CleaverBrooks CB780 User manual

INSTALLATION INSTRUCTIONS
32-00207-01
SIL3
Capable
CB780/CB784
Relay Modules
APPLICATION
The Cleaver-Brooks CB780/CB784 (833-2718/833-
2720) is a microprocessor based integrated burner control
for automatically fired gas, oil, or combination fuel single
burner applications. The CB780 consists of a Relay
Module and Keyboard Display Module. The CB784
consists of the Relay Module only. The Keyboard Display
Module is optional with the CB784. Subbase, Amplifier,
and Purge Card are required to complete the system.
Options include DATA CONTROLBUS MODULE™*, Remote
Display Mounting, First-Out Expanded Annunciator or
Modbus™ Module.
The CB780/CB784 is programmed to provide a level of
safety, functional capability and features beyond the
capacity of conventional controls.
Functions provided by the CB780/CB784 include
automatic burner sequencing, flame supervision, system
status indication, system or self-diagnostics and
troubleshooting
FEATURES
• Safety features:
— Interlock check.
— Closed loop logic test.
— Dynamic AMPLI-CHECK™.
— Dynamic input check.
— Dynamic safety relay test.
— Dynamic self-check logic.
— Expanded safe-start check.
— High Fire Purge Switch test.
— Internal hardware status monitoring.
— Low Fire Start Switch test.
— Tamper resistant timing and logic.
• Access for external electrical voltage checks.
• Application flexibility.
• Communication interface using Modbus Module
833-2820.
• Dependable, long-term operation provided by
microcomputer technology.
• First-out annunciation and system diagnostics
provided by a 2 row by 20 column Vacuum
Fluorescent Display (VFD) located on the Keyboard
Display Module (Optional on CB784).
Contents
Application ..................................................................................... 1
Features .......................................................................................... 2
Specifications ............................................................................... 2
Principal Technical Features .................................................. 6
Safety Provisions ......................................................................... 6
Installation ..................................................................................... 7
Wiring ............................................................................................... 10
Assembly ......................................................................................... 13
Operation ........................................................................................ 17
Static Checkout ............................................................................ 26
Troubleshooting ........................................................................... 26

CB780/CB784 RELAY MODULES
32-00207—01 2
• First-out expanded annunciation with 26 Light
Emitting Diodes (LEDs) for limits and interlocks
(optional).
• Five sequence information Light Emitting Diodes
(LEDs).
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Local or remote annunciation of operation and fault
information.
• Nonvolatile memory for retaining history files and
sequencing status after loss of power.
• Remote reset (optional).
• Report generation (optional).
• Burner controller data:
— Sequence status.
— Sequence time.
—Holdstatus.
—Lockout/alarmstatus.
— Flame signal strength.
— Expanded annunciator status.
— Total cycles of operation.
— Total hours of operation.
— Fault history of six most recent faults:
• Cycles of operation at time of fault.
• Expanded annunciator data at time of fault.
• Fault message and code.
• Hours of operation at time of fault.
• Sequence status at time of fault.
• Sequence time at time of fault.
— Diagnostic information:
• Device type.
• Flame amplifier type.
• Flame failure response time.
• Manufacturing code.
• On/Off status of all digital inputs and outputs.
• Selected prepurge time.
• Software revision and version of CB780/CB784
and Keyboard Display Module.
• Status of configuration jumpers.
• Status of Run/Test Switch.
SPECIFICATIONS
Electrical Ratings (see Table 1):
Voltage and Frequency: 120 Vac (+10/-15%), 50 or 60 Hz
(±10%).
Keyboard Display Module: 13 Vdc peak full wave rectified
(+20/-15%).
Power Dissipation:
CB780/CB784: 10W maximum.
Display Module: 3W maximum.
Maximum Total Connected Load: 2000 VA.
Fusing: 15A maximum, Type SC or equivalent—fast blow.

CB780/CB784 RELAY MODULES
332-00207—01
aThe CB780/CB784 must have an earth ground providing a connection between the subbase and the control panel or
the equipment. The earth ground wire must be capable of conducting the current to blow the 15A fuse (or breaker) in
event of an internal short circuit. The CB780/CB784 needs a low impedance ground connection to the equipment frame
which, in turn, needs a low impedance connection to earth ground. For a ground path to be low impedance at RF fre-
quencies, the connection must be made by minimum length conductors having maximum surface areas. Wide straps or
brackets are preferred rather than leadwires. Be careful to ensure that mechanically tightened joints along the ground
path, such as pipe or conduit threads or surfaces held together with fasteners, are free of nonconductive coatings and
are protected against mating surface corrosion.
b2000 VA maximum connected load to CB780/CB784 Assembly.
cCan also be 120 Vac, 1A pilot duty, Terminals 8 & 10 sum of the “c“ loads must not exceed 8A.
dCan also be 65 VA pilot duty with motorized valve, 1150 VA inrush, 460 VA open, 250 VA hold.
Environmental Ratings:
Ambient Temperature:
Operating: -40°F to +140°F (-40°C to +40°C).
Storage: -40°F to +150°F (-40°C to +66°C).
Humidity: 85% RH continuous, noncondensing.
Vibration: 0.5G environment.
Dimensions:
Refer to Fig. 1 and 2.
Weight:
CB780/CB784: 1 pound 10 ounces, unpacked.
Keyboard Display Module: 4 ounces, unpacked.
IMPORTANT:
Flame Detection System available for use with
CB780/CB784. To select your Plug-in Flame Sig-
nal Amplifier and matching Flame Detector, see
Table 2.
Table 1. Terminal Ratings.
Terminal No. Description Ratings
GFlame Sensor Grounda—
Earth G Earth Grounda—
L2(N) Line Voltage Common —
3 Alarm 120 Vac, 1A pilot duty.
4 Line Voltage Supply (L1) 120 Vac (+10%/-15%), 50 or 60 Hz (±10%).b
5 Burner Motor 120 Vac, 9.8AFL, 58.ALR (inrush).
6 Burner Controller and Limits 120 Vac, 1 mA.
7 Lockout/Running Interlock 120 Vac, 8A.
8 Pilot Valve/Ignition 120 Vac, 4.5A ignition and 50VA pilot duty.c
9MainFuelValve 120 Vac, 2A pilot duty.d
10 Ignition 120 Vac, 4.5A ignition.c
F(11) Flame Sensor 60 to 220 Vac, current limited.
12 Firing Rate High Fire 120 Vac, 75VA pilot duty.
13 Firing Rate Common 120 Vac, 75VA pilot duty.
14 Firing Rate Low Fire 120 Vac, 75VA pilot duty.
15 Firing Rate Modulate 120 Vac, 75VA pilot duty.
16 Unused —
17 Unused —
18 Low Fire Switch Input 120 Vac, 1 mA.
19 High Fire Switch Input 120 Vac, 1 mA.
20 Preignition Interlock Input 120 Vac, 1 mA.
21 Interrupted/Pilot Valve/First Stage Oil Valve 120 Vac, 2A pilot duty.
22 Shutter 120 Vac, 0.5A.

