Clearion 300 Series User manual

WATER TECHNOLOGIES
300 – 360 Series
Service Manual

300 – 360 Series
Main Menu
Control Start-Up Procedures
1. To Enter Main Menu Press the Menu/Enter Button
(Time of Day will Flash)
1. 2. 2. To Set the Time of Day Press the Set/Change Button
(First Digit will Flash) Example [ 12:00 ]
- To Change Digit Value Press the Set/Change Button
- To Accept the Digit Value Press the Menu/Enter Button
- Next Digit will Flash to Begin Setting
- Once the Last Digit Display is Accepted all Digits will Flash
3. To Set A.M or P.M. Press the Menu/Enter Button
- To Change Digit Value Press the Set/Change Button Example [ A ]
- To Accept the Digit Value Press the Menu/Enter Button
- Once A.M./P.M. is Accepted the Next Menu Item will Flash
4. To Set the Number of Days between Regeneration Cycles (A) Press the Set/Change Button
- Repeat instructions from step (2) Example [ A -
07]
Notes: 1) Maximum Value is 29
2) If Value Set to 0, Automatic Regeneration will Never Occur
3) Default Setting is 7 days
4) On Metered models an “H” will appear to enter Compensated Hardness Example [ H-20]
5. To Set the Number of Days between Air-Draw Cycles (d) Press the Set/Change Button
- Repeat instructions from step (2) “Used on Centurion Filter Only” Example [ d - 01]
Notes: 1) Maximum Value is 29
2) If Value Set to 0, Air-Draw is Turned Off, but an Air Cycle will still be Completed
when a Regeneration Cycle Occurs. If the Number of Days between Air-Draw Cycles is
set to a Higher Number of Days than the Number of Days between Regeneration Cycles,
it will have No Effect. In Order to turn Off All Cycles, both the Days Between
Regeneration and Days Between Air-Draw Cycles must be Set to 0.
3) Default Setting is 1 day
6. To Exit Main Menu Press the Menu/Enter Button
Note: If No Buttons are Pressed for 60 Seconds, the Main Menu will be Exited Automatically.
Page 2
MENU
ENTER
CHANGE
SET
12:00
Menu/Enter
Button
Set/Change
Button

300 – 360 Series
Normal Operation
Electronic Connections
P= Power Supply
B= Powered in Backwash Cycle Only
S= Powered in Entire Regen. Cycle
Control Start-Up Procedures
Page 3
Control Start-Up Procedures (Cont’d)
1. Home Display
- Alternates Between the display of Time of Day and Number of Days Until the Next Regeneration.
- Days Remaining Until the Next Regeneration will Count Down from the entered Regeneration
Day Override Value Until it Reaches 0 Days Remaining.
-A Regeneration Cycle will then be Initiated at the next Designated Regeneration Time
-Metered models alternate the Time of Day and Gallons Left Until the Next Regeneration. The
meter will count down to zero and then regenerate at the scheduled time set.
2. Battery Back-Up (Uses a Standard 9-Volt Alkaline Battery)
- Installing the Battery
- Features of Battery Back-Up
Maintains the Time of Day During Power Failures
Notes: 1) During Power Failures, the Display is Turned Off to Conserve Battery Power.
However, to Confirm that the Battery is Working, Press Either Button and
the Display will Turn On for Five Seconds.
2) If Power Failure Occurs while System is Regenerating, the Isobar II Completes its
Current Position and then Pauses Until Power is Restored. The Next Position is then
Commenced from its Beginning.
3) When Used without Battery Back-Up, the Unit Acts Like a Standard Valve—When a
Power Failure Occurs, the Unit Stops at its Current Point in the regeneration Position and
then Restarts at that Point when the Power is Restored. However, the Time will be Offset
by the Increment of Time the Unit was without Power.
P B S

