CLIMAVENETA W3000 compact User manual

W3000
TECHNICAL MANUAL
C0240111-04-05-GB
Replaces C0240111-03-05-GB
CLIMAVENETA S.p.A
Via Sarson, 57C
36061 Bassano del Grappa(VI)-ITALY
GB
Tel. (+39) 0424 509 500
Fax. (+39) 0424 509 509
www.climaveneta.it
The information contained in this document may be modified without prior notice.
No part of this document may be reproduced and/or disclosed to third parties or competitors.
April 2005

C0240111-04-05-GB
Summary
1 USER INTERFACE................................................................................................................ 3
2 MENU STRUCTURE ..............................................................................................................4
3 SETTING THE CONNECTIONS..............................................................................................6
3.1 Available hardware ............................................................................................................6
3.2 Connecting more than one unit............................................................................................9
3.3 Additional connections ..................................................................................................... 13
3.4 Configuring the terminals ................................................................................................. 14
4 SWITCHING THE UNIT ON AND OFF .................................................................................21
5 USER PROGRAMMING....................................................................................................... 23
5.1) SETTING THE OPERATING MODE ...................................................................................... 23
5.2) USER MENU................................................................................................................... 25
5.2.1 ) ADJUSTMENT............................................................................................................. 25
5.2.2 ) RECOVERY................................................................................................................. 31
5.3) SETPOINT MENU ............................................................................................................ 33
5.4) CLOCK MENU.................................................................................................................33
6 MANUFACTURER PROGRAMMING ..................................................................................... 34
6.1) FREECOOLING ............................................................................................................... 35
6.2) CONDENSATION ............................................................................................................ 36
7 ALARMS............................................................................................................................38
ANNEX 1A : TABLE OF W3000 MASKS .....................................................................................43
ANNEX 1B : TABLE OF W3000 BASE MASKS ............................................................................. 63
ANNEX 1C : PARAMETERS TABLE .............................................................................................69
ANNEX 2 : INPUT/OUTPUT TABLE ..........................................................................................78
“S” HARDWARE: ...................................................................................................................78
“M” HARDWARE:...................................................................................................................80
“L” HARDWARE: ...................................................................................................................82
“HL” HARDWARE: ................................................................................................................. 87
“B” HARDWARE (for hermetic compressors).............................................................................. 90
EXPANSIONS ....................................................................................................................... 92
SYMBOLS ...............................................................................................................................105
Notice:The W3000 controller software is protected by a digital signature.
This means that it can only work on cards supplied by Climaveneta and not on cards
purchased from other dealers.
2

C0240111-04-05-GB
1 USER INTERFACE
There are three types of user interface:
Depending on the type of user interface installed, there are more or less keys available for controlling the
unit and for accessing system information:
Key Description
W3000,
W3000 base
W3000
compact
[MENU key]: accesses the main menu.
[UP key]: moves around the masks and sets control parameter values
[DOWN key]: moves around the masks and sets control parameter
values
[ENTER key]: confirms entered data.
[ESC key]: goes back one level in the mask tree if you are in the
header masks, or returns to the unit controller.
[ALARM key]: displays the alarms and resets normal operating
conditions.
--- [SETPOINT key]: directly accesses the setpoint menu.
--- [ON/OFF key]: switches the machine on and off.
For each compressor, the following LED's are also located on the W3000 user interface:
Symbol Colour Description
Green If the LED shines steady the compressor is on, if it flashes the compressor
is demanded
Red The compressor is blocked by a compressor or circuit alarm
Green The compressor is in the “chiller” mode
Green The circuit is in the “freecooling” mode
Green The compressor is in the “heat pump” mode
Green If the LED shines steady the circuit is in the “recovery mode”, if it flashes
there is a “recovery alarm”
Green If the LED shines steady the circuit is in the “defrost mode”, if it flashes it is
in the “drip mode”
W3000 W3000 compact
W3000 base
3