CB780/CB784 RELAY MODULES
32-00207—01 4
Table 2. Flame Detection Systems (Fig. 3, 4, 5).
aCircuitry tests the flame signal amplifier 12 times a minute during burner operation and shuts down the burner if the
amplifier fails.
bThe 817-1743 Flame Detector should be used only on burners that cycle on-off at least once every twenty-four hours.
Appliances with burners that remain on for twenty-four hours continuously or longer should use the 817-1121 Flame
Detector with the 833-2741 Amplifier as the ultraviolet flame detection system.
cCircuitry tests all electronic components in the flame detection system (amplifier and detector) 12 times a minute
during burner operation and shuts down the burner if the detection system fails. Series 4 amplifiers check 60 to 120
times per minute.
Table 3. Sequence Timing For Normal Operation.a
*STANDBY and RUN can be an infinite time period.
**PURGE will be determined by which purge card is selected.
aThe operating sequence of the CB780 and CB784 Relay Modules are identical. The only difference between the Relay
Modules is that the Keyboard Display Module is standard with the CB780 and optional with the CB784.
bThe MFEP will be determined by which terminal is used, see Fig. 7 and 18.
SIL 3 Capable:
SIL 3 Capable in a properly designed Safety Instrumented
System. See form number 65-0312 for Certificate Agree-
ment.
Approvals:
Underwriters Laboratories Inc. listed, File No. MP268,
Guide No. MCCZ.
Factory Mutual approved, Report No. 1V9A0. AF.
IRI acceptable.
Federal Communications Commission, Part 15,
Class B—Emissions.
Mounting:
833-2725 for panel mount.
Required Components:
CB780: 120 Vac, 50/60 Hz, 833-2718.
CB784: 120 Vac, 50/60 Hz, 833-2720.
Plug-in Flame Signal Amplifier, see Table 2.
Plug-in Purge Timer Cards: selectable:
833-2730—30 sec.
833-2731—60 sec.
833-2732—90 sec.
833-2733—-2-1/2 min.
NOTE: The CB780 and CB784 are identical except for
the Keyboard Display Module which is standard
with the CB780 and optional with the CB784.
Accessories:
Optional:
DATA CONTROLBUS MODULE™—part no. 833-2729.
Provides communication and remote reset capabili-
ties on CB784; remote display capabilities on CB780
and CB784.
CB783 Expanded Annunciator—part no. 833-2726.
Keyboard Display Module—part no. 833-2727. (Stan-
dard on CB780; optional on CB784.)
Remote Mounting Kit for the Keyboard Display, NEMA
4—part no. 833-2740.
Tester—part no. 626-5050.
Plug-In Flame Amplifiers Applicable Flame Detectors
Type Color Self-Checking Part Number
Flame
Failure
Response
Time Fuel Type Part Number
Infrared Red No 833-2722 3 sec. Gas, oil, coal Infrared
(Lead Sulfide)
817-1742
Dynamic
AMPLI-CHECK™ 833-2723a
Red/Whi
te
No 833-3495 Infrared 817-4133
Dynamic
AMPLI-CHECK™ 833-3496a
Ultraviolet Purple No 833-2724 Gas, oil Ultraviolet 817-1743b
Ultraviolet
Self-Check
Green Dynamic
Self-Check 833-2741cGas, oil, coal Ultraviolet
(Purple Peeper®)
817-1121
Device Initiate Standby Purge
Flame
Establishing
Period
Run
Post
Purge
Timing
Interlock
Circuits
Firing
Rate
Circuit
Energy
Saving
Prepurge
Approval
Code BodiesPilot Main
CB780/
CB784
10 sec. * ** 4 or 10
sec.
10 or
15
sec.b
* 15 sec. Preignition
, Lockout,
High and
Low Fire
4-wire
modulatin
g
No FM/IRI
Modulating

CB780/CB784 RELAY MODULES
532-00207—01
Fig. 1. Mounting dimensions of CB780/CB784 Relay Module and 833-2725 Subbase, in inches (mm).
Fig. 2. Mounting dimensions of Keyboard
Display Module, in inches (mm).
Fig. 3. Ultraviolet Self-Check detector, mounting
dimensions in inches (mm).
Fig. 4. Ultraviolet detector, mounting
dimensions in inches (mm).
BURNER CONTROL
POWER
PILOT
FLAME
MAIN
ALARM
RESET
5
(127)
5 (127)
M23943C
REMOVE ONLY FOR TERMINAL TEST ACCESS.
1
1
5-1/4 (133)
BACK
ENTER
Edit: -+
2-1/32
(52)
BURNER CONTROL
29/32
(23)
19/32
(15)
1-1/4
(32)
1-1/32
(26)
5/32
(4)
5/16
(8)
M23388C
1/2
(13)
7/16 (11)
1-5/16
(49) 2-7/16 (62)
29/32
(23)
5/32 (4)
15/32
(12)
3-7/8 (99)
5/16
(8)
13/
32
(11)
BACK
ENTER
Edit: -+
4-27/32 (123)
4-3/32 (104)
2-3/4
(69)
MOUNTING FLANGE
1/2- 14 NPSM
LEADWIRES FACEPLATE
3/4Ð14 NPT
M20935A
3-3/4
(95)
7-7/32
(183)
5-1/8 (130)
3-7/16
(87)
5-1/4 (133)
817-1121
COLLAR WITH 1/2-14 NPSM
INTERNAL THREADS
4 (102) 6 FOOT (1.83 METER)
LEADWIRES (2)
M20937A
3-1/2 (89)
1-1/16
(27)
817-1743

CB780/CB784 RELAY MODULES
32-00207—01 6
Fig. 5. Infrared detector, mounting dimensions
in inches (mm).
PRINCIPAL TECHNICAL
FEATURES
The CB780/CB784 provides all customary flame
safeguard functions while providing significant
advancements in the areas of safety, annunciation and
system diagnostics.
Safety Shutdown (Lockout) Occurs
If:
1. INITIATE Period
a. Purge card is not installed or removed.
b. Purge card is bad.
c. Configuration jumpers were changed (after 200
hours).
d. AC line power errors, see Operation.
e. Four minute INITIATE period is exceeded.
2. STANDBY Period
a. Flame signal is present after 240 seconds.
b. Preignition Interlock is open an accumulative
time of 30 seconds.
c. Interlock check feature is enabled and the Inter-
lock String (including the airflow switch) is
closed for 120 seconds with controller closed.
d. Ignition/pilot valve/intermittent pilot valve ter-
minal is energized.
e. Main valve terminal is energized.
f. Internal system fault.
g. Purge card is not installed or removed.
h. Purge card is bad.
3. PREPURGE Period
a. Preignition Interlock opens anytime during PRE-
PURGE.
b. Flame signal detected after first ten seconds
during PREPURGE.
c. High Fire Switch fails to close within four min-
utes, fifteen seconds after firing rate motor is
commanded to drive to high fire position at start
of PREPURGE.
d. Low Fire Switch fails to close within four minutes,
fifteen seconds after firing rate motor is com-
manded to drive to low fire position at end of
PREPURGE.
e. Lockout Interlock does not close within 10 sec-
onds.
f. Lockout Interlock opens during PREPURGE.
g. Ignition/pilot valve/intermittent pilot valve ter-
minal is energized.
h. Main valve terminal is energized.
i. Internal system fault.
j. Purge card is removed.
k. Purge card is bad.
4. PILOT FLAME ESTABLISHING Period (PFEP)
a. Low Fire Switch opens.
b. Lockout Interlock opens.
c. Ignition/pilot valve/intermittent pilot valve ter-
minal is not energized.
d. Early Spark Termination terminal is energized
after five seconds.
e. No flame is present at end of PFEP.
f. Internal system fault.
g. Purge card is removed.
h. Purge card is bad.
5. MAIN FLAME ESTABLISHING Period (MFEP)
a. Low Fire Switch opens.
b. Lockout Interlock opens.
c. Ignition/pilot valve/intermittent pilot valve ter-
minal is not energized.
d. Main valve terminal is not energized.
e. No flame is present at end of MFEP.
f. Internal system fault.
g. Purge card is not installed or removed.
h. Purge card is bad.
6. RUN Period
a. No flame is present.
b. Lockout Interlock opens.
c. Main valve terminal is not energized.
d. Internal system fault.
e. Purge card is not installed or removed.
f. Purge card is bad.
7. POSTPURGE Period
a. Preignition Interlock does not close within five
seconds or opens after five-second time period.
b. Ignition/pilot valve/intermittent pilot valve ter-
minal is energized.
c. Main valve terminal is energized.
d. Internal system fault.
e. Purge card is removed.
f. Purge card is bad.
SAFETY PROVISIONS
Internal Hardware Status
Monitoring
The CB780/CB784 checks the purge card for correct
parity to prevent purge timing shifts and circuitry failures.
It also analyzes the integrity of the configuration jumpers
and internal hardware. The POWER LED blinks every four
seconds, signifying an internal hardware check.
Closed Loop Logic Test
The test verifies the integrity of all safety critical loads,
terminals 8, 9, 10 and 21. If the loads are not energized
properly; i.e., the main valve terminal is powered during
PREPURGE, the CB780/CB784 will lockout on safety
shutdown. The CB780/CB784 must react to input
APERTURE
BUSHING WITH
MAGNIFYING LENS COLLAR, 3/4-14 NPSM
INTERNAL THREADS
3/4-14
NPSM
3/4-14 NPSM
INTERNAL
THREADS
HEAT BLOCKCELL MOUNT
M27237A
2 LEADS IN A
48 INCH (1.2 METER)
FLEXIBLE CONDUIT
2-3/4*
(70)
1-1/4
(32)
1-5/8 (41)
1-1/16 (27)
1-1/4
(32)
817-1742 OR 817-4133
*
817-4133 IS 2-1/4 (58) TOTAL LENGTH

