Installation
• The central mixing unit can be sited anywhere on the primary before the underfloor heating manifolds.
• The mixing unit can be installed in either a horizontal or vertical position, however consideration must be given
to the circulator manufacturer’s instructions.
• The connections on the mixing unit are shown:
H = HOT (High temperature connection from the boiler) (4)
C = COLD (Return from the underfloor heating and to the boiler) (5) from UFH (3) to boiler
MIX = Mixed water outlet with water at the correct temperature for the underfloor heating (7)
• Adaptors are provided for 22mm compression connection Please ensure that the pipe work and mixing unit is
properly supported.
• Isolation valves and a bypass to be fitted as required depending on the boiler and system setup.
• Ensure that the system is free from debris. We recommend that strainers are installed to prevent debris from
entering the mixing unit.
• With the mixing unit installed and connected to the primary pipework and the circulator (10) fitted, the mixing
valve can be set to the required temperature. This is done by partially unscrewing the mixing valve knob screw (1)
and turning the knob clockwise to reduce the water temperature and anti-clockwise to increase the water
temperature. The settings and corresponding temperatures from the table below are approximate. The
temperature should be checked on the temperature gauge (6) (wait for the temperature to settle) and the setting
adjusted to achieve the desired flow water temperature. The temperature gauges at each manifold should also
be checked, if there a drop in water temperature then the setting at the mixing valve should be increased.
• The water temperature going into the underfloor heating pipe should never exceed 60˚C and should not be set
for continuous running higher than 55˚C.
• The valve is pre-set to 45˚C. This may be too low for some underfloor heating systems.
All temperatures approximate
• Once the temperature has been set, tighten the screw (1) to lock the setting.
• Check the mixed temperature from time-to-time to ensure that the system is operating as it should.