CommScope SYSTIMAX 360 1100GS3 User manual

860584440
Issue 1, February 2015
www.commscope.com
SYSTIMAX 360™1100GS3 and 1100GS6
Evolve Modular Panel Instructions
© 2015 CommScope, Inc.
All rights reserved
This product is covered by one or more U.S.
patents or their foreign equivalents. For patents, see
www.commscope.com/ProductPatent/ProductPatent.aspx
Page 1 of 11
For RoHS Inquiries:
CommScope Inc.
Corke Abbey, Bray
Co. Dublin, Ireland
Attn: Legal Department
General
The SYSTIMAX 360™1100GS3 (Cat 6) and 1100GS6 (Cat 6A) Evolve modular panels exceed ISO and TIA
Performance Category standards. The performance category is identified by the color of the jacks. Jacks with
gray jack housings are Category 6A (GS6) and jacks with black jack housings are Category 6 (GS3). The
SYSTIMAX 360 1100GS3 (Cat 6) and 1100GS6 (Cat 6A) Evolve modular panels and can be used for EIA-T568A
or EIA-T568B wiring applications and are available in 24-port and 48-port flat and angled versions.
SYSTIMAX 360 InstaPATCH®fiber modules can be used in the 1100GS 24-port and 48-port flat panels when
the separately orderable Evolve fiber bezels, rear cable management bar, and front cable trough are utilized.
The 1100GS Evolve panels are available iPatch®ready. For instructions on using panels in an iPatch
application, see 860516491 iPatch®Upgrade Module Instructions for SYSTIMAX 360 Panels.
Panel kits are available unpopulated for use with separatelyordered modules.
Ordering information for modular panels is listed below:
360 GS3 Modular Panels
360 GS6 Modular Panels
Material ID
Description
Material ID
Description
760152561
1100GS3 Evolve 24-port flat panel
760152587
1100GS6 Evolve 24-port flat panel
760152579
1100GS3 Evolve 48-port flat panel
760152595
1100GS6 Evolve 48-port flat panel
760151308
1100GS3 Evolve 24-port angled panel
760151324
1100GS6 Evolve 24-port angled panel
760151753
1100GS3 Evolve 48-port angled panel
760151779
1100GS6 Evolve 48-port angled panel
Ordering information for panel kits is listed below:
360 Flat Panel Kits*
360 Angled Panel Kits*
Material ID
Description
Material ID
Description
760155739
1100GS Evolve 24-port flat panel kit
760152785
1100GS Evolve 24-port angled panel kit
760155747
1100GS Evolve 48-port flat panel kit
760152793
1100GS Evolve 48-port angled panel kit
*Modules are not included and must be ordered separately

860584440
Instruction Sheet
www.commscope.com
Page 2 of 11
SYSTIMAX 360™1100GS Evolve 24-Port Flat Panel and 24-Port Angled Panel
How to Contact Us
To find out more about CommScope® products, visit us on the web at http://www.commscope.com/
For technical assistance:
- Within the United States, contact your local account representative or technical support at
1-800-344-0223. Outside the United States, contact your local account representative or
PartnerPRO™Network Partner.
- Within the United States, report any missing/damaged parts or any other issues to
CommScope Customer Claims at 1-866-539-2795 or email to [email protected].
Outside the United States, contact your local account representative or PartnerPRO Network
Partner.
Tools Required
Phillips head screwdriver
Cable jacket scoring tool
D-914 punch tool with M110 blade
Specifications
Wire Termination
Wire Size:
22-24 AWG (0.64 - 0.51 mm) Solid Copper
22-24 AWG (0.64 - 0.51 mm) Seven Stranded Copper
Insulation Size:
0.042 inch maximum DOD
Insulation Types:
Polyethylene, Polypropylene, and FEP
IDC Reterminations:
20 minimum
Modular Jack Mating Cycles:
750 minimum
Environmental Data
Temperature Range:
-40°F (-40°C) to 158°F (70°C) (Storage)
14°F (-10°C) to 140°F (60°C) (Operational)
Humidity:
95% Noncondensing