300 – 360 Series
Starting Extra Regeneration Cycle
Control Start-Up Procedures (Cont’d)
Page 4
1. To Start Delayed Extra Cycle Example [ 1 ]
- If Days Remaining Until Next Regeneration does not Read ‘1’, Press and Hold the Set/Change
Button for 3 Seconds Until the Display Reads ‘1’ or ‘0000’ on metered models
- Regeneration Cycle will Initiate at the Next Designated Regeneration Time
2. To Start Immediate Extra Cycle First Complete Above Step
-With Days Remaining Until the Next Regeneration at ‘1’ or ‘0000’
-Press and Hold the Set/Change Button
- After 3 Seconds the Regeneration Cycle will Begin
3. To Fast Cycle Thru Regeneration First Complete Above 2 Steps
Note: Fast Cycling is Not Necessary unless Desired to Manually Step Through Each Cycle Step
-Press and Hold the Set/Change Button for 3 Seconds to Advance to the Next Cycle Step
Softeners Filters
Step 1: Backwash Step 1: Backwash
Step 2: Brine and Rinse Step 2: Rest
Step 3: Rapid Rinse Step 3: Rapid Rinse
Step 4: Brine Refill Step 4: Not used

300 – 360 Series
Centurion Only Regeneration Cycle Step Explanations
Control Start-Up Procedures
Control Start-Up Procedures (Cont’d)
Step 1: Air Release Step
For 3 to 4 Minutes
- Not Programmable
Step 2: Backwash Step
- Default of 20 Minutes
Page 5
Step 3: Rest Step
- Default of 12 Minutes
Step 4:Rapid Rinse Step
- Default of 12 Minutes
Step 5: Air Draw Step
- Default of 12 Minutes
Notes:
- When the Valve is Between Positions, the Display will Flash the Number of the Step it is
Moving Towards.
- The Default Time at Which a Regeneration will Occur is 2:00 A.M.
New feature: The Motor’s Run Direction During a Particular Regeneration Cycle Step is
Indicated by the Rotation Direction of the Last 2 Digit Displays.
MENU
ENTER
CHANGE
SET
2-20
5-

300 – 360 Series
Final Set-Up
Error Codes
Control Start-Up Procedures (Cont’d)
Page 6
With Proper Valve Operation Verified:
1. Add water to the top of the air check. Manually step the valve to the
Brine Draw Position and allow the valve to draw water from the brine tank
until it stops. Note: The air check will check at approximately the midpoint
of the screened intake area.
2. Next, manually step the valve to the Brine Refill Position and allow the
valve to return to Service automatically.
3. With the valve in Service, check that there is about 3.0’ to 5.0’
above the grid in the brine tank, if used.
4. Fill the brine tank with salt to complete Set-Up. The control will run automatically.
There are four (4) error codes which could indicate a possible problem with the control valve:
Error 2 - Homing slot expected. Valve will begin searching for home
(Normal operation continues)
Error 3 - Encoder is not sending a signal
(Valve requires service to continue)
Error 4 - Unable to find homing slot
(Valve requires service to continue)
Error 5 - Motor overload (stalled position or shorted motor)
(Valve requires service to continue)
Error 5 Explanation: The unit thinks the motor is locked. This can only happen when the valve
is running the motor, it is not seeing any encoder slots, and the motor is overloaded. This
usually alerts the presence of corrosion inside the valve clogging the system