C0240111-04-05-GB
2 MENU STRUCTURE
The tree structures for moving around the various menus are shown below.
Termoregolatore
Selezione
Menù utente
Menù Alarm
Password
utente
Esc /
Password
costruttore
Power On
Selezione
Menù unità
Selezione
Menù setpoint
Selezione
Menù I/O
Selezione
Menù orologio
Selezione
Menù costruttore
Esc
Esc
Esc
Tasto
Menù
np
np
np
np
np
Tasto
Alarm
Esc
Esc Menù utente
Menù costruttore
Menù setpoint
Menù I/O
Menù orologio
Esc
Esc
Esc /
Esc /
Esc /
Esc /
Menù unità
np
np
Esc
Esc
np
np
np
np
np
np
np
Esc /
np
Thermoregulator
Menu
key
Unit menu
selection
Setpoint menu
selection
I/O menu
selection
Clock menu
selection
User menu
selection
Manufacturer
menu selection
User
Password
Factory
Password
Alarm menu
Unit menu
Setpoint menu
I/O menu
Clock menu
User menu
Manufacturer
menu
Alarm
key
Figure 2.1:menu tree for W3000-W3000 compact
Unit menu
selection
Setpoint menu
selection
User menu
Clock menu
np
DISPLAY MASK
ESC
np
I/O menu
selection
np
np
Clock menu
selection
User menu
selection
np
Manufacturer
menu selection
np
Unit menu
Setpoint menu
I/O menu
User
password
Manufacturer
menu
ESC
Alarm menu
Display
menu
np
np
np
np
ESC
ESC
ESC
ESC
ESC
np
np
Figure 2.2:menu tree for W3000 base
4

C0240111-04-05-GB
The menus are briefly described below:
x The “Unit Menu” contains information such as temperature, pressure and circuit states.
x The “Setpoint menu” is used to set the setpoints for the various available functions.
x The “I/O menu” shows the status of the digital inputs and values read from the analogue inputs.
It also shows the status of the digital outputs and the voltage supplied to the analogue outputs.
If expansions are necessary (depending on the configuration parameters), the inputs and outputs
of the latter are also shown.
x The “Clock menu”, if the clock card is present, is used to set and display the date and time.
x Parameters relative to user programming of the unit can be displayed and set in the “User
menu”.
x The “Manufacturer menu” is used to display and set critical system parameters.
5

C0240111-04-05-GB
3 SETTING THE CONNECTIONS
Set the hardware connections before switching on the unit. The inputs/outputs table explaining the
functions of the various connectors on the unit is contained in [annex 2] at the end of this manual.
3.1 Available hardware
6
Fuse
Anal o g Sele ctio n Serial Card
Clock card
Prog ramming K ey
W3000
W3000
UNIT “L”
UNIT “S”
UNIT “M”

C0240111-04-05-GB
7
W3000
W3000
UNIT “XL”
UNIT “B”

C0240111-04-05-GB
W3000
EXPANSION “E”
8

C0240111-04-05-GB
3.2 Connecting more than one unit
Caution: perform the following operations before touching the cards in order to prevent
electrostatic discharge:
x wear the bracelet (connected to the earth circuit) and the heel strap
x the card should be closed inside an antistatic bag protecting it from electrostatic
discharge: remove it from the bag and place it on the light-blue mat with the yellow
edge or on the dark-blue mat.
x You can now work on the card.
Several intercommunicating cards can be connected together on units “L” or “XL”.
There are two connection types: “base-expansion” on the expansion serial line and “master-slave” on the
“plan” serial line. The “mixed” connection, instead, combines the two above connections. Details are
shown below.
3.2.1 “BASE-EXPANSION” CONNECTION
In the “base-expansion” connection, the entire intelligence of the unit resides in the base. The connected
expansions are exclusively used as additional I/O. The cards must be connected together with a three-
wire shielded cable connected from terminal J23 of the base to terminal J3 of expansion “E” or to
terminal J11 of expansion “M” (see figure 3.1).
Figure 3.1: “base-expansion” connection
The expansions must be given a specific address depending on the type of chiller and the enabled
functions:
EXPANSIONS FOR HERMETIC COMPRESSORS:
Additional function Function, chiller type Expansion
address
Expansion
type
Recovery enable Chiller with heat recovery 1 E
Recovery enable Multi-use
Heat pump with total heat recovery 2M
Freecooling enable
HP relay enable
Low temperature control enable
Low pressure transducer enable
Freecooling chiller
Chiller with HP relay
Low temperature chiller
Any chiller with hermetic
compressors where low pressure
monitoring is required
3E
9