www.commscope.com
860584440
Instruction Sheet
Page 3 of 11
Parts List
Verify parts against parts list below:
Quantity
Description
24-Port Flat
Panel
48-Port Flat
Panel
24-Port
Angled Panel
48-Port
Angled Panel
1
─
─
─
24-port flat panel
─
1
─
─
48-port flat panel
1
24-port angled panel
─
─
─
1
48-port angled panel
1
1
─
─
Front cover (1U or 2U)
─
─
1
1
Center cover (1U or 2U) angled panel
─
─
2
2
Side covers for angled panel (1U or 2U)
right and left
4
4
4
4
P12-24 x ½” mounting screws
1
2
1
2
Cable management bar
4
8
4
8
Cable management troughs
4
8
4
8
Hook-and-loop straps
1
2
1
2
Termination manager kit
4
8
4
8
Rear label, T568A wiring
1
2
1
2
Front label card (4 labels per card)
1
2
1
2
Front label cover card (4 covers per card)
1
1
1
1
Instruction sheet
Note: Panel kits include all the parts listed above with the exception of the termination manager kit(s) and T568A
wiring labels. These are provided with the separately ordered distribution modules.
Separately Orderable Items
Contact your SYSTIMAX sales representative for the latest information on the wide variety of 360 InstaPATCH®
modules that are compatible with the fiber bezel.
Distribution modules for the 360 1100GS3/1100GS6 panel kits must be ordered separately and are listed below:
Material ID
Description
760151167
360 1100GS3 Evolve distribution module 6-port kit
760151183
360 1100GS6 Evolve distribution module 6-port kit
760175877
360 1100G2 Evolve fiber bezel, 4-pack, cool grey
760175919
360 1100G2 Evolve rear cable manager
760175893
360 1100G2 Evolve 1U front cable trough
760175901
360 1100G2 Evolve 2U front cable trough
WARNING –Important Safety Instructions
When using this product, the following basic safety precautions should be followed to reduce the risk of fire,
electric shock, and injury to persons:
1. Never install communications wiring in wet locations unless it is designed for wet locations.
2. Never install this product during a lightning storm. There is a remote risk of electric shock.
3. Never touch uninsulated communication wiring or terminals unless the communication circuit has been
disconnected at the network interface.
4. Caution: All wiring that connects to this equipment must meet applicable local and national building codes
and network wiring standards for communication cable.

860584440
Instruction Sheet
www.commscope.com
Page 4 of 11
Step 1 –Mount Panel to Rack
1. Mount panel to rack using the four 12-24 mounting screws provided. After securing panel to rack, snap the
Evolve cover(s) onto the front of the panel.
Note: Verify the SYSTIMAX name is upright on the flat panel cover and on angled panel center cover
before snapping in place. These two covers can be installed upside down. Side covers on angled panel are
interchangeable and are not side specific.
Instructions for Installing Copper Components in Panel (See Page 7 for
Installing Fiber Components)
Step 2 –Populate Panel with Distribution Modules (For Panel Kits Only)
Note: Distribution modules are ordered separately.
1. From the rear side of the panel, insert the front face of the module into the desired panel opening. Press
firmly until both the left and right side module snaps fully engage with the panel. When installing modules in
either of the two end positions, it is necessary to engage the outermost snap first.
Step 3 –Terminate Conductors on Rear of Panel
T568 Wiring Diagram Termination Manager
Note: The module comes with a T568B wiring designation label installed. If T568A wiring is desired, first
remove the "B" type label and then place the "A" type label. Do not place the "A" type label on top of the "B"
type label.
8 7 6 5
2 1 4 3
4 4
3
2
1
2
3
1
B A
1 2 3 4 5 6 7 8 BR BR
GR
GR
OR
OR
BL BL
W
WW
W
T568 Wiring Pairs
IDC Connector
Modular Jack
Front of Panel Back of Panel
Locktab
(2 places)
Entry
holes
Fold slots
(4 places)
Entryholes

