IEI Technology MiniMax 3 Assembly instructions

IEI MiniMax 3
Installation/Programming Manual
Document Number: 6055672
Re ision: 1.0
Date: 01/23/07

Table of Contents IEI MiniMax 3 Installation/Programming Manual
Table of Contents
Section 1: System Features and Specifications........................................................ 5
1.1 System Features...........................................................................................................................5
1.2 Specifications................................................................................................................................6
1.3 System Defaults............................................................................................................................6
1.4 Max 3 Door Control Module Diagram...........................................................................................
1.5 Backplane Diagram.......................................................................................................................8
Section 2: Installation................................................................................................... 9
2.1 Check the Packing List..................................................................................................................9
2.2 Mount the Enclosure.....................................................................................................................9
2.3 Ground the Unit...........................................................................................................................10
2.4 Connect the RS-485 Cable from the Module to the Backplane..................................................11
2.5 Wire an Electric Door Lock to the Main Relay of the Max 3 Module.......................................... 12
2.5.1 Installing a Diode to Prevent Electrical Kickback from Lock – DC Locks Only................... 13
2.5.2 Installing an MOV to Prevent Electrical Kickback from Lock – AC Locks Only...................13
2.6 Connect a Secured Series Front End (SSFE) Reader to the Door Control Module...................14
2. Connect the Primary Wiegand Front End Reader (IN Reader)..................................................15
2.8 Connecting a Secondary Wiegand Front End Reader (OUT Reader)........................................16
2.9 Wire a Request to Exit (REX) device and Door Contact.............................................................1
2.10 Wire the Alarm Shunt Relay......................................................................................................18
2.11 Wire the Door Ajar Relay..........................................................................................................19
2.12 Wire the Forced Door Relay......................................................................................................20
2.13 Network the MiniMax 3..............................................................................................................21
2.13.1 Connect the MiniMax 3 Backplane Directly to a PC..........................................................21
2.13.2 Connect Multiple Backplanes Together.............................................................................22
2.13.3 Connect the SEG-M to the MiniMax 3 (LAN/WAN Connection)........................................23
2.13.4 Connecting the SEG-1 to the MiniMax 3 (LAN/WAN Connection)....................................24
2.14 Installing a Tamper Switch........................................................................................................25
2.15 Complete Connections Between the 16.5 VAC Transformer and Backplane.......................... 26
2.16 Power up the System................................................................................................................2
Section 3: Programming............................................................................................ 28
3.1 Programming Methods................................................................................................................28
3.2 Entering Program Mode and Changing the Master Code...........................................................29
3.2.1 Entering Program Mode.......................................................................................................29
3.2.2 Changing the Master Code..................................................................................................29
3.2.3 Programming a Supervisor Code........................................................................................29
3.3 Changing the Door Number........................................................................................................30
3.4 Changing the Main Relay Time...................................................................................................30
3.5 Setting the Time and Date..........................................................................................................30
3.6 Programming Users....................................................................................................................31
3.6.1 User Types...........................................................................................................................31
3.6.2 Programming a “Code Only” User.......................................................................................32
3.6.3 Programming “Card Only” Users by Presentation..............................................................32
3.6.4 Programming 26-Bit “Card Only” Users without Presentation.............................................32
3.6.5 Programming “Code AND Card” Users...............................................................................33
3.6.6 Programming “Code or Card” Users....................................................................................33
3.6. Programming 26-Bit “Card Only” Users via Batch Entry without Presentation................... 33
Page 2 of 48 Document #: 6055672, Re 1.0 D1c