CB780/CB784 RELAY MODULES
732-00207—01
changes but avoid the occurrence of nuisance shutdown
events. Signal conditioning is applied to line voltage
inputs to verify proper operation in the presence of normal
electrical line noise such as transient high voltage spikes
or short periods of line dropout. Signal conditioning is
tolerant of synchronous noise (line noise events that occur
at the same time during each line cycle).
Dynamic Ampli-Check™
Dynamic AMPLI-CHECK™ circuitry tests the flame signal
amplifier during burner operation and shuts down the
CB780/CB784 if the flame amplifier fails.
Dynamic Flame Amplifier and
Shutter Check
Self-checking circuitry tests all electronic components in
the flame detection system and amplifier 10 to 12 times
per minute and shuts down the CB780/CB784 if the
detection system fails.
Dynamic Input Check
All system input circuits are examined to verify that the
CB780/CB784 is capable of recognizing the true status of
external controls, limits and interlocks. If any input fails
this test, a safety shutdown occurs and the fault is
annunciated.
Dynamic Safety Relay Test
Checks the ability of the dynamic safety relay contacts to
open and close. It also verifies that the safety critical loads,
terminals 8, 9, 10 and 21, can be de-energized, as
required, by the Dynamic Self-Check logic.
Dynamic Self-Check Safety Circuit
The microcomputer tests itself and related hardware while
at the same time the safety relay system tests the
microcomputer operation. If a microcomputer or safety
relay failure occurs and does not allow proper execution of
the
self-check routine, safety shutdown will occur and all
safety critical loads will be de-energized.
Expanded Safe-Start Check
The conventional safe-start check, which prevents burner
start-up if flame is indicated at start-up, is expanded to
include a flame signal check during STANDBY, a
preignition interlock check, an interlock check, and a
safety critical load check.
High Fire Purge and Low Fire Start
Switch Tests
High Fire Purge Switch Test examines the Purge Position
Interlock Switch at the moment the firing rate motor is
commanded to the high fire position. If the switch is
bypassed, welded or otherwise closed prematurely, the
system will automatically add 30 seconds to allow
additional drive time for the firing rate motor to reach or
near the open position before starting the purge timing;
otherwise, purge timing starts when the High Fire Switch
is closed. This switch will also cause a hold (four minutes,
fifteen seconds) condition when the switch is open before
purge or opens during purge. The
CB780/CB784 will lockout and annunciate an alarm if the
switch fails to close within the hold time period.
Low Fire Start Switch Test examines the Low Fire Start
Switch at the moment PREPURGE is completed. If the
switch is bypassed, welded or otherwise prematurely
closed, the system automatically adds 30 seconds to allow
the firing rate motor additional time to reach or near the
low fire start position before ignition trials; otherwise,
ignition trials start after the Low Fire Switch closes. The
test also is used to prove that the firing rate motor is at low
fire position throughout the ignition trial period. This
switch will also cause a hold (four minutes, fifteen
seconds) condition if the switch opens after purging is
complete. The CB780/CB784 will lockout and annunciate
an alarm if the switch fails to close within the hold time
period.
Mandatory Purge
If lockout occurs after the initiation of ignition trials, (or at
anytime during a sequence when the fuel valves may have
been energized), a mandatory POSTPURGE period is
imposed.
Off Cycle (STANDBY or PREPURGE)
Flame Signal Check
The flame detection subsystem (flame detector and
amplifier) is monitored during STANDBY. If a flame
simulating condition or an actual flame exists, a system
hold occurs and start-up is prevented. If the flame signal
exists at any time after the first 40 seconds of STANDBY, a
safety shutdown will occur and be annunciated. A shutter-
check amplifier and self-checking detector are energized
for the first 40 seconds during STANDBY and the last two
seconds before exiting STANDBY. If a flame exists, a safety
shutdown occurs. An
AMPLI-CHECK™ Amplifier is energized continually
through STANDBY and PREPURGE to detect any
possibility of a runaway detector or a flame. If either
situation happens, a safety shutdown occurs. A standard
amplifier is energized continually through STANDBY and
PREPURGE. If either situation happens, a safety shutdown
occurs.
Preignition Output Circuit Check
At the end of PREPURGE, the Dynamic Safety Relay
operation is checked. Also, all safety critical loads,
terminals 8, 9, 10 and 21 are checked to verify the
terminals are not powered. If the Dynamic Safety Relay
operation is faulty, or if any of the safety critical loads are
powered, safety shutdown occurs and is annunciated.
Tamper-Resistant Timing and Logic
Safety and logic timings are inaccessible and cannot be
altered or defeated.