C0240111-04-05-GB
Number of compressors for circuit 3
or 4
Chiller with 3 or 4 hermetic
compressors per circuit 4E
EXPANSIONS FOR SEMI-HERMETIC COMPRESSORS:
Additional function Function, chiller type Expansion
address
Expansion
type
Recovery enable Chiller with heat recovery 1 E
Recovery enable Multi-use
Heat pump with total heat recovery 2M
Freecooling enable
HP relay enable
Setpoint variation enable
Recovery setpoint variation enable
Secondary setpoint enable
Freecooling chiller
Chiller with HP relay
Unit with setpoint or secondary
setpoint enable
3E
Number of evaporators 0
Number of compressors per circuit 2
Condensing units
Unit with 2 alternative compressors
per circuit
4E
At least one pump enable
Heat pump
Recovery enable
Freecooling enable
HP relay enable
Low temperature control enable
2 evaporators
Chiller with pumps on card
Heat pump chiller
Chiller with heat recovery
Freecooling chiller
Chiller with HP relay
Low temperature chiller
Chiller with more than one
evaporator
5E
EXPANSIONS FOR CENTRIFUGE COMPRESSORS:
Additional function Function, chiller type Expansion
address
Expansion
type
Setpoint variation enable
Secondary setpoint enable
Unit with setpoint or secondary
setpoint enable 3E
10

C0240111-04-05-GB
3.2.2 “MASTER-SLAVE” CONNECTION
Intelligence is distributed instead in the “master-slave”
connections. Suppose we have a unit with 4 cooling
circuits: the master card manages circuits 1 and 2 while
the slave card manages circuits 3 and 4. In this case,
the additional card is not simply an input/output
expansion, but is fully involved managing part of the
unit. The card software is the same and identifies its
functions depending on the card address: the one with
address 1 (odd) will be the master and will
communicate with the card with address 2 (even and
greater). Pay special attention to card addresses for
this reason.
Connect the cards together with a 3-wire shielded
cable connected between terminals J11 of the cards,
as shown in figure 3.2.
Figure 3.2: “master-slave” connection
3.2.3 “MIXED” CONNECTION:
The “mixed” connection is used in units with 3/4 cooling circuits where an increase in inputs/outputs is
required. The master card manages circuits 1 and 2 while the slave card manages circuits 3 and 4.
Additionally, depending on the required functions or the type of machine, cards used simply as
expansions can be connected. The expansions will be connected to both the master and the slave if the
required inputs/outputs are circuit functions (recovery valves, freecooling,…). They will only be connected
to the master if they are machine functions (pumps, external air temperature,…).
Figure 3.3 shows the connections between the cards and the expansions: a 3-wire shielded cable
connects terminals J11 of the master and slave cards, and a 3-wire shielded cable connects terminals J23
of the master and/or slave cards with terminal J3 or J11 of expansions “E” or “M”.
11

C0240111-04-05-GB
Figure 3.3: “mixed” connection
12

C0240111-04-05-GB
3.3 Additional connections
CONFIGURING ANALOGUE INPUTS ON “S” OR “M” CARDS:
On “S” or “M” cards, the analogue inputs must be configured with dipswitches.
Analogue inputs B1, B2, B3 and B4 can be configured both as a temperature probe and as pressure
transducers; inputs B5 and B6 as temperature probes or as a digital input.
Description Dipswitch setting
Configuring analogue inputs B1, B2,
B3 and B4 as an NTC temperature
probe;
ON
123456
DIP
Configuring analogue inputs B1, B2,
B3 and B4 as a 0-20mA or 4-20mA
pressure transducer;
ON
123456
DIP
Configuring analogue inputs B5 and
B6 as an NTC temperature probe;
21
ON
Configuring analogue inputs B5 and
B6 as a digital input commanded by
an ON-OFF signal;
12
ON
Example
B1 and B2 temperature probes,
B3 and B4 pressure transducers,
B5 temperature probe,
B6 ON-OFF input.
ON
123456
DIP ON
123456
DIP
12
ON
MOUNTING THE CLOCK CARD:
The clock card manages date and time settings.
It is already built into the electronic controller on chillers with “L” cards; on chillers with “S” or “M” cards
it is already built into the Black Box card (if fitted).
Mount as follows:
1) If the clock card is not installed or is damaged, the mask shown to
the side is displayed in the “Clock” menu.
Clock card
not installed
2) Switch off the electronic control unit
3) Remove the “clock card” cover with a screwdriver
4) Fit the optional card into the toothed connector;
5) Close the cover
6) Switch on power
7) Make sure the mask shown in point 1) is no longer displayed in the “Clock” menu.
MOUNTING THE SERIAL CARD:
For information on mounting the serial card, consult the “Interface Manual“ (serial).
13