www.commscope.com
860584440
Instruction Sheet
Page 5 of 11
Note: If using SYSTIMAX GigaSPEED®X10D 91B series cable, 95B series cordage, or Xpress®88 series
cable, see preparation instructions below.
Note: See pages 10 and 11 for proper use of the termination manager.
1. Prepare cable for IDC termination. Terminate conductors on the IDC terminals per the wiring diagram shown
above and utilizing the termination manager.
Preparation of X10D 91B Series Cable, 95B Series Cordage, or Xpress 88 Cable
for Termination
Preparation of the SYSTIMAX GigaSPEED X10D 91B series cable, 95B series cordage, or Xpress 88 series
cable is shown above. For complete instructions on preparing these cables for termination, see instruction
sheet 860469402.
Step 4 –Assemble and Install Rear Cable Manager
1. Attach the four cable troughs onto bar as shown and insert four hook-and-loop straps into slots in cable
troughs.
Pull flute and tapes
offto one or more sides
Unwind separator tape
Pull off to the side so that it can
be trimmed close to the jacket

860584440
Instruction Sheet
www.commscope.com
Page 6 of 11
2. Attach cable bar to rear of panel. For 48-port panels, two cable bars are provided.
3. Lay cables evenly in cable troughs and secure using hook-and-loop straps as shown.
Step 5 –Install Front Labels and Label Covers
1. Print the port designations on the white label cards provided. Slide labels and label covers into the label
holders from either end. Each label holder will accommodate labels up to .265 inches (6.7mm) high x 3.50
inches (89mm) wide.
2. Blank, voice, and data icons can be ordered separately in a wide variety of colors and placed into the
pockets in the lower portion of the label holders.
Note: Product code M61K-XX (blank, voice, and data icons) to be ordered separately. XX denotes the color
abbreviation.

www.commscope.com
860584440
Instruction Sheet
Page 7 of 11
3. To print a designation label, go to http://www.commscope.com/Resources/Labeling-Templates and scroll
down to 360 Panels and Shelves. Select the proper label template:
360 Evolve-360 PATCHMAX UNP Label Sheet A4 (760186502)
or
360 Evolve 360 PATCHMAX UNP Label Sheet US LTR (760183244).
Note: Labeling website has two options for printing labels; letter size and A4 size.
Instructions for Installing Fiber Components in Panel
Step 2a –Install Evolve Fiber Adapter Bezels
Note: Fiber modules, bezels, rear trunk cable management bar, and front fiber management trough are ordered
separately.
1. Position a bezel against opening from rear of panel. Push bezel from the rear until it snaps into panel
opening. Repeat for all bezels.
Step 3a –Install Evolve G2 Fiber Trunk Cable Management Bar on Rear of Panel
1. Attach fiber management bar to rear of panel immediately behind the fiber row. Place hook at both ends of
bar into slots in panel brackets as shown.
Step 4a –Install Evolve G2 Fiber Management Trough on Front of Panel
Note: For instructions on installing the fiber management trough, see 860548809 SYSTIMAX 360 1100
Evolve G2 Fiber Management Trough.
1. Refer to the instructions packaged with the trough and install either the 1U trough on front of the 24-port
panel or the 2U trough on front of the 48-port panel.
2. Refer to the instructions packaged with the trough and install designation labels on trough door.

860584440
Instruction Sheet
www.commscope.com
Page 8 of 11
Step 5a –Populate Panel with Fiber Modules
1. Orient module in ALPHA or BETA position as required and insert into one of the openings in the panel.
2. Push module into opening until latches engage with an audible click.
3. Repeat for remaining modules.
Step 6a –Install and Route Fiber Trunk Cables
1. Terminate MPO connectors into modules.
2. Slip fiber routing clips over fiber management bar at equally spaced positions, similar to as shown above.
3. Spread open a slot position provided on fiber routing clip and secure fiber cable inside.
4. Repeat until all cables are inserted in the clips and adjust position of clips as necessary to hold the trunk
cables in an organized manner.
5. Wrap a strip of hook-and-loop fastener around each fiber routing clip to secure cables.
Fiber
management
system
Fiber routing clips
Fiber trunk cables
(not supplied)
Fiber module
(not supplied)
Hook and loop strip
MPO connector

www.commscope.com
860584440
Instruction Sheet
Page 9 of 11
(Optional Step) Removing Covers from Panel
1. When removing either the flat or angled panel side cover(s), grip cover on the top and bottom at the
outside edge where shown by arrows and pull forward. As cover tabs release, position fingers close to
tabs to apply further pulling force.
2. For angled panel only, remove both side covers from panel before removing center cover.