CB780/CB784 RELAY MODULES
32-00207—01 8
Verified Spark Termination
The ignition terminal is monitored to verify early spark
termination (five seconds ignition and pilot and five
seconds pilot only).
First-Out Annunciation and Self-
Diagnostics
Sequence Status Lights (LEDs) provide positive visual
indication of the program sequence: POWER, PILOT,
FLAME, MAIN and ALARM. The green POWER LED blinks
every four seconds to signify the CB780/CB784 hardware
is running correctly.
Multi-function Keyboard Display Module (standard with
CB780, optional with CB784) shows elapsed time during
PREPURGE, PILOT IGN, MAIN IGN, and POSTPURGE. As
an additional troubleshooting aid, it provides sequence
timing, diagnostic information, historical information and
expanded annunciator information when a safety
shutdown or hold or normal operation occurs.
First-out Annunciation reports the cause of a safety
shutdown or identifies the cause of a failure to start or
continue the burner control sequence with an English text
and numbered code via the Keyboard Display Module. It
monitors all field input circuits, including the Flame
Signal Amplifier and Firing Rate Position Switches. The
system distinguishes 118 modes of failure and detects
and annunciates difficult-to-find intermittent failures.
Self-Diagnostics adds to the First-out Annunciation by
allowing the CB780/CB784 to distinguish between field
(external device) and internal (system related) problems.
Faults associated within the flame detection subsystem,
CB780/CB784 or plug-in Purge Card, are isolated and
reported by the Keyboard Display Module, see
Troubleshooting section and CB780/CB784 System
Annunciation Diagnostics and Troubleshooting, Bulletin
Number CB-7803.
Interlock Requirements
The following interlock inputs are provided:
Low Fire Interlock
This interlock verifies the firing rate motor is in the low fire
position before and during ignition trials.
High Fire Interlock
This interlock verifies the firing rate motor is in the high
fire position prior to and during PREPURGE.
Lockout Interlock
This interlock (ILK) input signifies a Lockout Interlock. If
the Lockout Interlock is open for more than ten seconds
into PREPURGE, the CB780/CB784 will lockout. After
entering PREPURGE, if the Lockout Interlock opens
during the first ten seconds, the purge timer will be reset.
This provides a continuous PURGE to occur without
interruption before the Pilot Flame Establishing Period. If
a Lockout Interlock opens anytime after ten seconds into
PURGE, during the Ignition Trials or Run, it causes a
lockout.
A typical Lockout Interlock string contains an airflow
switch (see Fig. 7). The Interlock Check is a site
configurable option (see Table 7). If this feature is enabled,
the CB780/CB784 will lockout after 120 seconds
whenever control terminal 6 is energized, and the Lockout
Interlock string (including airflow switch) is closed during
STANDBY.
Preignition Interlock
The Preignition Interlock input is typically connected to
proof-of-closure switches for fuel valve(s). The Preignition
Interlock must be energized throughout PREPURGE. If the
Preignition Interlock opens during STANDBY, it causes a
hold (30 seconds). The CB780/CB784 will lockout if the
interlock does not close within 30 seconds during
STANDBY. If the Preignition Interlock opens during
PREPURGE, it will lockout. If the Preignition Interlock is
open after five seconds into POSTPURGE, the
CB780/CB784 will lockout. The Preignition Interlock is
ignored during the ignition trials state and during RUN.
INSTALLATION
WARNING
Fire or Explosion Hazard.
Can cause severe injury, death or property
damage.
To prevent possible hazardous burner operation,
verification of safety requirements must be
performed each time a control is installed on a
burner.
When Installing This Product…
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous
condition.
2. Check the ratings given in the instructions and
marked on the product to make sure the product is
suitable for the application.
3. Installer must be a trained, experienced, flame safe-
guard technician.
4. After installation is complete, check out the product
operation as provided in these instructions.
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect the power supply before beginning
installation to prevent electrical shock, equipment
and control damage. More than one power supply
disconnect may be involved.
Wiring Information
1. Wiring connections for the CB780/CB784 are
unique; therefore, refer to Figs. 6, 7, 8 or 9 or the cor-
rect Specifications for proper subbase wiring.
2. Wiring must comply with all applicable codes, ordi-
nances and regulations.

CB780/CB784 RELAY MODULES
932-00207—01
3. Wiring, where required, must comply with NEC Class
1 (Line Voltage) wiring.
4. Loads connected to the CB780/CB784 must not
exceed those listed on the CB780/CB784 label or
the Specifications, see Table 1.
5. Limits and interlocks must be rated to simultane-
ously carry and break current to the ignition trans-
former, pilot valve, and main fuel valve(s).
6. All external timers must be listed or component rec-
ognized by authorities who have jurisdiction for the
specific purpose for which they are used.
IMPORTANT:
1. For on-off gas-fired systems, some authorities
who have jurisdiction prohibit the wiring of any
limit or operating contacts in series between the
flame
safeguard control and the main fuel valve(s).
2. Two Flame Detectors can be connected in parallel
with the exception of Infrared Flame Detector
(817-1742).
3. This equipment generates, uses and can radiate
radio frequency energy and, if not installed and
used in accordance with the instructions, may
cause interference to radio communications. It
has been tested and found to comply with the lim-
its for a Class A computing device of Part 15 of
FCC rules which are designed to provide reason-
able protection against such interference when
operated in a commercial environment. Operation
of this equipment in a residential area may cause
interference; in which case, the users at their own
expense may be required to take whatever mea-
sures are required to correct this interference.
4. This digital apparatus does not exceed the Class A
limits for radio noise for digital apparatus set out
in the Radio Interference Regulations of the Cana-
dian Department of Communications.
Humidity
Install the CB780/CB784 where the relative humidity
never reaches the saturation point. The CB780/CB784 is
designed to operate in a maximum 85% RH continuous,
noncondensing, moisture environment. Condensing
moisture may cause a safety shutdown.
Vibration
Do not install the CB780/CB784 where it could be
subjected to vibration in excess of 0.5G continuous
maximum vibration.
Weather
The CB780/CB784 is not designed to be weather tight. If
installed outdoors, the CB780/CB784 must be protected
by an approved weather-tight enclosure.
Mounting Wiring Subbase
NOTE: For installation dimensions, see Fig. 1.
1. Mount the subbase in any position except horizon-
tally with the bifurcated contacts pointing down. The
standard vertical position is recommended. Any
other position decreases the maximum ambient
temperature rating.
2. The 833-2725 Wiring Subbase can be mounted
directly in the control cabinet. Be sure to allow ade-
quate clearance for servicing, installation, access or
removal of the CB780/CB784, Expanded Annuncia-
tor, Keyboard Display Module, flame amplifier, flame
amplifier signal voltage probes, Run/Test Switch,
electrical signal voltage probes and electrical field
connections.
3. For surface mounting, use the back of the subbase
as a template to mark the four screw locations. Drill
the pilot holes.
4. Securely mount the subbase using four no. 6 screws.
WIRING
1. Proper Wiring:
a. For proper subbase wiring, refer to Fig. 7.
b. For proper remote wiring of the Keyboard Display
Module, refer to Fig. 8, 9 or 10 or to the Specifica-
tions for the Keyboard Display Module, Modbus™
Module or DATA CONTROLBUS MODULE™.
2. Disconnect the power supply from the main discon-
nect before beginning installation to prevent electri-
cal shock and equipment damage. More than one
disconnect may be involved.
3. All wiring must comply with all applicable electrical
codes, ordinances and regulations. Wiring, where
required, must comply with NEC, Class 1 (Line Volt-
age) wiring.
4. Recommended wire size and type:
a. All Line Voltage terminals use no. 14 or 16 cop-
per conductor (90°C or higher) 600 volt insula-
tion wire (wire size must be coordinated with fuse
protection). For high temperature installations,
use wire selected for a temperature rating above
the maximum operating temperature. All lead-
wires should be moisture resistant.
b. Keyboard Display Module—For communications
purposes, use an unshielded 22 AWG 2-wire
twisted cable and one wire for ground if the lead-
wire run and noise conditions permit; however,
some installations may need up to five wires,
three for communications and two for remote
reset (in either a single cable or separate cables
for communications or remote reset) or use
Belden 8771 shielded cable or equivalent. The
Keyboard Display Module, DATA CONTROLBUS
MODULE™ (for remote mounting or communica-
tions) or Modbus Module must be wired in a
daisy chain configuration, (1(a)-1(a), 2(b)-2(b),
3(c)-3(c)). The order of interconnection of all the
devices listed above is not important. Be aware
that modules on the closest and farthest end of
the daisy chain configuration string require a
120 ohm (1/4 watt minimum) resistor termina-
tion across terminals 1 and 2 of the electrical
connectors, for connections over 100 feet, see
Fig. 8, 9 and 10.
c. DATA CONTROLBUS MODULE™—For communi-
cations purposes, use an unshielded 22 AWG 2-
wire twisted cable if the leadwire run and noise