IEI MiniMax 3 Installation/Programming Manual Table of Contents
3.6.8 Programming Consecutive “Card Only” Users via Batch Entry by Presentation................ 34
3.6.9 Command 50 Quick Program Feature - “Code Only” or “Card Only”..................................34
3. Deleting Users.............................................................................................................................35
3. .1 Delete a Single User............................................................................................................35
3. .2 Delete a Block of Users.......................................................................................................35
3.8 Programming Extended Unlock Time.........................................................................................36
3.9 Programming Facility Code.........................................................................................................36
3.10 Programming User Lockout......................................................................................................36
3.11 Programming the Door Ajar Output Time.................................................................................3
3.12 Programming the Forced Door Time........................................................................................3
3.13 Using the Default Auto-Unlock Timezone.................................................................................38
3.13.1 Enable/Disable Timezones................................................................................................38
3.13.2 Enable/Disable Auto-Unlock..............................................................................................38
3.13.3 Enable/Disable First-In Auto-Unlock..................................................................................38
3.14 Programming Error Lockout......................................................................................................39
3.14.1 Setting the Error Lockout Threshold..................................................................................39
3.14.2 Setting the Error Lockout Duration....................................................................................39
3.15 Programming Wiegand LED Active State.................................................................................39
3.16 Programming Wiegand Sounder Active State..........................................................................40
3.1 Enable/Disable Control Module Audio Indicators..................................................................... 40
3.18 Reseting System Defaults and Erasing Memory......................................................................41
3.18.1 Resetting the Master Code and System Defaults Only.....................................................41
3.18.2 Erasing Entire Memory/Resetting System Defaults.......................................................... 41
3.18.3 Erasing the Transaction Event Log...................................................................................41
3.19 Programming Daylight Savings Time........................................................................................42
3.19.1 Enabling/Disabling Daylight Savings Time........................................................................42
3.19.2 Selecting Daylight Savings Time Format...........................................................................42
3.20 Programming Options Chart.....................................................................................................43
Section 4: Troubleshooting........................................................................................ 46
4.1 Troubleshooting Chart.................................................................................................................46
4.2 Keypad Self-Test.........................................................................................................................46
4.3 Front End Error Indicators...........................................................................................................46
4.4 Lithium Battery Replacement......................................................................................................4
Document #: 6055672, Re 1.0 D1c Page 3 of 48

List of Tables and Illustrations IEI MiniMax 3 Installation/Programming Manual
List of Tables
Table 1: System Features.......................................................................................................................5
Table 2: Specifications.............................................................................................................................6
Table 3: System Defaults........................................................................................................................6
Table 4: User Types..............................................................................................................................31
Table 5: Control Module Audio Indicators.............................................................................................40
Table 6: Programming Options Chart....................................................................................................43
Table : Troubleshooting Chart.............................................................................................................46
Table 8: Front End Error Indicators.......................................................................................................46
List of Illustrations
Figure 1: Max 3 Module Diagram............................................................................................................
Figure 2: MiniMax 3 Backplane Diagram................................................................................................8
Figure 3: Connecting the GND Terminal from Transformer to the Backplane......................................10
Figure 4: RS-485 Connection from Max 3 Module to Backplane..........................................................11
Figure 5: Connecting Diode Across Strike............................................................................................13
Figure 6: Connecting Diode Across Maglock........................................................................................13
Figure : Connecting MOV Across Strike..............................................................................................13
Figure 8: Connect Secured Series Front End to DCM..........................................................................14
Figure 9: Connect Primary Wiegand Front End Reader to DCM..........................................................15
Figure 10: Connect Secondary Wiegand Front End Reader to DCM...................................................16
Figure 11: Wiring a REX Switch and Door Contacts.............................................................................1
Figure 12: Wiring the Alarm Shunt Relay..............................................................................................18
Figure 13: Wiring the Door Ajar Relay...................................................................................................19
Figure 14: Wiring the Forced Door Relay..............................................................................................20
Figure 15: Wiring MiniMax 3 Backplane to a PC...................................................................................21
Figure 16: Connecting Multiple Backplanes Together.......................................................................... 22
Figure 1 : Connecting the SEG-M to the MiniMax 3.............................................................................23
Figure 18: Connecting the SEG-1 to the MiniMax 3..............................................................................24
Figure 19: Installing a Tamper Switch...................................................................................................25
Figure 20: Completing the Transformer Connections...........................................................................26
Figure 21: Plug on Detachable Keypad.................................................................................................28
Page 4 of 48 Document #: 6055672, Re 1.0 D1c

