, if time printing is
executed during the trace printing, the dot interval may become longer. The dot interval is extended with the
inserted printing. Therefore, this is not abnormal.
(4) Printing is formed with dots of one pin. Therefore, if the power is turned off while characters are being formed,
they cannot be formed correctly. This is not abnormal.

- 4 -
2. For Safe Use
If the unit is used in a manner not specified by manufacturer, the protection provided by the unit may be impaired.
For safe use of the unit, please read and understand the following cautions.
2-1. Preconditions for Use
The unit is a component type general product to be used mounted on an indoor instrumentation panel. Avoid using under
other conditions.
Use after the system safety is implemented such as the fail-safe design and periodical inspection on the final product side.
Also, for wiring/adjustment/operation of the unit, ask professionals with instrumentation knowledge to perform.
Furthermore, also the person who actually uses the unit is required to read this instruction manual to fully understand
various cautions and basic operation.
2-2. Symbol Mark
This instruction manual includes the following symbol marks. Make sure to fully understand the meaning of them.
Symbol mark
Meaning
Cautions are explained to avoid causes for death or serious injuries of users.
Cautions are explained to avoid causes for slight injuries of users or damages of the unit
or peripheral devices.
2-3. Label
For safe use of the unit, the following labels are used.
Label
”Name” and place
Meaning
“Alert symbol mark”
Various terminals
(back side)
Place to be handled with cautions to avoid “electric
shock”, “injuries”, etc.
“Protective conductor
terminal”
Right side of power terminal
(back side)
Terminal to be grounded to avoid electric shock
100 to 240V AC
50/60Hz, 40VA
“Power source specification”
Power conductor terminals
Specification of power (voltage range, frequency,
and power consumption) used for the unit
!
!
Warning
!
Caution

- 5 -
2-4. Important Explanation
To avoid severe accidents, make sure to read and understand the following.
1. Switch and overcurrent protection device
This unit is not provided with a replaceable overcurrent
protective device. Prepare a switch and an overcurrent
protective device for the power supply (circuit breakers,
circuit protectors or the like) within 3m of this unit in a
location where the operator can access easily. Use a switch
and an overcurrent protective device conforming to
IEC60947-1 and IEC60947-3.
2. Be sure to ground this instrument
To avoid electric shock, before turning the power on,
connect the protective conductor terminal of this recorder to
the protective conductor of the power supply equipment,
and do not remove it during use.
3. Before turning on the power supply
For safety, first check that the power source is within the
range indicated on the power label, and then turn on the
external power switch.
4. Avoid repair and modification
Avoid repair and modification with parts replacement by
persons other than service personnel authorized by CHINO.
Not only damage or malfunction of this recorder may occur,
but also dangers such as electric shock may occur. In
addition, the inner unit does not have to be pulled out in the
normal use.
5. Use the unit following the instruction
manual
For safe use, use the unit following the instruction manual.
Please note that CHINO does not have any responsibilities
for any claims for failures or damages occurred with abuse
or misuse of this recorder.
6. Installing the safety device
Regarding the use of a device that anticipates a big loss due to failure of the controller and the peripheral device,
always install a safety device for preventing these losses and implement fail safe design in the final product.
Do not use it in important in facilities like, human life,atomic energy, aviation and space.
7. Turn off the power supply if abnormality occurs
Turn off the power supply immediately and contact your local CHINO’s sales office if any abnormal odor, noise or
any smoke occurs, or if this unit becomes high temperature that is too hot to be touched.
8. Do not put hands in this product
Do not put your hands or tools inside of this product. It may cause electric shock or injuries.
There is no operation such as pulling out an inner unit or using tools when using this product.
Overcurrent
protection
device
Switch
!
Warning
Power terminal
Protective
conductor
terminal
Power label
100 to 240VAC
50/60Hz 40VA
MAX
To the protective
conductor of
power supply
facility
Power/protective
conductor
terminal
Power source
For safety, the fuse below is included in the
power unit of the unit. It cannot be replaced.
Manufacturer:Daito Communication
Apparatus Co.,Ltd
Model: SBL32
Fuse in power unit
Reference