C0240111-04-05-GB
3.4 Configuring the terminals
The first operation to perform when a network is started up for the first time or an I/O card is replaced, is
to activate the procedure for terminal configuration.
This cannot be done with W3000 base. In this case, configure the terminals with a W3000 or W3000
compact terminal and then replace the display with a W3000 base.
Before starting this procedure it is advisable to check that each I/O card and each terminal has been
identified with the correct address established when the network was designed. It is important to
remember that the address set with the dip-switches or software configuration is only received if the
device is reset. RESET the device by disconnecting the power supply. Moreover, it is advisable to perform
global resetting of all network devices if a mistake has been made in the configuration of the addresses
(more than one card with the same address).
The configuration procedure can be activated from any terminal (keyboard), which may also be
connected temporarily only to perform configuration operations and removed upon completion. The
operations to perform are described in the following paragraphs.
3.4.1 SETTING THE KEYBOARD ADDRESS
After connecting the keyboard to the device (using two cables for W3000 and just one cable for W3000-
compact ) perform the following procedure:
1) Press [UP], [DOWN] and [ENTER] together and hold down until
the mask shown to the side appears.
Display address
Setting..........:00
I/O Card address:
2) Press [ENTER] to set the required keyboard address (e.g.: 21 )
using [UP] and [DOWN]
Display address
Setting..........:21
I/O Card address:--
3) This mask means that the address of the keyboard has been
set.
Display address
changed
4) If an empty mask appears, instead, it means that the keyboard
is not communicating with any card. Either the card must be
addressed or the plan network must be configured.
N.B.: This is a timed procedure; if the parameters are not set within a few seconds, the display turns off.
In this case, the operation must be repeated.
3.4.2 “S”, “M” AND “B” CARD SETTINGS
In “S”, “M” or “B” cards the card address is set by the software using the keyboard.
Proceed as follows:
1) Make sure the keyboard address is set to 0 ( see para 3.4.1).
2) Disconnect the card from the power supply (turn off the
general switch).
3) Power the card and press [ALARM] and [UP] together; hold
the keys down until the mask shown to the side appears.
pLan address: 0
UP: increase
DOWN: decrease
ENTER: save & exit
14

C0240111-04-05-GB
4) Set the required address (e.g.: 1 )
To do this, press [UP] or [DOWN]; press [ENTER] to confirm.
pLan address: 1
UP: increase
DOWN: decrease
ENTER: save & exit
5) An “empty” mask appears because the address of the keyboard
is 0 and that of the card is (for example) 1; the two devices
therefore cannot communicate. Disconnect the power supply
from the card (N.B.: the address set for the keyboard will not
be reset)
6) Set the keyboard address (see para 3.4.1): do not set it to zero
or to an address that is already used in the previously set card.
When the keyboard address is set, a blank mask appears.
7) Repeat the keyboard address setting procedure but this time
set the “I/O card address” field with the address number used
for the card. A mask similar to the one shown to the side will
appear.
Terminal Config
Press ENTER
To Continue
8) Configure the plan network (see para 3.4.4).
3.4.3 “L”, “XL” AND “E” CARD SETTINGS
1) Make sure the card is disconnected from the power supply
2) Set the required address using the dip-switches (see below)
3) Set the keyboard address (see para 3.4.1)
4) Configure the plan network (see para 3.4.4)
In this case set the card address with the following dip-switches:
ON
123456
DIP ON
1234
DIP
Cards “L”, ”XL” Cards ”E”
Table of possible combinations: (0 = off, 1= on)
Dip-switch setting
1 2 3 4 5 6
Address
000 0 0 0 0
110 0 0 0 0
201 0 0 0 0
311 0 0 0 0
400 1 0 0 0
510 1 0 0 0
601 1 0 0 0
15