IEI MiniMax 3 Installation/Programming Manual Section 1: System Features and Specifications
Section 1: System Features and Specifications
The following section outlines the MiniMax 3 features, specifications and default settings.
1.1 System Features
Table 1: System Features
Feature Description/Details
Users 2000
Base Capacity Supports Max 3 Module; Controls Door
Additional Capability Network up to 64 doors with additional Max 3 modules
Communication Type RS-485 Network; Connect via RS-232 to RS-485 Converter, USB to RS485 Converter
or LAN connection using SEG-M or SEG- .
Audit Trail *2000 Event Transaction Log
Front End Support Each Max 3 Module supports either two Wiegand or Secured Series front End readers
for IN/OUT operation.
Programming Max 3 Module supports keypad or PC programming
Auto-Unlock Time Zones
9:00 A.M. to 5:00 P.M. Monday-Friday
*Eight user definable time zones for auto-unlock or access control
*32 single day or block holidays
First-In Auto-Unlock Requires valid entry to initiate auto-unlock schedule.
Forced Door Alarm Relay/Timer
Alarm Zone Shunting Relay
Timed Egress Input
Non-Volatile EEPROM Memory
* Indicates feature available with PC software only.
Document #: 6055672, Re 1.0 D1c Page 5 of 48

Section 1: System Features and Specifications IEI MiniMax 3 Installation/Programming Manual
1.2 Specifications
The following table lists the Electrical, mechanical and environmental specifications.
Table 2: Specifications
Electrical
Power Supply 6.5VAC 40VA or 50VA Class 2 Transformer (Revere # RT-G 640SL/M, Revere #
RT-G 650SL/M or Globtek, Inc. # DA-40- 6.5G)
Current Requirements 0mA (backplane with module)
Front End 3.8 VDC, 300 mA (max. current draw)
Lock Output 3.8VDC or 6.5VAC, 600mA (max. current draw)
Aux 3.8VDC, 00mA (max. current draw)
Main Relay 2-24 VAC/DC, 2A (max. contact current)
Alarm Shunt, Door Ajar
and Forced Door Relays 2-24VAC/DC, A (max. contact current)
REX/Door Loop Dry contact closure
Wiring equirements
RS-485 Cable 24AWG, shielded, two twisted-pair telephone cable with a shunt capacitance of 6
pF/Ft (required only when using software)
Front End Cable Stranded wire with overall foil shield.
REX/Door Loop Cable Stranded wire with overall foil shield.
Mechanical
Enclosure Surface mount
Height 3.56” (9.04cm)
Width .29” (28.67 cm)
Length .3 ” (28.7 cm)
Material 9 gauge steel
Environmental
Temperature Tolerance -20°F to 30°F (-28°C to 54°C)
Recommended Use For indoor use only
1.3 System Defaults
The following table lists the default settings for the Max 3 Door Control Module.
Table 3: System Defaults
Option Default Setting Option Default Setting
Master Code 234 Main Relay Time 5 Seconds
Door Ajar Output Time 30 Seconds Forced Door Output Time 0 Seconds
Audio Keypress Feedback Enabled Visual Keypress Feedback Enabled
User Lockout Enabled User Lockout Type By Location
Time Zones Disabled Auto-Unlock Disabled
First-In Auto-Unlock Disabled User Timezone 24 Hours
Daylight Savings Time Enabled DST Format US
Wiegand LED State Active Low Wiegand Sounder State Active Low
Error Lockout Threshold 3 Attempts Error Lockout Duration 0 Seconds
Extended Unlock Time 0 Seconds Facility Code
Door Number Auto-Unlock Time Zone
(Without software)
9 A.M to 5 P.M.; Monday
through Friday
Page 6 of 48 Document #: 6055672, Re 1.0 D1c