CB780/CB784 RELAY MODULES
32-00207—01 10
conditions permit; however, some installations
may need up to five wires, three for communica-
tions and two for remote reset (in either a single
cable or separate cables) or use a Belden 8771
shielded cable or equivalent. The Keyboard Dis-
play Module, DATA CONTROLBUS MODULE™
(for remote mounting or communications) or
Modbus Module must be wired in a daisy chain
configuration, (1(a)-1(a), 2(b)-2(b),
3(c)-3(c)). The order of interconnection of all the
devices listed above is not important. Be aware
that modules on the closest and farthest end of
the daisy chain configuration string require a
120 ohm (1/4 watt minimum) resistor termina-
tion across terminals 1 and 2 of electrical con-
nectors, for connections over 100 feet, see Fig. 8,
9 and 10.
Fig. 6. Internal block diagram of the CB780/CB784 (see Fig. 7, 8, 9, or 10 for detailed wiring instructions.
CONFIGURATION
JUMPERS
MICROCOMPUTER
RESET
PUSHBUTTON
RUN/TEST
SWITCH
STATUS LEDs
PLUG-IN PURGE
TIMER CARD
SAFETY RELAY
CIRCUIT
POWER SUPPLY
KEYBOARD
DISPLAY MODULE
HIGH FIRE
COMMON
MODULATE
LOW FIRE
HIGH FIRE SWITCH
PLUG-IN
FLAME
AMPLIFIER
RELAY
DRIVE
CIRCUIT
CONTROL
POWER
TEST
JACK
REMOTE
RESET
DDL
DDL
COMMUNICATIONS
INDICATES FEEDBACK SENSING
TO RELAY STATUS FEEDBACK
AND LINE VOLT INPUTS
FIELD WIRING
INTERNAL WIRING
IGNITION
PILOT
PILOT/V2
MAIN VALVE
1K
9K
RELAY
STATUS
FEEDBACK
AND LINE
VOLTAGE
INPUTS
LIMITS CONTROLLER
LOCKOUT
INTERLOCK
PRE-IGNITION
INTERLOCK
1K1 2K1 5K1
8K1
8K2
9K1
9K2
120 Vac
FLAME SIGNAL
TEST
LOW FIRE SWITCH
PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DEDICATED DATA LINK.
RS485
1
2
3
L1
(HOT) L2
4
6
20
7
4K1
7K1
2K2
10
8
21
9
18
19
8K
7K
6K
5K
4K
3K
2K
F
G
22
1
BLOWER
6K1
5
ALARM
3K1
3
L2
12
13
15
14
M7420A
2
2
1

CB780/CB784 RELAY MODULES
11 32-00207—01
d. Remote Reset—Use no. 22 AWG or greater
twisted pair wire, insulated for low voltage; see
Fig. 8, 9 and 10.
e. Use the recommended wire size for the 13 Vdc
full wave rectified transformer power input of no.
18 AWG wire insulated for voltages and tempera-
tures encountered in the application. Suggested
wire types include TTW(60C), THW(75C) and
THHN(90C).
5. Recommended grounding practices:
a. The earth ground provides for a connection
between the subbase and the control panel of
the equipment. The earth ground wire must be
capable of conducting the current to blow the
20A fuse (or breaker) in event of an internal short
circuit. The CB780/CB784 needs a low imped-
ance ground connection to the equipment frame
which, in turn, needs a low impedance connec-
tion to earth ground. For a ground path to be low
impedance at RF frequencies, the connection
must be made with minimum length conductors
that have a maximum surface area. Wide straps
or
brackets are preferred rather than leadwires. Be
careful to ensure that mechanically tightened
joints along the ground path, such as pipe or
conduit threads or surfaces held together with
fasteners, are free of nonconductive coatings
and are protected against corrosion on mating
surfaces.
b. Keyboard Display Module, DATA CONTROL BUS
MODULE™ or Modbus™ Module—The shield, if
used, should be connected to the signal ground
terminal 3(c) provided as part of the
CB780/CB784 device ControlBus connection.
Connect the shield at both ends to earth ground.
c. CB780/CB784—Each CB780/CB784 will have
an earth ground terminal that must be grounded
to the metal control panel with wire as short as
practical. Each ground wire must be capable of
carrying a fault current equal to the rating of the
protective fuse (20A). A number 14 copper con-
ductor is adequate, but wide straps or brackets
are preferred rather than leadwires.
6. Recommended wire routing:
a. Flame detector leadwires:
(1) Do not run high voltage ignition transformer
wires in the same conduit with the flame
detection wiring.
(2) Do not route scanner wires in conduit with
line voltage circuits.
(3) Enclose scanner wires without armor cable in
metal cable or conduit.
(4) Follow directions in flame detector Instruc-
tions.
b. DATA CONTROLBUS OR MODBUS MODULE™:
(1) Do not run high voltage ignition transformer
wires in the same conduit or close proximity
with the MODULE™ wiring.
(2) Do not route MODULE™ wires in conduit with
line voltage circuits.
c. Keyboard Display Module (VFD): Because the
VFD is powered from a low voltage, energy lim-
ited source, it can be mounted outside of a con-
trol panel if it is protected from mechanical
damage.
d. Remote Reset:
(1) Do not run high voltage ignition transformer
wires in the same conduit with the Remote
Reset wiring.
(2) Do not route Remote Reset wires in conduit
with line voltage circuits.
NOTE: A 13 Vdc power supply must be used any time
more than one Keyboard Display Module is used.
7. Maximum wire lengths:
a. CB780/CB784 leadwires—The maximum length
of leadwire is 300 feet to terminal inputs (Con-
trol, Preignition Interlock, Running/Lockout
Interlock, High Fire Switch and Low Fire Switch).
b. Flame Detector leadwires—The maximum flame
sensor leadwire length is limited by the flame
signal strength.
c. Remote Reset leadwires—The maximum length
of wire is 1000 feet to a Remote Reset pushbut-
ton.
d. DATA CONTROLBUS or MODBUS MODULE™—
The maximum module cable length depends on
the number of system modules connected, the
noise conditions and the cable used. The maxi-
mum length of all interconnecting wire is 1000
feet.
8. Make sure loads do not exceed the terminal ratings.
Refer to the label on the CB780/CB784 or to the rat-
ings in Specifications; see Table 1.
9. Check the power supply circuit. The voltage and fre-
quency tolerance must match those of the
CB780/CB784. A separate power supply circuit may
be required for the CB780/CB784. Add the required
disconnect means and overload protection.
10. Check all wiring circuits and complete the Static
Checkout, see Table 8, before installing the
CB780/CB784 on the subbase.
11. Install all electrical connectors.
12. Restore power to the panel.