C0240111-04-05-GB
711 1 0 0 0
800 0 1 0 0
910 0 1 0 0
10 01 0 1 0 0
11 11 0 1 0 0
12 00 1 1 0 0
13 10 1 1 0 0
14 01 1 1 0 0
15 11 1 1 0 0
16 00 0 0 1 0
17 10 0 0 1 0
18 01 0 0 1 0
19 11 0 0 1 0
20 00 1 0 1 0
21 10 1 0 1 0
22 01 1 0 1 0
23 11 1 0 1 0
24 00 0 1 1 0
25 10 0 1 1 0
26 01 0 1 1 0
27 11 0 1 1 0
28 00 1 1 1 0
29 10 1 1 1 0
30 01 1 1 1 0
31 11 1 1 1 0
32 00 0 0 0 1
3.4.4 CONFIGURING THE PLAN NETWORK
x CONFIGURING THE PLAN NETWORK (local):
For each unit with an on-board keyboard, perform the following procedure to create a “locale” plan
network:
1) Press [UP], [DOWN] and [ENTER] together and hold down until
the mask shown to the side appears.
Display address
Setting..........:00
I/O Card address:
2) Set the required address for the keyboard (e.g.: 21 ) Display address
Setting..........:21
I/O Card address:--
3) Press [ENTER] to display the address of the cards in pLan (in
this case 1 ).
N.B.: If there is more than one card, press [UP] or [DOWN] to
choose which card to configure.
Display address
Setting..........:21
I/O Card address:01
4) Press [ENTER] to configure the terminals; press [ENTER] to
confirm
Terminal config
Press ENTER
To continue
5) In this mask, the [ENTER] key moves the cursor from one field
to another and the [UP] or [DOWN] keys change the values.
P:01 means that the card with address 1 is being configured.
P:01 Adr Priv/Shared
Trm1 None --
Trm2 None --
Trm3 None -- Ok?No
16

C0240111-04-05-GB
6) Configure keyboard 21 (previously set) as Pr=private (usually
the one on the unit), Sp=printer or Sh=shared
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 None --
Trm3 None -- Ok?No
7) The remote keyboard must also be configured. Simply define
the keyboard addressed with 32 (even if not present) as Sh.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 32 Sh
Trm3 None -- Ok?No
8) To save the settings and exit the configuration procedure,
move the cursor to “No”, change it to “Yes” and press [ENTER].
To exit without saving the settings, wait 30 seconds without
touching the keyboard.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 32 Sh
Trm3 None -- Ok?Yes
9) The following mask may appear. If no expansions are
connected, simply press [ESC] to show the main display menu.
#####################
expansion
connection ……
#####################
To connect several units together and remote control them, thereby forming a plan network (global),
connect a remote keyboard controlling all the plans (local).
The remove keyboard cannot be used with a W3000 base keyboard. If a W3000 keyboard is fitted to the
unit, change it with a W3000 or W3000 compact.
x CONFIGURING THE PLAN NETWORK (global):
It is easy to install a PLAN network (global). Just a few but essential operations are required. If just one
of these is not performed correctly, the entire system will not work.
The remote keyboard will work problem-free if the following operations are performed one after the
other.
1 ) Set the on-board machine card and
keyboard addresses (see configuring the
local plan network)
Leaving the network cable disconnected.
configure the terminals on each card and
keyboard (then connect the remote keyboard).
2 ) Check the chillers work correctly without
being connected to the network.
3 ) Disconnect the power supply from the
chillers
4 ) Connect all the chillers to the network
except for the remote keyboard. Connect connectors J11 together. Do not connect
the remote keyboard !!!
5 ) Power the chillers.
6 ) Check that all the networked devices work
correctly
If any faults occur, check the configuration of the
terminals to make sure that no two devices have
the same address.
7 ) Connect the remote keyboard to one of the
units (see below: connecting the remote
keyboard)
If the converter is fitted (see below: remove
keyboard from 200 to 500 metres away), make
sure the remote keyboard is powered.
8 ) Make sure the remote keyboard address is
set to 32. Follow the procedure for addressing the remote
keyboard.
9 ) Make sure that the devices outside the
chillers are correctly configured.
Make sure that no two components of the
network share the same address (to avoid
conflicts)
10) Wait a few seconds until network
communication has stabilised.
17