300 – 360 Series
Master Programming Mode
To Enter Master Programming Mode, Press and Hold both Buttons for 5 Seconds.
Note: all Master Programming functions have been preset at the factory. Unless a
change is desired, it is NOT necessary to enter Master Programming Mode.
1. Regeneration Type (t)
-This Display is used to set the Regeneration Type. This option setting is identified by the letter ‘t’ in
the left digit. There are two possible settings:
-Timeclock / Filter Delayed – The control will determine that regeneration is required when the set
regeneration time has been reached. The regeneration frequency setting will determine which days a
regeneration cycle will be initiated. Example (t - - c)
-Meter Delayed (Demand) The control will determine that a regeneration is required when the
available volume of softened water drops to or below zero. Regeneration is to begin at the scheduled
time set. Example (t - - d)
•The Set/Change button will adjust this value. To accept the digit value press the
Menu/Enter button.
2. Regeneration Day Override (A) – Meter Mode Only
-Press Menu/Enter button. This display is used to set the maximum amount of time (in days) the unit
can be in service without a regeneration. This option setting is identified by the letter ‘A’ in the left
digit. Regeneration will begin at the scheduled time. A setting of zero will cancel this feature.
-Example: Override every 7 days (A- 07) or Cancel setting (A-00) Maximum setting is 29.
3. To Set Regeneration Time (r) Example [r 12A]
- The time of day at which a regeneration may take place is designated by the letter ‘r’.
- The first display digit indicates A.M or P.M. To change the value press the Set/Change button.
- Press Menu/Enter button to accept the value and move to the next digit.
- The second and third display digits indicate the hour at which the regeneration will occur.
- Change the Digits with the Set/Change button and accept with the Menu/Enter button.
- After the entire display flashes, press the Menu/Enter button to move to the next menu item.
2. 2. 4. To Set Regeneration Cycle Step Times (2)(3)(4)(5) Example [ # - 20]
- The next 4 displays set the duration of time in minutes for each regeneration cycle step.
- The step number which is currently modifiable is indicated on the far left of the display screen.
- The number of minutes allotted for the selected regeneration step is displayed on the far right.
- Change the digits values using the Set/Change and Menu/Enter buttons as described above.
Note on Air-Draw Cycle (5): Centurion Filter Only
The longer the unit is set to remain in the air-draw cycle (5), the more air is drawn into the system. A
default setting of 12 minutes draws air down to the level of a normal resin bed height and then returns
the unit to the home display. If the system needs more air, increase the time setting for step (5) or
change the number of days between air-draw cycles to 2-3 days (or lower than your current setting).
There is no way to view the number of days until the next air draw will take place.
Page 7

300 – 360 Series
5. System Capacity in Grains (c) – Meter Mode Only
-Press the Menu/Enter button. This display is used to set the system capacity in grains and is used in conjunction
with the hardness setting to calculate total gallons of treated water available between regenerations. This option
is identified by the letter ‘c’ in the left digit. The maximum value for this item is 399.
Example: 32,000 grain capacity (c 032)
6. To Exit the Master Programming Mode Press the Menu/Enter Button
Note: If no buttons are pressed for 60 seconds, the Master Programming Mode will be exited automatically.
Page 8

300 – 360 Series
Master Programming Mode Flow Chart
MENU
ENTER
CHANGE
SET
Regen. Time
MENU
ENTER
CHANGE
SET
MENU
ENTER
To Change Value
To Accept Value
Regen. Step
2,3,4, & 5 MENU
ENTER
CHANGE
SET
MENU
ENTER
To Change Value
To Accept Value
-To Enter Master Programming Mode,
Press and Hold both Buttons for 5 Seconds
The Program Mode will be exited
and normal operation resumed.
Repeat for
All Steps
Page 9

300 – 360 Series
Control Valve Drive Assembly
Page 10
Page 10

300 – 360 Series
Valve Drive Assembly Parts List
Part Number
Description
1
20111X001
Slide Cover
2
20001X111
Screw / Bracket
3
20111X003
Back Bracket
4
20001X008
Washer / Piston
5
n /a
Screw / Motor
6
EVB-010 MTR PA
Motor
6
EVB-015 MTR
Centurion Motor
7
20001X005
Back Plate
8
20001X001
Screws Power Head
9
20001X120
Main Gear
10
20001X107
Encoder Wheel
11
20001X111
Encoder
12
20001X004
Front Plate
13
n /a
Screw / Board
14
EVB-015
Elec. Board Soft & Filter
14
EVB-015-CF
Elec. Board Centurion
15
20111X010
Electronic Housing Cover
16
20111X007
Electronic Housing Button
17
20111X002
Front Bracket
18
n /a
Washer / Front Bracket
19
VH1-B (Softeners)
Body Assembly
19
VH2-B (Filters)
Body Assembly
20
20111X009
Air Injector Assembly
21
20111X013
Air Injector O-Ring
22
20111X012
Nipple Check Valve
L-Iso2S, L-Iso2F, L-CF
Electronic Housing Label
Page 11