- 6 -
3. Model Code List
AL47□□-□□□-□□□
Input point
06: 6 points
Communications
N: None
E: Ethernet
R: RS232C
A: RS422A/RS485
Q: RS232C + RS485
C: RS422A/RS485 + RS485
G: Ethernet + RS422A/RS485 + RS485
F: Ethernet + RS422A/RS485 + RS485 + Low-order communications
Alarm output + remote contacts
0: None
2: 2 mechanical relay 'a' contact alarm outputs
4: 4 mechanical relay 'c' contact alarm outputs + 5 remote contacts
A: 6 mechanical relay 'a' contact alarm outputs + 5 remote contacts
Power
A: 100 to 240V AC
For OP/SP
NNN: None
NNP: SD card playback

- 7 -
4. Mounting and Wiring
4-1. External Dimensions
Following dimensions are measured while the brackets are attached to the unit.
Unit: mm
4-2. Mounting
(1) Use the recorder mounting on an indoor installed instrumentation panel.
(2) Brackets can be attached to a panel of steel with thickness of 2 to 6mm or
equivalent strength.
Select thickness of a panel considering weight and depth of the unit with panel
formation for actual use.
(3) For mounting the recorder on the panel, be careful of injury by dropping it.
1. Panel cutout and mounting method
Unit: mm
138
+1
0
+1
0
138
200
200
●Minimum interval on multiple
units mounting
!
Caution
216 When alarm output/remote contacts unit and communication unit are added

- 8 -
(1) Insert the unit into the panel cutout from the front of the panel.
(2) Fix the unit to the panel using the brackets (tightening torque: 1.0Nm). Brackets are attached to the top and
bottom surfaces.
2. Mounting condition
To avoid accidents, make sure to read and understand the following.
Industrial environment
Select a location distant from sources of electric field or magnetic field and without mechanical vibration or shock.
●Overvoltage category......II (EN standard) ● Altitude...........................2000m or less
●Pollution degree..............2
(EN standard) ●Working place ................Indoor
Normal operating condition
● Ambient temperature···0 to 50℃(20 to 65%RH,non-condensing)
● Ambient humidity·········20 to 80%RH,non-condensing(5 to 45℃)
● Power voltage ·············General specification : 100 to 240V AC ±10%
● Power frequency·········General specification : 50/60Hz ±2%
Atmosphere
●For safety, avoid a location with corrosive gas, explosive gas, flammable gas and combustible gas.
● Avoid a location with dust, smoke, or steam.
Mounting angle
● Lateral tilting················0 to 10°
● Longitudinal tilting ·······Forward tilting: 0°Backward tilting: 0 to 30°
● View angle···················-10 to +30°with the horizon as the standard
Angles other than the above affect the recording operation.
!
Caution
Slide
Indicator
View angle
About 30°
About 10°
Panel thickness
(2 to 6mm)
Brackets

- 9 -
4-3. Wiring
1. Terminal board diagram
The figure below is the diagram of the terminal board with the option [Alarm relay output (6 points ‘a’ contact) +
remote contacts and communication interface].
The figure below is the diagram of the terminal board with the option [Alarm relay output (4 points ‘c’contact) +
remote contacts (20 points) and communication interface].

- 10 -
The figure below is the diagram of the terminal board with the option [Alarm relay output (2 points ‘a’contact) and
communication interface].

- 11 -
Alert symbol mark ( ) and location
mark is attached to the location to which if human body touches, an electric shock
may be generated.
Terminal name
Location of attached mark
Power terminal
Lower left of power terminal
Measurement input terminal
Upper left of terminal cover
Mechanical relay ‘c’contact alarm terminal
Upper left of terminal cover
Mechanical relay ‘a’contact alarm terminal
Lower left of N.O terminal
!
!
!
Warning
For easy wiring, the input unit, alarm output/remote contacts unit, and communication unit are removable.
(1) Every unit can be removed when two mouting screws are removed.
(2) The recorder and each unit are connected with a connector.
Turn off the power and then remove/attach
Make sure to turn off the external power switch before units are removed/attached
to prevent damages on electric circuits.
Input terminal block and alarm terminal block are removable.
Reference
Only thermocouple input unit cannot be replaced with other instrument unit. If done so, measurement errors
are generated.
Note
Thermocouple input unit replacement
!
Warning
[Alarm output/remote contacts unit]
[Input unit]
[Communications unit]
Mounting screws
Mounting screws
Mounting screws