IEI MiniMax 3 Installation/Programming Manual Section 1: System Features and Specifications
1.4 Max 3 Door Control Module Diagram
The diagram below shows the component locations and terminal connections on the Max 3 Door Control Module.
Document #: 6055672, Re 1.0 D1c Page 7 of 48
Figure 1: Max 3 Module Diagram
Communication LEDs
RX = Receive Data
TX = Transmit Data

Section 1: System Features and Specifications IEI MiniMax 3 Installation/Programming Manual
1.5 Backplane Diagram
The diagram below shows the component locations and terminal connections on the Backplane.
Notes:
The Max 3 communicates to the PC via an RS-485 connection. For this connection use TS3 on the far right, bottom of the backplane.
The module is then connected to the backplane via connector P .
Port C is used for configuring the SEG-M, when it's plugged onto J2 on the backplane.
Page 8 of 48 Document #: 6055672, Re 1.0 D1c
Figure 2: MiniMax 3 Backplane Diagram

IEI MiniMax 3 Installation/Programming Manual Section 2: Installation
Section 2: Installation
This section contains detailed procedures and wiring diagrams for installing the IEI MiniMax 3 Access Control System. This section is
presented in the order you should follow to install the unit. Not every section is necessary for every application.
The system must be installed within the protected area in accordance with the National Electrical Code (NFPA 70), local codes, and
the authority having jurisdiction. It should also be located in an area that is accessible for programming purposes. After the installation
is complete, the cabinet door should remain closed and locked to protect the contents.
Note: Programming commands are inserted into the installation procedures for your convenience. Programming should only be done
after all electrical connections are made and the system is powered up.
2.1 Check the Packing List
Open the box and inside is a metal enclosure. The metal enclosure has a removable lid, to give you easier access when wiring. Inside
the metal enclosure is:
•1 Backplane mounted on standoffs
•1 6.5VAC Transformer
•1 Camlock with key
•1 Hardware Pack containing:
•1 Wire nuts (ORANGE)
•4 Wall anchors (BLUE)
•4 #8 ¼” sheet metal screws
•1 Set of battery cables (BLACK AND RED)
•1 Ground cables (BLACK wire with RED flush tab receptacle)
•1 Max 3 Module
•1 detachable keypad for programming (Pre-mounted to Max 3 Module)
•1 Secured Series Software Package
•1 MiniMax 3 Installation and Programming Manual
Please check the contents of the enclosure and verify all components on the packing list are present. Taking this inventory will
familiarize you with the components as well as ensure you have a complete kit.
2.2 Mount the Enclosure
The enclosure is designed to be wall mounted (surface mounted) using the supplied hardware. You must mount the enclosure on the
secure side of the door in a secured area such as a locked utility closet. Make sure it is accessible for programming and maintenance
purposes. Do not use the controller as access device to enter or exit through the door.
Mounting Procedure:
Unlock and open the metal enclosure. Notice that the enclosure lid opens from top to bottom so the enclosure lid forms a tabletop for a
convenient workspace.
. Use the supplied wall anchors and sheet metal screws to secure the enclosure to the wall.
2. Drill /64’’ diameter holes for the wall anchors.
3. Tap the wall anchors into the wall until the outer flange is flush to the wall surface.
4. Insert the sheet-metal screws ¾ of the way into the anchors.
5. Hang the enclosure by aligning the slotted holes (cut into the rear of the cabinet) with the sheet-metal screws. Space between
slotted holes; on-center 9 /6” Horizontally and 0 /8” Vertically.
6. The enclosure should now be resting on the sheet-metal screws.
7. Tighten the sheet-metal screws until they are snug.
Document #: 6055672, Re 1.0 D1c Page 9 of 48
Note: MiniMax 3 System Kit contains additional components including proximity reader.