C0240111-04-05-GB
x If there is global network comprising just W3000 chillers, the W3000-compact can be used as a
remote keyboard. After configuring the various units (each with a different address in order not
to generate conflicts in the global network), connect the remote keyboard and repeat the
procedure.
In this case, the various machines of the network are switched by pressing [ESC] and [UP]
together.
x If the plan network does not comprise just W3000 chillers, a 16-key keyboard must be used. In
this case, press [UNIT] to switch between one card and another. In this case, however, the
terminals must be given a special configuration as the 16-key keyboard is only recognised on
“terminal 3”.
The terminal configuration procedure remains the same up to point 6 of paragraph 3.4.5, after
which:
7) The remote keyboard can be configured even if the plan
network doe not comprise just W3000 chillers. Simply
define the keyboard addressed with 32 (N.B.: on
terminal 3) as Sh, i.e.: shared.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 None --
Trm3 32 Sh Ok?No
8) To save the settings and exit the configuration
procedure, move the cursor to “No”, change it to “Yes”
and press [ENTER]. To exit without saving the settings,
wait 30 seconds without touching the keyboard.
P:01 Adr Priv/Shared
Trm1 21 Pr
Trm2 None --
Trm3 32 Sh Ok?Yes
x CONNECTING THE REMOTE KEYBOARD:
x “T” SHUNT:
Figure 3.4a:photo of a T shunt
Figure 3.4b:wiring diagram of a T
shunt
Let us analyse a vital component for connecting several
units in a network: the “T” shunt.
This is a shunt with phone connectors (called A,B,C in
figure 3.4b).
CONFIGURATION: For our purposes, configure
terminals J14 and J15 (see Figure 3.4b). There are
several pins in each terminal. Short pins 1 and 2 with a
jumper.
Figure 3.4c:terminal card of a T shunt T
Screw terminal Function
0 Earth (sheath of shielded cable)
1+VRL=30V
2GND
3 Rx+/Tx+
4 Rx+/Tx+
5GND
6+VRL=30V
x REMOTE KEYBOARD UP TO 200 metres:
To connect a remote keyboard, two “T” shunt cards must be used, one near the controller and the
other near the remote keyboard, configured as indicated above. The T shunt cards must be
connected together by terminals.
1. If the remote keyboard monitors just one unit, proceed as follows:
18

C0240111-04-05-GB
x Disconnect the connector J10 connecting the keyboard on the unit with the card,
and connect it to connector “A” of the “T” shunt (see figure 3.5).
x Connect connector J10 on the card to connector “B” of the “T” shunt.
The correct configuration is shown in figure 3.5:
C
B
A
A
C
B
Figure 3.5 : connecting the remote keyboard (for distances less than 200 metres)
2. If a remote keyboard monitors more than one unit, the above configuration may only be
used for the last card in the network (the nearest to the remote keyboard).
x REMOTE KEYBOARD FROM 200 metres UP TO 500 metres
N.B.: The remote keyboard cannot be installed more than 500 m away.
If the remote keyboard must be installed over 200 metres away from the plan network, a power
unit must be installed near the remote keyboard. The only difference between this and a remote
keyboard up to 200 metres is that the power unit must be to terminals 1 and 2 of the T shunt
(the one near the remote keyboard)
The connection diagram is:
19

C0240111-04-05-GB
SHIELDED
TWISTED
Figure 3.6: connecting the remote keyboard (for distances between 200 and 500 metres)
20
Other manuals for W3000 compact
1
Table of contents
Other CLIMAVENETA Thermostat manuals