CB780/CB784 RELAY MODULES
32-00207—01 12
Fig. 7. Wiring the CB780/CB784 Relay Module.
M7408A
G
L2
3
4
5
6
7
8
9
10
F
(L1)
13
14
15
16
17
18
19
20
21
22
12
LOCKOUT INTERLOCKS
(INC. AIR FLOW SWITCH)
MASTER
SWITCH
LOW FIRE
START SWITCH
5 SECOND IGNITION
(EARLY SPARK)t
(TERMINATION)
MAIN FUEL
VALVE(S)
BURNER
CONTROLLER/LIMITS
BURNER MOTOR
(BLOWER)
HIGH FIRE
COMMON
LOW FIRE
MODULATE
120V ALARM
10 SEC. INTERRUPTED
PILOT/IGNITION
PREIGNITION
INTERLOCK
SERIES 90
FIRING RATE
MOTOR
SERIES 90
CONTROLLER
817-1742
INFRARED
(LEAD SULFIDE)
FLAME DETECTOR
817-1743
ULTRAVIOLET
FLAME DETECTOR
817-1121
ULTRAVIOLET
FLAME DETECTOR
120V, 50/60 Hz POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
DO NOT WIRE TO ANY UNUSED TERMINALS.
FOR DIRECT SPARK IGNITION (OIL
OR GAS)
IGNITION
TRANSFORMER
FUEL VALVE
R
W
B
R
W
B
L1
(HOT)
L2 1
OR
OR
BLUE
BLUE
WHITE
YELLOW
L2
WHITE
WHITE
BLACK
BLACK
L1
L2
8
9
10
L2
833-2725
2
15 SEC.
INTERRUPTED
PILOT VALVE
2
1
HIGH FIRE
PURGE SWITCH

CB780/CB784 RELAY MODULES
13 32-00207—01
Fig. 8. Wiring multiple Keyboard Display Modules.
L1
(HOT)
L2
1
1
1
A
B
A
B
C (GND)
+13 VDC
RESET
C (GND)
+13 VDC
RESET
123 45
123 45
MOMENTARY
PUSH BUTTON
SWITCH
833-2727 KEYBOARD DISPLAY MODULE
(MOUNTED ON CB 780/CB 784 RELAY MODULE)
13 VDC
POWER SUPPLY
833-2727 REMOTE KEYBOARD DISPLAY MODULE
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO 120
OHM TERMINATING RESISTORS ARE REQUIRED FOR
CONNECTIONS OVER 100 FEET. CABLE SHIELD MUST BE
TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED
CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
M27263A
832-1693
120 OHM
RESISTOR
832-1693
120 OHM
RESISTOR
2
2TERMINALS OF 833-2760 5-WIRE CONNECTOR (PROVIDED
SEPARATELY).

CB780/CB784 RELAY MODULES
32-00207—01 14
Fig. 9. Wiring the Data ControlBus™ Module with Remote Keyboard Display Module.
ASSEMBLY
Mounting CB780/CB784 Relay
Modules
NOTE: For installation dimensions, see Fig. 1.
Relay Module Mounting
1. Mount the CB780/CB784 vertically, see Fig. 11, or
mount horizontally with the knife blade terminals
pointing downward. The CB780/CB784 must be in
an electrical enclosure.
2. Select the location in the electrical enclosure. Be
sure to allow adequate clearance for servicing,
installation and removal of the CB780/CB784, Key-
board Display Module, flame amplifier, flame ampli-
fier signal voltage probes, electrical signal voltage
probes, and electrical connections.
a. Allow an additional two inches below the
CB780/CB784 for the flame amplifier mounting.
b. Allow an optional three-inch minimum to both
sides of the CB780/CB784 for electrical signal
voltage probes.
3. Make sure no subbase wiring is projecting beyond
the terminal blocks. Tuck wiring in against the back
of the sub-base so it does not interfere with the knife
blade terminals or bifurcated contacts.
IMPORTANT:
The CB780/CB784 must be installed with a plug-
in motion rather than a hinge action.
4. Mount the CB780/CB784 by aligning the four L
shaped corner guides and knife blade terminals with
the bifurcated contacts on the wiring subbase and
tightening the two screws securely without deform-
ing the plastic.
Installing the Purge Card
1. Remove the Keyboard Display Module or DATA
CONTROLBUS MODULE™, see Fig. 13 or 14.
2. Remove the current Purge Card from the
CB780/CB784 by pulling the plastic support cover
upward.
3. Make sure that the Purge Card selected has the
desired timing.
4. Insert Purge Card into the opening of the
CB780/CB784 compartment, see Fig. 12.
1
1
2
2
832-1693
120 OHM
RESISTOR
832-1693
120 OHM
RESISTOR
1
A
B
A
B
C (GND)
+13 VDC
RESET
C (GND)
+13 VDC
RESET
12345
123 45
MOMENTARY
PUSH BUTTON
SWITCH
833-2729 DATA CONTROLBUS OR 833-2820 MODBUS MODULE™
(MOUNTED ON CB 780/CB 784)
833-2727 REMOTE KEYBOARD DISPLAY MODULE
THREE WIRE SHIELDED CABLE MAY BE REQUIRED. TWO
832-1693 120 OHM TERMINATING RESISTORS ARE REQUIRED
FOR CONNECTIONS OVER 100 FEET. CABLE SHIELD MUST BE
TERMINATED TO EARTH GROUND AT BOTH ENDS. IF SHIELDED
CABLE IS NOT USED, TWISTED PAIR WIRE MUST BE USED.
WHEN CONNECTING THE KEYBOARD DISPLAY MODULE DATA
CONTROLBUS MODULE™, OR REMOTE RESET MODULE
EXTERNAL FROM THE CONTROL CABINET, APPROPRIATE
MEASURES MUST BE TAKEN TO MEET EN60730 SAFETY
LOW VOLTAGE REQURIEMENTS (SEE APPROVALS).
M27260A
3
3

CB780/CB784 RELAY MODULES
15 32-00207—01
5. Reinstall the Keyboard Display Module or DATA
CONTROLBUS MODULE™ onto the CB780/CB784
and restore power to the device.
6. Run the burner system through at least one com-
plete cycle to verify the system is operating as
desired.
Fig. 10. Electrical panel installation.
IMPORTANT:
The CB780 will not function properly without one
of the following mounted correctly: Keyboard Dis-
play Module, or DATA CONTROLBUS MODULE™.
Mounting Keyboard Display
Module
1. Align the two interlocking ears of the Keyboard Dis-
play Module with the two mating slots on the
CB780/CB784; see Fig. 13.
2. Insert the two interlocking ears into the two mating
slots and with a hinge action push on the lower cor-
ners of the Keyboard Display Module to secure it to
the
CB780/CB784.
3. Verify the Keyboard Display Module is firmly in
place.
Mounting Data ControlBus™
Module
1. Align the two interlocking ears with the two mating
slots on the CB780/CB784; see Fig. 14.
2. Insert the two interlocking ears into the two mating
slots and push on the lower corners of the DATA
CONTROLBUS MODULE™ to secure it to the
CB780/CB784.
3. Be sure the DATA CONTROLBUS MODULE™ is firmly
in place.
Fig. 11. Purge card installation.
Fig. 12. Keyboard Display Module installation.