Section 2: Installation IEI MiniMax 3 Installation/Programming Manual
2.3 Ground the Unit
Grounding the system before making any electrical connections is imperative!
By grounding the system first you not only increase personal safety during installation, but you also protect the unit from damage due
to static discharge or any other transient voltage effects. We cannot stress enough the importance of completely grounding the unit
before making any connections or even touching the backplane (the large circuit board in the enclosure). Wire as shown and plug the
transformer into a grounded electrical socket.
Page 10 of 48 Document #: 6055672, Re 1.0 D1c
Do not make any AC
Power connections
until Step 13 of the
installation.
TOUCH THE GROUNDED METAL CABINET BEFORE TOUCHING THE BACKPLANE OR
THE MAX 3 DOOR CONTROL MODULE. THIS WILL REMOVE ANY STATIC CHARGE ON
YOUR PERSON. STATIC ELECTRICITY CAN DAMAGE THE ELECTRONIC COMPONENTS
USED ON THE CONTROLLERS.
Figure 3: Connecting the GND Terminal from Transformer to the Backplane

IEI MiniMax 3 Installation/Programming Manual Section 2: Installation
2.4 Connect the RS-485 Cable from the Module to the Backplane
The Max 3 Door Control Module requires an additional three position cable to make the RS-485 connection to the backplane. This
cable is connected from P5 on the upper right corner of the module to the three position connector underneath the module on the top
right of the backplane labeled P . Simply plug one end of the cable into P5 and the other end into P on the backplane. The diagram
below illustrates how to connect the module to the backplane.
Document #: 6055672, Re 1.0 D1c Page 11 of 48
Figure 4: RS-485 Connection from Max 3 Module to Backplane

Section 2: Installation IEI MiniMax 3 Installation/Programming Manual
2.5 Wire an Electric Door Lock to the Main Relay of the Max 3 Module
The locking device is connected to terminal strip TS as shown in
the diagram on the right. The two diagrams below show how to
connect both a Maglock and an Electric Strike using an external
power supply.
For either locking device, positive voltage (V+) from an external
power source is connected to the relay common terminal (C).
When using a Maglock, connect the lock's positive side to the
normally closed (NC) terminal and the negative side to negative on
your power supply. When using an Electric Strike, connect the
lock's positive side to the normally open (NO) terminal and the
negative side to negative on your power supply.
Connecting a Maglock (Fail-Safe) Connecting an Electric Strike (Fail-Secure)
Programming the Main Relay Time:
The command sequence below is used to change the Main Relay time. The default value is 5 seconds.
Action Press
Enter Program Mode 99 # Master Code *
Program Main Relay Time # time # 0 # **
(time = to 99 seconds)
Exit Program Mode *
Page 12 of 48 Document #: 6055672, Re 1.0 D1c
NOTES:
You must use an external power supply to power your
lock.
The relay is a FO M C D Y CONTACT, which
means there is no output voltage on the relay contacts.
When using AC voltage, polarity does not matter.

IEI MiniMax 3 Installation/Programming Manual Section 2: Installation
2.5.1 Installing a Diode to Pre ent Electrical Kickback from Lock – DC Locks Only
If your electric locking device does not come pre-installed with internal protection for electrical “kickback voltage” use the supplied
N4004 diode for DC locks only. This “kickback voltage” could possibly damage the Max 3 control module and installing the diode
could help prevent this from happening. When installing the diode, connect it across the positive (V+) and negative (V-) of your
locking device. The diode is polarized, which means the cathode mark (silver band at one end) must be connected to the positive
connection as shown below. You must connect the diode as close as possible to the locking device for it to work properly.
2.5.2 Installing an MOV to Pre ent Electrical Kickback from Lock – AC Locks Only
If your electric locking device does not come pre-installed with internal protection for electrical “kickback voltage” use the supplied
MOV for AC locks only. This “kickback voltage” could possibly damage the Max 3 control module and installing the MOV could
help prevent this from happening. When installing the MOV, connect it across the AC connection to your locking device. This device
is not polarized so it does not matter which direction you install it. You must connect the MOV as close as possible to the locking
device for it to work properly.
Document #: 6055672, Re 1.0 D1c Page 13 of 48
Figure 6: Connecting Diode
Across Maglock
Figure 5: Connecting Diode Across Strike
Figure 7: Connecting MOV Across
Strike