- 12 -
2. Precautions on wiring
Precautions on wiring are described below. Observe them to maintain safety and reliability.
1) Feed power source
For the power source for the unit, use the single-phase power source with stable voltage and without
waveform strain to prevent malfunctions.
(1) Switch and overcurrent protective device
Add a switch and overcurrent protective device (250V,3A) to the feed power source
to prevent an electric shock on wiring. The unit has no replaceable fuse.
(2) Connect after the power source is turned OFF
When performing power and input/output wiring, make sure to turn OFF the feed
power source to prevent an electric shock.
2) Separate from strong power circuits
For input/output wiring, avoid adjacency or parallel with strong power circuits such as power lines. Separate
50cm or more for adjacency or parallel.
3) Separate thermocouple input from heat sources.
To reduce reference junction compensation errors for thermocouple input, especially separate terminals
from heat sources (heating body). Also, avoid radiation such as direct sunlight.
4) Separate from noise sources.
Separate from noise sources as much as possible. Unexpected troubles may occur. If separation from
noise sources is disabled, implement countermeasures.
Main source
Countermeasures
Electromagnetic switch or others
Power line with distortion of wave
Inverter
Thyristor regulator
Insert noise filters between power source and input/output
terminals. CR filters are used in many cases.
!
Warning

- 13 -
5) Use crimping terminals.
(1) To prevent looseness or disconnection of terminals and short circuit between terminals, install
crimping terminals to termination of connection cables.
(2) To prevent an electric shock, use crimping terminals with insulation sleeves.
Terminal Type and Termination Treatment
Terminal board
Diameter
Tightening torque
Termination treatment (Unit: mm)
Power/Protective
conductor
M4
1.2Nm
O type
Terminals other
than the above
M3.5
0.8Nm
O type Y type
* Be sure to use O type for the alarm output terminals.
* For other terminals, use also O type as possible.
Communications
terminal
M3
0.5Nm
O type Y type
* Use O type as possible.
6) Unused terminals
Avoid using unused terminals for relaying. Electric circuits may be damaged.
Treat properly the wired cables.
Treat surely wired cables not to get hung up on people and things.
Disconnection of wiring with hanging up maycause an electric shock.
8.5 or less
4.3 or less
t: 0.8
With an insulation sleeve
8or less
3.7 or more
With an insulation sleeve
8or less
3.7 ormore
t: 0.8
With an insulation sleeve
5.2 or less
3.2 or more
t: 0.8
With an insulation
sleeve
5.2 or less
3.2 or more
With an insulation sleeve
t: 0.8
!
Warning

- 14 -
After wiring, install the
terminal cover.
L
N
Copper cable (green/yellow)
with 2mm2 of wire or more
Make sure to connect to
protective conductor of power
facility.
600V vinyl insulated
cable
Power source
3. Power/protective conductor terminals wiring
1) Power/protective conductor terminals
Turn OFF feed power source.
Before power/protective conductor terminals wiring, make sure to turn off the feed power
source to prevent an electric shock.
2) Power terminal wiring
Using 600V vinyl insulated cables as the power line,
install crimping terminals with insulation sleeves to the
termination for wiring.
Note: Use the following standard cables.
(1) IEC 60227-3
(2) ANSI/UL817
(3) CSA C22.2 No.21/49
3) Protective conductor terminal wiring
Make sure to connect to the protective conductor of the
power equipment. Install crimping terminals with
insulation sleeves for wiring.
Grounding wire: Copper cable with wire diameter
2mm2or more (green/yellow)
mark at power terminals
After wiring the power terminals have power supply voltage applied. Make sure to install
power terminal covers after wiring to prevent an electric shock.
Pay attention to power supply voltage and noise.
The power supply voltage of the unit is indicated on power terminals. Applying power
other than the indicated one causes accidents or malfunction. In addition, if the power
has noise interference, implement countermeasures such as noise cut transformer
installation.
!
!
Warning
!
Warning
!
Caution
Display based on CSAstandard in Canada. The live side
of single-phase AC power supply is L, and the neutral
side is N display. To get sufficient performance, observe
the L/N wiring.
L/N display of power terminal
Note
Power terminal
L
N
Protective
conductor terminal
100 to 240V AC
50/60Hz 40VA MAX
Power (voltage, frequency, and power consumption)
!