300 – 360 Series
Control Valve Drive Assembly (Filter Version)
Page 12

300 – 360 Series
Control Valve Drive Assembly Parts List
(Filter Version)
Page 13
15
O-Ring
20561X204
1
16
O-Ring
20001X215
1
17
O-Ring
N/S
2
18
Injector Plug
N/S
1
19
O-Ring
N/S
2
19A
Injector Plug & O-Ring Assembly -
Incl. (1) EA. #17 Through #19
20001X217
1
20
Injector Seal
20001X224
1
21
Injector Cap
20001X223
1
22
10-24 X 1 Hex Washer HD Screw
20001X226
2
22A
Filter Conversion Kit -
Incl. (1) EA. #19A, #24A,
#26A, #20, #21, & (2) #22
20001X221
1
23
O-Ring
N/S
1
24
Filter Plug
N/S
1
24A
O-Ring & Filter Plug Assembly -
Incl. (1) EA. #23 & #24
20001X229
1
25
O-Ring
N/S
1
26
Brine Valve Cap
N/S
1
26A
O-Ring & Brine Valve Cap Assembly
20001X230
1
Items #27 Through #30 Used Only With Clock Regeneration
27
Adapter Coupling
N/S
2
28
O-Ring
20561X216
4
28A
Adapter Coupling & O-Ring Assembly -
Incl. (1) #27 & (2) #28
20561X215
1
29
Mounting Clip
20561X201
2
30
8-18 X 5/8" Hex Washer HD Screw
20561X217
2
N/S Indicates Non-Stocked Item
Shaded Ref # Indicates Assembly or Kit
Ref
#
Description
Part #
Qty
0
Valve Body Complete
20001X200
1
1
Valve Body Only
20001X201
1
2
End Spacer
N/S
1
3
Seal
N/S
5
4
Spacer
N/S
4
4A
Seal & Spacer Kit -
Incl. (1) #2, (5) #3, & (4) #4
20001X232
1
5
Down Flow Piston
N/S
1
6
Piston End Rod Retainer
N/S
1
7
End Plug Assembly
N/S
1
8
Piston Arm
N/S
1
8A
Piston Assembly -
Incl. (1) EA. #5 Through #8
20001X231
1
9
Hex Washer HD. 10-24 X 13/16" Screw
N/S
3
10
Drain Retainer
20001X214
1
11
O-Ring
20251X254
1
12
Flow Control Button 1.5 GPM
20251X266
1
Flow Control Button 2.0 GPM
20251X267
1
Flow Control Button 2.4 GPM
20251X268
1
Flow Control Button 3.0 GPM
20251X269
1
Flow Control Button 3.5 GPM
20251X270
1
Flow Control Button 4.0 GPM
20251X271
1
Flow Control Button 5.0 GPM
20251X272
1
Flow Control Button 7.0 GPM
20251X274
1
13
Plastic Flow Control Housing
N/S
1
14
Drain Line Fitting 90°Elbow
1/2" NPT X 1/2" Tubing
20251X255
1
14A
Flow Control Assembly - Specify GPM on Order. -
Incl. (1) EA. #11 Through #14
Flow Control Assembly 1.5 GPM - PVC
20251X256
1
Flow Control Assembly 2.0 GPM - PVC
20251X257
1
Flow Control Assembly 2.4 GPM - PVC
20251X258
1
Flow Control Assembly 3.0 GPM - PVC
20251X259
1
Flow Control Assembly 3.5 GPM - PVC
20251X260
1
Flow Control Assembly 4.0 GPM - PVC
20251X261
1
Flow Control Assembly 5.0 GPM - PVC
20251X262
1
Flow Control Assembly 7.0 GPM - PVC
20251X264
1