Section 2: Installation IEI MiniMax 3 Installation/Programming Manual
2.6 Connect a Secured Series Front End (SSFE) Reader to the Door Control
Module
The Max 3 supports IEI Secured Series Front Ends, which include keypads, card readers and touch chip readers. These are connected
to to the Front End terminal strip TS5. You can connect up to two readers to each Door Control Module, for In/Out operation by
simply wiring them in parallel (both readers to the same four screw terminals). Each screw terminal is labeled with a wire color (black,
red, white/black and white yellow). These correspond to the color wire on the wire harness supplied with the front end reader.
You must use a four-conductor stranded cable with overall foil shield to connect the Front End to the Door Control Module. You also
must terminate the drain wire (the bare wire inside the foil shield), from the front end cable, to the fast-tab located on the Max 3
Backplane. There is a fast-tab located under each module on the lower edge of the backplane. They are labeled FT , FT2, FT3 and
FT4. Connect the drain wire from the front ends connected to module one to FT and so on. IEI has included four ground cables and
wire-nuts to make this connection. Do not terminate the drain wire at the Front End eader. Cut off the exposed drain wire and
wrap the insulation and the foil shield in electrical tape.
Page 14 of 48 Document #: 6055672, Re 1.0 D1c
Note: The Max 3 Door Control Module must be configured to operate in Secured
Series Front End Mode. To do this, locate jumper JP2 above terminal strip TS7 and
place the jumper on both pins.
Wire Size vs. Cable Length Chart
Distance Wire Size
250 Feet 22 AWG
500 Feet 20 AWG
000 Feet 8 AWG
Note: If you experience problems with
front end communications after connecting
a second keypad or reader, wiring a
separate ground wire from each keypad to
the black terminal on the Max 3 DCM may
solve the issue. If this does not fix the
problem contact IEI Technical Support.
Figure 8: Connect Secured Series Front End to DCM

IEI MiniMax 3 Installation/Programming Manual Section 2: Installation
2.7 Connect the Primary Wiegand Front End Reader (IN Reader)
Wiegand readers are connected directly to the Front End Terminals on the Door Control Module. The primary reader (IN) should be
mounted on the exterior of the door and used to gain access into the secured area. The diagram and table below describe the
connections in detail. Please note that the Primary Wiegand Reader Data 0 wire is connected to DO PRI (Data 0 Primary) on terminal
strip TS5.
The LED connection is used to indicate status of the Main Relay and the Sounder connection is used to indicate various error
conditions. These are explained in more details in later sections.
You must use a four to six conductor stranded cable with overall foil shield to connect the Front End to the Door Control Module. You
also must terminate the drain wire (the bare wire inside the foil shield), from the front end cable, to the fast-tab located on the Max 3
Backplane. There is a fast-tab located under each module on the lower edge of the backplane. They are labeled FT , FT2, FT3 and
FT4. Connect the drain wire from the front ends connected to module one to FT and so on. IEI has included four ground cables and
wire-nuts to make this connection. Do not terminate the drain wire at the Front End eader. Cut off the exposed drain wire and
wrap the insulation and the foil shield in electrical tape.
Document #: 6055672, Re 1.0 D1c Page 15 of 48
IMPO TANT: The Max 3 Door Control Module must be configured to
operate in Wiegand Front End Mode. To do this, locate jumper JP2 above
terminal strip TS7 and place the jumper on one pin. This is the default
condition.
Primary Wiegand eader Connections
Wiegand eader DCM Terminal Strip
V- (Power) Black TS5
V+ (Power) RED TS5
Data 0 D0 PRI TS5
Data D TS5
LED Control LED TS7
Sounder Control SND TS7
Note: The primary reader
records an IN event in the
transaction log.
Figure 9: Connect Primary Wiegand Front End
Reader to DCM