- 15 -
4) Measurement input terminals wiring
1) Measurement input terminal
Turn OFF the feed power source before
wiring to prevent an electric shock.
Install crimping terminals with insulation
sleeves to input terminals for wiring.
2) DC voltage (current) input wiring
Use instrumentation twisted cables for
measures against noise as input cables.
For current input, connect the shunt resistor
for current input to the channel to be
measured before wiring.
3) Thermocouple (TC) input wiring
Make sure to wire thermocouple cable (or
compensation lead wire) to input terminals of
the unit.
If a copper conductive wire is connected
halfway, big measurement error will be
generated.
In addition, avoid parallel connection of a pair
of thermocouple wires with other instruments
(controller or others) that causes troubles.
4) Resistance thermometer (RTD) input wiring
To prevent measurement errors, use 3-core
cables as the input cable in which lines have
the same resistance.
In addition, one resistance thermometer
cannot be connected in parallel with other
instruments (a controller or others).
mark on measurement input terminals
High voltage may be applied to the measurement input terminals due to common mode
noise. Allowable noise value is 30VAC or 60VDC or less. Check that the voltage is equal
to or less than the allowable value. Install terminal covers after wiring to prevent an
electric shock and protect input cables. For thermocouple input, installing terminal
covers reduces reference junction compensation errors.
!
Instrumentation
twisted cable
DC voltage input
(+)
(-)
1 2 3 4 5 6
DC voltage (current) input
!
Resistance thermometer (RTD) input
3-core cable (Same line
diameter, same length)
Note: Cable resistance per 1 cable is 10Ω or less.
3 lines have the same resistance.
1 2 3 4 5 6
Resistance thermometer
A
B
B
!
TC,mV(+) and RTD(A) terminals and TC,mV(-)
and RTD (B “middle”) terminals are insulated
for each channel, and RTD (B”lower”) terminal
shorts internally between channels.
Measurement input termiinsulation
Note
Allowable input voltage
Input type
Allowable input voltage
Voltage, thermocouple input
±10VDC *
Resistance thermometer input
±6VDC
*±60VDC for channels specified with ±10V range or more
Caution
!
Compensation leas wire
Red (+)
White (-)
1 2 3 4 5 6
Thermocouple (TC) input
!
Thermocouple
!
Warning

- 16 -
5) Input unit terminal cover mounting/removing
(1) Raise the cover to the direction of the arrow.
(2) Turn to the direction of the arrow.
(3) Pull it to the direction of the arrow to remove.
5. Alarm output terminals wiring (option)
1) Alarm output terminals
The terminal configuration depends on the output specification.
Alarm relay output 6 points (‘a’contact)
Alarm relay output 4 points (‘c’ contact)
Alarm relay output 2 points (‘a’ contact)
(1)
(2)
(3)
N.O terminal (M3.5)
COM terminal (M3.5)
Alarm relay output
(6 points)
COM terminal (M3.5)
N.O terminal (M3.5)
COM terminal (M3.5)
N.O terminal (M3.5)
ALARM RELAY
1
2
N.O terminal (M3.5)
COM terminal (M3.5)
Alarm terminal
(4points)
12
34
N.C terminal (M3.5)

- 17 -
2) Wiring
Turn OFF the feed power source and the power source for buffer relay before wiring to prevent an electric
shock.
(1) Wire the cable to the load via the buffer relay.
(2) To the alarm output terminals, type O crimp style terminal with insulation sleeve which is connected to
double insulated signal wire should be connected. ( Refer to P13 )
Mechanical relay ‘a’contact output example
Mechanical relay ‘c’ contact output example
* N.C terminal is opened on alarm occurrence in opposite way to N.O terminal.
mark on alarm output terminals
Maximum of 240VAC can be connected to the alarm output terminals of this unit.
Basic insulation (dielectric strength 1390V) is carried out between the alarm output
channels, however, from the malfunction etc. 240VAC may be output to each alarm
output terminals. Double insulation or reinforced insulation to the outside circuit
connected to an alarm output terminal should be set.
A buffer relay power supply is applied to the alarm output terminals after connections
and so creates a risk of electric shock if touched. Terminal cover must be mounted after
connection. Moreover, safety measures to the outside circuit should be set.
Implement safety measures.
The alarm output of the unit may generate output failure with wrong operation, failure,
abnormal input, or others. Double insulation or reinforced insulation in outside circuit side
of all the channels should be set in any system for safety ensuring.
!
!
Caution
!
Warning
: Contact protective element
(Attachment to a side is desirable.)
N.O
COM
b
a
Z
Z
Buffer relay
Recorder
Power
Load
: Contact protective element
(Attachment to a side is desirable.)
Buffer relay
Recorder
Power
Load
Z
Z
N.C
N.O
COM
b
a
240VAC
Max
Load
240VAC
Max
Load
※
Recorder
※Basic insulation between output channels
Double insulation
or
Reinforced insulation