300 – 360 Series
Control Valve Assembly (Softener Version)
Page 14

300 – 360 Series
Control Valve Drive Assembly Parts List (Softener Version)
Ref
#
Description
Part #
Qty
0
Valve Body Complete
20001X200
1
1
Valve Body Only
20001X201
1
2
End Spacer
N/S
1
3
Seal
N/S
5
4
Spacer
N/S
4
4A
Seal & Spacer Kit -
Incl. (1) #2, (5) #3, & (4) #4
20001X232
1
5
Down Flow Piston
N/S
1
6
Piston End Rod Retainer
N/S
1
7
End Plug Assembly
N/S
1
8
Piston Arm
N/S
1
8A
Piston Assembly -
Incl. (1) EA. #5, #6, #7, & #8
20001X231
1
9
Hex Washer HD. 10-24 X 13/16"
Screw
N/S
3
10
Brine Valve Seat
N/S
1
11
Brine Valve Stem
N/S
1
12
Brine Valve Spacer
N/S
1
13
O-Ring
N/S
1
14
Quad Ring
N/S
1
15
Brine Valve Cap
N/S
1
16
Brine Valve Spring
N/S
1
17
Plain Nylon Washer
N/S
1
18
Retaining Ring
N/S
1
18A
Brine Assembly -
Incl. (1) EA. #10 Through #18
20001X210
1
19
Drain Retainer
20001X214
1
20
O-Ring
20251X254
1
21
Flow Control Button 1.5 GPM
20251X266
1
Flow Control Button 2.0 GPM
20251X267
1
Flow Control Button 2.4 GPM
20251X268
1
Flow Control Button 3.0 GPM
20251X269
1
Flow Control Button 3.5 GPM
20251X270
1
Flow Control Button 4.0 GPM
20251X271
1
Flow Control Button 5.0 GPM
20251X272
1
Flow Control Button 7.0 GPM
20251X274
1
22
Plastic Flow Control Housing
N/S
1
23
Drain Line Fitting 90°Elbow
1/2" NPT X 1/2" Tubing
20251X255
1
23A
Flow Control Housing - Specify GPM on Order. -
Incl. (1) EA. #20 Through #23
Flow Control Assembly 1.5 GPM -
PVC
20251X256
1
Flow Control Assembly 2.0 GPM -
PVC
20251X257
1
Flow Control Assembly 2.4 GPM -
PVC
20251X258
1
Flow Control Assembly 3.0 GPM -
PVC
20251X259
1
Flow Control Assembly 3.5 GPM -
PVC
20251X260
1
Flow Control Assembly 4.0 GPM -
PVC
20251X261
1
Flow Control Assembly 5.0 GPM -
PVC
20251X262
1
Flow Control Assembly 7.0 GPM -
PVC
20251X264
1
Ref
#
Description
Part #
Qty
24
O-Ring
20561X204
1
25
O-Ring
20001X215
1
26
O-Ring
N/S
2
27
Injector Plug
N/S
1
28
O-Ring
N/S
2
28A
Injector Plug & O-Ring
Assembly -
Incl. (1) EA. #26, Through
#28
20001X217
1
29
Injector Throat
N/S
1
30
Injector Nozzle
N/S
1
31
Vortex Generator
N/S
1
31A
Injector Assembly - Specify Size -
Incl. (1) EA. #26, & #28 Through
#31
20001X219
1
32
Injector Screen
20001X222
1
33
Injector Seal
20001X224
1
34
Injector Cap
20001X223
1
35
10-24 X 1 Hex Washer HD
Screw
20001X226
2
35A
Injector Kit - Specify Size -
Incl. (1) EA.
#31A, #32, #33, #34, & (2)
#35
20001X220
1
36
BLFC Button Retainer
20561X240
1
37
5 GPM BLFC Button
20251X318
1
38
O-Ring
20561X239
1
39
BLFC Adapter
20561X241
1
39A
BLFC Assembly .5 GPM -
Incl. (1) EA. #36 through #39
20001X228
1
N/S Indicates Non-Stocked Item
Shaded Ref # Indicates Assembly
or Kit
Page 15
Items #40 Through Used Only With Clock Regeneration
40
Adapter Coupling
N/S
2
41
O-Ring
20561X216
4
41A
Adapter Coupling & O-Ring
Assembly -
Incl. (1) #40 & (2) #41
20561X215
1
42
Mounting Clip
20561X201
2
43
8-18 X 5/8" Hex Washer HD
Screw
20561X217
2