CB780/CB784 RELAY MODULES
32-00207—01 16
Fig. 13. Data ControlBus™ mounting.
Remote Mounting of Keyboard
Display Module
1. The Keyboard Display Module can be mounted
either on the face of a panel door or on other remote
locations; see Fig. 15.
2. When mounting the Keyboard Display Module on
the face of a door panel, closely follow these instruc-
tions:
a. Select the location on the door panel for flush
mounting. Pay attention to the insertion dimen-
sion of the two Keyboard Display Module screws,
two interlocking ears and the two plug-in con-
nectors to allow for sufficient clearance, 1/4 inch
minimum inward from the surface of the door
panel.
b. Use the Keyboard Display Module as a template;
see Fig. 28. Mark the two screw locations, two
interlocking ear locations and two plug-in con-
nector locations. Drill the pilot holes for the
mounting screws. Provide for two holes on the
door panel for the interlocking ears and plug-in
connector holes.
c. Mount the Keyboard Display Module securing
the two no. 4 screws.
3. A second Keyboard Display Module or a Data
ControlBus™ Module must be installed on the
CB780/CB784. Connections from the module to the
remote display are completed following wiring
shown in Fig.8, 9, 10.
Installing Plug-In Flame Signal
Amplifier
1. Disconnect power supply before beginning installa-
tion to prevent electrical shock and equipment dam-
age. More than one disconnect may be involved.
2. Align the amplifier circuit board edge connector with
the keyed receptacle on the CB780/CB784. Verify
the amplifier nameplate faces away from the Relay
Module, see Fig. 16.
3. Push in the amplifier until the circuit board is fully
inserted into the receptacle and then push the
amplifier toward the CB780/CB784 retaining clasp.
4. Verify the amplifier is firmly in place.
5. Perform all required checkout tests.
Installing the Flame Detector
NOTE: Table 2 lists the flame detection systems avail-
able for use with the CB780/CB784. Make sure
the correct combination of amplifier and flame
detector(s) is used.
Proper flame detector installation is the basis of a safe
and reliable flame safeguard installation. Refer to the
instructions packed with the flame detector and the
equipment manufacturer instructions; see Fig. 17.
Keep the flame signal leadwires as short as possible from
the flame detector to the wiring subbase. Capacitance
increases with leadwire length, reducing the signal
strength. The maximum permissible leadwire length
depends on the type of flame detector, leadwire and
conduit. The ultimate limiting factor in the flame detector
leadwire is the flame signal; see Table 9.
Fig. 14. Remote mounting of Keyboard Display Module.
Fig. 15. Flame signal amplifier mounting.

CB780/CB784 RELAY MODULES
17 32-00207—01
Fig. 16. Flame detector wiring.
OPERATION
Sequence of Operation
The CB780/CB784CB780/CB784 has the following
operating sequence, see Fig. 18 and Table 4.
INITIATE
The CB780/CB784 enters the INITIATE sequence when
the Relay Module is powered. The CB780/CB784 can also
enter the INITIATE sequence if the Relay Module verifies
voltage fluctuations of +10/-15% or frequency
fluctuations of ±10% during any part of the operating
sequence. The INITIATE sequence lasts for ten seconds
unless the voltage or frequency tolerances are not met.
When the tolerances are not met, a hold condition will be
initiated and will be displayed on the VFD for at least five
seconds. When the tolerances are met, the INITIATE
sequence will restart. If the condition is not corrected and
the hold condition exists for four minutes, the
CB780/CB784 will lockout. Causes for hold conditions in
the INITIATE sequence:
1. AC line dropout is detected.
2. AC line noise that can prevent a sufficient reading of
the line voltage inputs.
3. Brownouts caused by a low line voltage.
The INITIATE sequence
also delays the burner
motor starter from being
energized and
de-energized from an
intermittent AC line input
or control input.
STANDBY
The CB780/CB784 is
ready
to start an operating
sequence when the
operating control
determines a call for heat
is present. The burner
switch, limits, operating control and all microcomputer
monitored circuits must be in the correct state for the
CB780/CB784 to continue into the PREPURGE sequence.
NORMAL START-UP PREPURGE
The CB780/CB784 provides a PREPURGE timing
selectable from 30 seconds to 2-1/2 minutes with power
applied and the CB780/CB784 operating control
indicating a call for heat:
Running Interlocks, Preignition Interlocks, Burner Switch,
Run/Test Switch, Lockout Interlocks and all
microcomputer
monitored circuits must be in the correct operating state.
1. The blower motor output, terminal 5, is powered to
start the PREPURGE sequence. The firing rate motor
is driven to the high fire position. The PREPURGE
timing does not begin until the Lockout Interlock
String and High Fire Switch are both closed.
2. The Preignition Interlock input must remain closed
throughout PREPURGE; otherwise, safety shutdown
occurs.
BLUE
YELLOW
WHITE
WHITE
BLACK
BLACK
F
G
22
L2
L1
L2
M27238A
BLUE
WHITE
F
G
F
G
INFRARED (817-1742, 817-4133)
ULTRAVIOLET (817-1743)
SOLID STATE SELF-CHECKING
ULTRAVIOLET (817-1121)
1
2
1FLAME DETECTOR LEADS ARE COLOR CODED. THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE WHITE
MUST BE CONNECTED TO THE G TERMINAL. THE UV SENSING TUBE IS POLARITY SENSITIVE. REVERSING THE LEADS EVEN
MOMENTARILY CAN DAMAGE OR DESTROY THE UV TUBE.
FLAME DETECTOR LEADS ARE COLOR CODED. THE BLUE LEAD MUST BE CONNECTED TO THE F TERMINAL AND THE YELLOW
MUST BE CONNECTED TO THE G TERMINAL. THE UV SENSING TUBE IS POLARITY SENSITIVE. REVERSING THE LEADS EVEN
MOMENTARILY CAN DAMAGE OR DESTROY THE UV TUBE.
817-1742: 1 BROWN WIRE AND 1 WHITE WIRE FROM THE 817-1742, CONNECT TO THE CB 780/CB 784 WIRING SUBBASE,
COLOR NOT IMPORTANT. 817-4133 1 BLUE WIRE CONNECTED TO THE F TERMINAL AND 1 WHITE WIRE CONNECTED TO
THE GROUND TERMINAL OF THE CB780/784 WIRING SUBBASE. KEEP WIRES AS SHORT AS POSSIBLE AND TWIST THEM.
2
3
3
INITIATE 00:10
Diagnostic Info
M20277A
STANDBY
Total Cycles 132
M20278A

CB780/CB784 RELAY MODULES
32-00207—01 18
3. The Lockout Interlock or Running Interlock inputs
(interlock circuit including Airflow Switch) must
close by ten seconds into PREPURGE; otherwise, a
safety shutdown occurs.
4. After the firing rate motor reaches the PREPURGE
rate position and PREPURGE timing is completed,
the firing rate motor will drive to the low fire position.
5. When the firing rate motor reaches low fire position,
the Low Fire Switch, terminal 18, input must be
energized before entering the Ignition Trial state.
IGNITION TRIALS
Pilot Flame
Establishing
Period (PFEP):
1. With the firing
rate motor at the
low fire position:
a. The pilot valve and the ignition transformer, ter-
minals 8, 10 and 21, are energized. The
CB780/CB784 has a fifteen second interrupted
pilot valve, terminal 21 and a ten second inter-
rupted pilot valve/ignition, terminal 8.
b. During PFEP, the Low Fire Switch must remain
closed. If it opens, a safety shutdown occurs.
c. The Preignition Interlock input is ignored
throughout the Ignition Trial state.
2. Flame must be proven by the end of the four or ten
second PFEP to allow the sequence to continue. If
flame is not proven by the end of PFEP, a safety
shutdown occurs.
3. With flame
proven, the
ignition,
terminal 10,
is
de-energized for early spark termination.
4. Main Flame Establishing Period (MFEP):
a. The CB780/CB784 has a selectable ten second
or fifteen second MFEP. After the Ignition Trials,
and with the presence of flame, the main fuel
valve, terminal 9, is powered. If a flameout
occurs, the CB780/CB784 will lockout within 3
seconds.
RUN
A ten second
stabilization
period occurs
at the beginning
of the RUN period.
1. The firing rate motor releases to modulation.
2. The CB780/CB784 is now in RUN and will remain in
RUN until the controller input, terminal 6, opens,
indicating that the demand is satisfied or a limit has
opened.
POSTPURGE
The CB780/CB784
provides a fifteen
second POST-PURGE
following the completion
of the RUN period. The blower motor output is powered to
drive all products of combustion and any unburned fuel
from the combustion chamber. It also supplies
combustion air to burn fuel being purged from the fuel
line downstream of the fuel shutoff valve.
1. The main fuel valve and intermittent pilot valve, ter-
minals 9 and 21, are de-energized and the firing rate
motor is commanded to the low fire position to begin
the POSTPURGE period.
2. The Preignition Interlock closes within the first five
seconds of POSTPURGE.
3. After the fifteen second POSTPURGE period is com-
pleted, the CB780/CB784 reenters STANDBY.
MAIN IGN 00:15
Flame Signal 2.7V
M20284A
RUN
Expanded Annun.
M20285A
POST PURGE 00:12
Device RM7800L
M20286A
PILOT IGN 00:10
Fault History
M20283A