860584440
Instruction Sheet
www.commscope.com
Page 10 of 11
1 Patch Panel Termination Manager Instructions
The termination managers provide pair positioning, control,
and strain relief features to the rear termination area of the
panel. See Figure 1. Instructions for using the termination
manager are listed below.
Feed Pairs into Termination Manager (Figure 2)
1. Trim jacket back at least 3 inches (76mm) to expose
twisted pairs.
2. Without crossing over or rearranging pairs out of
the jacket, position pairs in-line per pair colors below:
T568B Wiring Application (Shown)
Blue, Brown, Orange, Green
T568A Wiring Application
Blue, Brown, Green, Orange
3. Insert pairs through 4 holes on top surface of termination
manager, one pair per hole, as shown.
4. Continue to feed pairs through termination manager until
resistance is encountered at the jacket. This will usually be
about 1/4 inch (6mm) from the jacket.
Fold Pairs into Slots (Figure 3)
5. Fold each pair over into adjoining slots on bottom end of
termination manager. Conductor colors must be arranged
in the slots as listed below:
T568B Wiring Application (Shown)
BL/OR Pairs –Blue/Orange conductors on top
BR/GR Pairs –both White conductors on top
T568A Wiring Application
BL/GR Pairs –Blue/Green conductors on top
BR/OR Pairs –both White conductors on top
Important: Add twist as needed to align pairs with
slots. Never remove twist for any pair. Do not allow
pairs to untwist inside termination manager or inside
cable jacket.
6. Ensure that both conductors of each pair are in slots
completely without being pinched over bottom end surface.
Figure 1. Termination Manager
Locktab
(2 places)
Entry
holes
Fold slots
(4 places)
Entryholes
Figure 2. Feed Pairs into Termination Manager
Top
surface
Orange pair
Brown pair
Blue pair Green pair
Figure 3. Fold Pairs Back into Slots
Orange on top
White on
top
Blue on top

www.commscope.com
860584440
Instruction Sheet
Page 11 of 11
Snap Termination Manager onto Rear Housing
(Figure 4)
7. Snap assembled termination manager onto rear
housing with pair colors in proper position. Push on
using the termination manager housing, not by
pushing with the cable. (Ensure that both lock tabs on
manager fully seat into rear housing).
8. After termination manager is snapped onto rear
housing, untwist individual pairs fully and line up
correct color conductor and white conductor with the
label on the rear housing.
Seat Wires into IDC Terminal Slots
(Figure 5)
9. Grasping each untwisted pair, push the conductors
down into IDC terminal slots to seat them before
punching down. Seat down into slots as far as
possible. (It may be easier to use needle nose pliers
to perform this task).
10. Using the D-914 punch tool with M110 blade on
HI impact setting, punch down conductors making
sure the tool is straight and that conductors fully
engage in the IDC terminals. Stagger the punch-down
tool up and down, so that it stays in alignment with
the staggered terminal slots.
Recommendations to Aid Assembly
1. The termination manager should be snapped onto the
rear housing immediately after the pairs have been
fed and folded over into the slots. All termination
managers should be installed on the panel before
proceeding to seat and punch down conductors.
2. Flex cables down for easier access, then seat and
punch down the entire top row of the panel.
3. Flex cables up for easier access, then seat and
punch down the entire bottom row.
2
Figure 4. Snap Termination Manager onto
Rear Housing
Pairs
folded back
Figure 5. Seat Untwisted Pairs into IDC
Terminal Slots
Visible
pair entry
Remove twists,
then push
conductors
down into
terminal slots
This manual suits for next models
1
Table of contents
Other CommScope Control Panel manuals
Popular Control Panel manuals by other brands

Honeywell
Honeywell Pro-Watch 7000 Security Manual

Danfoss
Danfoss VLT FC Series operating instructions

Simplex
Simplex MINIPLEX 4100ES Series operating instructions

Belden
Belden Miranda iMC-Panel-200 Operator's guide

WAGO
WAGO WAGO-PERSPECTO 762 Series manual

Bentel Security
Bentel Security NormaOtto Series user manual