300 – 360 Series
Meter Assembly Parts List
Meter Assembly
Ref
#
Description
Part #
Qty
1A
Meter Assembly, Turbine Complete
20564X200
1
Page 16

300 – 360 Series
By-Pass Assembly (Plastic)
Page 17
Ref
#
Description
Part #
Qty
1
Plastic Bypass Valve Assembly
20561X292
1

300 – 360 Series
Ref
#
Description
Part #
Qty
1
Bypass Valve 3/4" Stainless
Steel
20561X270
1
Bypass Valve 1" Stainless Steel
20561X283
1
Page 18
By-Pass Assembly
(Stainless Steel)

300 – 360 Series
Service Instructions
A. General Preliminary Instructions—PERFORM BEFORE ALL SERVICING OPERATIONS!
1. Turn off water supply to conditioner:
If the conditioner installation has a “three valve” by-pass system, first open the valve in the by-pass line,
then close the valves at the conditioner inlet and outlet.
If the conditioner has an integral by-pass valve, put it in the by-pass position.
If there is only a shut-off valve near the conditioner inlet, close it.
2. Relieve water pressure in the conditioner by stepping the control into the backwash position momentarily.
Return the control to the service position.
3. Unplug electrical cord from outlet.
4. Disconnect brine tube and drain line connections at the injector body.
B. To Replace Brine Valve (need first A1-A3?)
1. Remove the control valve back cover.
Disconnect the meter signal wire from the
meter
2. Remove screw and washer at drive yoke.
Remove powerhead mounting screws. The
entire powerhead assembly will now lift off
easily.
3. Remove piston retaining plate screws and pull
upward on end of piston yoke until assembly is
out of valve.
4. Pull brine valve from injector body, also
remove and discard O-ring at bottom of brine
valve hole.
5. Apply silicone lubricant to new O-ring and
reinstall at bottom of brine valve hole.
6. Apply silicone lubricant to O-ring on new
Brine valve assembly and press into brine
valve hole, shoulder on bushing should be
flush with injector body.
7. Insert screws through injector cap and into
mating holes in the valve body. Tighten screws.
8. Reconnect brine tube and drain line.
9. Return by-pass or inlet valving to normal service
position. Water pressure should now be applied
to the conditioner, and any by-pass line shut off.
10. Check for leaks at all seal areas. Check drain
seal with the control in the backwash position.
11. Plug electrical cord into outlet.
12. Set time of day and cycle the control valve
manually to assure proper function. Make sure
control valve is returned to the service position.
13. Make sure there is enough salt in the brine tank.
14. Start regeneration cycle manually if water is hard.
C. To Replace Injectors and Screen (need first A1-A3?)
1. Remove injector cap screws, remove cap and
discard gasket. Remove vortex generator from
end of the injector assembly.
2. Remove injector assembly. Apply silicone
lubricant to new injector assembly O-rings and
install. Be sure to push injector assembly tightly
so O-rings are seated. Replace vortex generator.
Install a new screen.
3. Apply silicone lubricant to new gasket and install
around oval extension on injector cap.
4. Repeat B7-B14
D. To Replace Powerhead
1. Remove the control valve back cover. Remove the
three screws along the outer edge of the back plate
and remove the front cover. Disconnect the power
supply and the circuit board signal wire from the
motor and feed them back through he control.
Disconnect the optical sensor signal wire.
Disconnect the meter signal wire from circuit board
and feed back through the control.
2. Remove screw and washer at drive yoke. Remove
powerhead mounting screws. The entire
powerhead assembly will now lift off easily.
3. Put new powerhead on top of the valve. Be sure
the drive pin on main gear engages slot in drive
yoke (wide side of drive yoke upright must face to
the left away from the motor).
4. Replace powerhead mounting screws. Replace
screw and washer at drive yoke.
5. Reconnect meter signal, optical sensor, power
supply, and circuit board signal wires.
6. Reinstall front cover and back cover.
Page 19