CB780/CB784 RELAY MODULES
19 32-00207—01
Fig. 17. CB780/CB784 sequence.
KEYBOARD DISPLAY MODULE (KDM)
The first line of the Keyboard Display Module provides
current status of the burner sequence (STANDBY, PURGE,
PILOT IGN, MAIN IGN, RUN and POST-PURGE), timing
information (PURGE, PILOT IGN, MAIN IGN and
POSTPURGE) in minutes and seconds, hold information
(PURGE HOLD: T19) and lockout information (Lockout,
Fault Code, Message and Sequence); see Fig. 19. The
extreme right side of the first line will either be blank or it
will show a small arrow pointing to the second line
followed by a two-letter code (DI-Diagnostic Information,
Hn-Fault History Information, and EA-Expanded
Annunciator). When the arrow and two-letter code are
displayed, it indicates the second line is showing a
selectable message submenu. The second line will display
selectable or preemptive messages. A selectable message
supplies information for flame strength, system status
indication, system or self-diagnostics and
troubleshooting. A preemptive message will have
parentheses around the message and supply a detailed
message to support the sequence status information. A
preemptive message can also be a lockout message. A
preemptive message will replace a selectable message to
support the sequence status information. It will also
replace a selectable message after 60 seconds if it or a
lockout message is available. The CB780/CB784 LEDs
provide positive visual indication of the program
sequence: POWER, PILOT, FLAME, MAIN and ALARM.
Fig. 18. Keyboard Display Module and
sequence status LEDs (Table 4).
NOTE: Normal sequences (in Table 4) are in BOLD TYPE,
while abnormal sequences are not in bold type.
CB780/CB784
POWER
00
VFD
DISPLAY
OPERATING
CONTROLS
AND
INTERLOCKS
BURNER
FLAME
SIGNAL
FIRING
RATE
MOTOR
INITIATE
POWER
STANDBY
POWER
PREPURGE
DRIVE TO
HIGH FIRE
POWER
PILOT
FLAME
MAIN
POWER
PFEP
4 OR 10 SEC
PILOT
FLAME
MAIN
POWER
MFEP
PILOT
FLAME
MAIN
RUN
POWER
POSTPURGE
POWER
STANDBY
00 00 10 25 00 1520
MOTOR OUTPUT SWITCHING
MOTOR ACTION
BURNER/BLOWER MOTOR
IGN.
15 SEC. PILOT
LIMITS AND BURNER CONTROLLER CLOSED
LOCKOUT INTERLOCKS CLOSED
PREIGNITION INTERLOCK CLOSED
LOW FIRE SW.
SAFE START CHECK FLAME PROVING
10 SEC. IGN./PILOT 8
10
5
5 SEC.
21
6
TO
7TO
20TO
518
TO
13 15
TO
13 12
TO
M7411B
INTERLOCK CHECK
HIGH FIRE SW.
19
TO
13 14
TO 13 14
TO
5
4
6
L1
MAIN VALVE 9
TIMED
PURGE
POWER
FLAME
MAIN
PILOT
ALARM
POWER
FLAME
MAIN
PILOT
ALARMALARMALARMALARM
PREPURGE
DRIVE TO
LOW FIRE
00
LED
DISPLAY
IC
PII
SSC
833-2760 FIVE WIRE CONNECTOR FOR
COMMUNICATIONS, REMOTE KEYBOARD
DISPLAY AND REMOTE RESET
SEQUENCE
STATUS
SELECTABLE
MESSAGE OR
PREEMPTIVE
MESSAGE
SEQUENCE
STATUS
LEDs
RESET
PUSHBUTTON
FLAME
SIMULATOR INPUT FLAME CURRENT
TEST JACKS
RUN/TEST SWITCH
DI = DIAGNOSTICS
H1 = HISTORY
EA = EXPANDED
ANNUNCIATOR
CAPTIVE
MOUNTING
SCREW
PLUG-IN
PURGE
CARD
KEYBOARD
DISPLAY
MODULE
RELAY
MODULE
FLAME
AMPLIFIER
M27264B

CB780/CB784 RELAY MODULES
32-00207—01 20
Table 4. Sequence Status Display Information (see Fig. 19).
Burner Sequence LEDs Energized (BOLD type)
INITIATE minutes:seconds
selectable —message
POWER, PILOT, FLAME, MAIN AND ALARM
INITATE HOLD: AC
(AC Freq/Noise)
POWER, PILOT, FLAME, MAIN AND ALARM
INITIATE HOLD: AC
(AC Line Dropout)
POWER, PILOT, FLAME, MAIN AND ALARM
INITIATE HOLD: AC
(AC Frequency)
POWER, PILOT, FLAME, MAIN AND ALARM
INITIATE HOLD: AC
(Low Line Voltage)
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY HOLD: REM
(Remote Control)
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY HOLD: F/G
(Flame Detected)
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY HOLD:
(Preignition ILK)
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY HOLD:
(Lockout ILK)
POWER, PILOT, FLAME, MAIN AND ALARM
PURGE HOLD:
(High Fire Switch)
POWER, PILOT, FLAME, MAIN AND ALARM
PURGE DELAY
(High Fire Jumprd)
POWER, PILOT, FLAME, MAIN AND ALARM
PURGE HOLD: TEST
(Run/Test Switch)
POWER, PILOT, FLAME, MAIN AND ALARM
PURGE DELAY:
(Low Fire Jumprd)
POWER, PILOT, FLAME, MAIN AND ALARM
PURGE HOLD: F/G
(Flame Detected)
POWER, PILOT, FLAME, MAIN AND ALARM
PURGE HOLD:
(Low Fire Switch)
POWER, PILOT, FLAME, MAIN AND ALARM
PILOT IGN minutes:seconds
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
PILOT HOLD: TEST
(Run/Test Switch)
POWER, PILOT, FLAME, MAIN AND ALARM
MAIN IGN minutes:seconds
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
RUN
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
RUN
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
RUN LOWFIRE:TEST
(Run/Test Switch)
POWER, PILOT, FLAME, MAIN AND ALARM
POSTPURGE minutes:seconds
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
Waiting for connection… POWER, PILOT, FLAME, MAIN AND ALARM
RESET/ALARM TEST
selectable—message
POWER, PILOT, FLAME, MAIN AND ALARM
Additional sequence status information when an Expanded Annunciator is connected to the relay module, also see
CB780/CB784 System Annunciation Diagnostics and Troubleshooting, Bulletin Number CB-7803.
BURNER OFF:
(Burner Switch)
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY HOLD:
(Expanded Annunciator hold
message)
POWER, PILOT, FLAME, MAIN AND ALARM
STANDBY HOLD:
(Circuit Fault)
POWER, PILOT, FLAME, MAIN AND ALARM
This manual suits for next models
1
Table of contents