300 – 360 Series
Service Instructions (Cont’d)
Page 20
E. To Replace Piston Assembly
1. Follow Steps A.1 through A.3
2. Remove control valve back cover. Disconnect
the meter signal wire from the meter
3. Remove screw and washer at drive yoke.
Remove powerhead mounting screws. The entire
powerhead assembly will now lift off easily.
4. Remove piston retaining plates screws.
5. Pull upward on end of piston yoke until assembly
is out of valve.
6. Inspect the inside of the valve to make sure that
all spacers and seals are in place, and that there is
no foreign matter that would interfere with the
valve operation.
7. Take new piston assembly as furnished and push
piston into valve by means of the end plug.
Twist drive yoke carefully in a clockwise
direction to properly align it with drive gear.
Reinstall piston retaining plate screws.
8. Place powerhead on top of valve. Be sure drive
pin on main gear engages slot in drive yoke (wide
side of drive yoke upright must face to the left
away from the motor).
9. Replace powerhead mounting screws. Replace
screw and washer at drive yoke.
10. Reconnect brine tube and drain line.
11. Return by-pass or inlet valving to normal service
position. Water pressure should now be applied
to the conditioner, and any by-pass line shut off.
12. Replace the control valve back cover.
13. Follow Steps A.9 through A.13
F. To Replace Seals and Spacers
1. Follow Steps A.1 through A.3
2. Remove the control valve back cover.
Disconnect the meter signal wire from the
meter.
3. Remove screw and washer at drive yoke.
Remove powerhead mounting screws. The
entire powerhead assembly will now lift off
easily. Remove piston retaining plate screws.
4. Pull upward on end of piston rod yoke until
assembly is out of valve. Remove and replace
seals and spacers.
5. Take piston assembly and push piston into valve
by means of the end plug. Twist drive yoke
carefully in a clockwise direction to properly
align it with drive gear. Reinstall piston retaining
plate screws. (Same as E7-E9?)
6. Place powerhead on top of valve. Be sure drive
pin on main gear engages slot in drive yoke (wide
side of drive yoke upright must face to the left
away from the motor).
7. Replace powerhead mounting screws. Replace
screw and washer at drive yoke.
8. Return by-pass or inlet valving to normal service
position. Water pressure should now be applied
to the conditioner, and any by-pass line shut off.
9. Replace the control valve back cover. (Same as
E11-E13?)
10. Follow Steps A.9 through A.13
G. To Replace Meter
1. Follow Steps A.1 through A.3
2. Remove two screws and clips at by-pass valve or
yoke. Pull resin tank away from plumbing
connections.
3. Remove signal wire from meter.
4. Remove two screws and clip at meter and pull
the meter out of the control valve.
5. Apply silicone lubricant to four new O-rings and
assemble to four ports on new meter.
6. Assemble meter to control valve. Note: meter
portion of module must be assembled at valve
outlet. Install two screws and clips.
7. Install signal wire into new meter.
8. Push resin tank back to the plumbing connections
and engage meter ports with by-pass valve or
yoke.
9. Attach two clips and screws at by-pass valve or
yoke. Be sure clip legs are firmly engage with
lugs.
10. Return by-pass or inlet valving to normal service
position. Water pressure should now be applied
to the conditioner, and any by-pass line shut off.
11. Check for leaks at all seal areas.
12. Follow steps A.9 through A.13.
H. To Check Drive Motor Operation
1. Remove the control valve back cover.
2. To verify drive motor operation, push service
button located on back of motor. Motor should
run. Release button. After 1 minute, the control
should automatically advance to Rapid Rinse
(cycle #4) Position. It will remain in Rapid
Rinse for 5 minutes and then advance to Service
Position.
Other manuals for 300 Series
2
This manual suits for next models
1
Table of contents
Popular Control Unit manuals by other brands

VLT
VLT 670 Series Installation, operating, & maintenance instructions

Kemo Electronic
Kemo Electronic M171 manual

M-system
M-system EtherCAT R7I4DECT-1-PA8A instruction manual

Charger
Charger SP Series Programming manual

ASCO Valves
ASCO Valves 8210 Series Installation & maintenance instructions

Skylab
Skylab WG217 user manual