Section 2: Installation IEI MiniMax 3 Installation/Programming Manual
2.8 Connecting a Secondary Wiegand Front End Reader (OUT Reader)
The diagram below shows how to connect a secondary (out) reader to the Door Control Module. The secondary reader (OUT) should
be mounted on the interior side of the door and used to exit the secured area. Please note that the Secondary Wiegand Reader Data 0
wire is connected to DO SEC (Data 0 Secondary) on terminal strip TS7.
The LED connection is used to indicate status of the Main Relay and the Sounder connection is used to indicate various error
conditions. These are explained in more details in later sections.
You must use a four to six conductor stranded cable with overall foil shield to connect the Front End to the Door Control Module. You
also must terminate the drain wire (the bare wire inside the foil shield), from the front end cable, to the fast-tab located on the Max 3
Backplane. There is a fast-tab located under each module on the lower edge of the backplane. They are labeled FT , FT2, FT3 and
FT4. Connect the drain wire from the front ends connected to module one to FT and so on. IEI has included four ground cables and
wire-nuts to make this connection. Do not terminate the drain wire at the Front End eader. Cut off the exposed drain wire and
wrap the insulation and the foil shield in electrical tape.
Page 16 of 48 Document #: 6055672, Re 1.0 D1c
Note: The secondary reader
records an OUT event in the
transaction log.
IMPO TANT: The Max 3 Door Control Module must be configured to
operate in Wiegand Front End Mode. To do this, locate jumper JP2 above
terminal strip TS7 and place the jumper on one pin. This is the default
condition.
Figure 10: Connect Secondary Wiegand Front End
Reader to DCM
Secondary Wiegand eader Connections
Wiegand eader DCM Terminal Strip
V- (Power) Black TS5
V+ (Power) RED TS5
Data 0 D0 SEC TS7
Data D TS5
LED Control LED TS7
Sounder Control SND TS7

IEI MiniMax 3 Installation/Programming Manual Section 2: Installation
2.9 Wire a Request to Exit (REX) de ice and Door Contact
equest to Exit ( EX) This is a normally open loop, when momentarily closed activates the Main Relay for the
length of time programmed in the Main Relay Time (command ).
Door Switch Input This is a normally closed loop that tells the Max 3 the door status. This is used for the Door
Ajar, Forced Door and Auto-Relock features.
Auto-Relock
Auto Re-lock refers to the feature that automatically locks the door one second after the door contact switch is opened. This allows
you to program a long unlock time, when required, without worrying about the door remaining open after the person has entered. No
programming is necessary for this feature, but it does require you connect a door contact switch as shown in the diagram above.
Remember you must remove jumper JP1 for the door contact input to operate.
Document #: 6055672, Re 1.0 D1c Page 17 of 48
Figure 11: Wiring a REX Switch and Door Contacts
Note: Use stranded wire with
overall foil shield for the
REX and Door Contact
cables. Connect the drain
with to the fast-tab on the
backplane.

Section 2: Installation IEI MiniMax 3 Installation/Programming Manual
2.10 Wire the Alarm Shunt Relay
The Alarm Shunt Relay is used when you are controlling access to a door that is monitored by an external alarm system. This relay
activates at the same time as the Main Relay (by either a valid code/card or REX) so you can bypass the existing alarm panel, as
shown in the diagram below. For this feature you must wire dedicated door contact to terminals TS6 (door contact switch input) as
shown below. The Alarm Shunt Relay remains energized until one second after the door contact switch input is closed. Remember you
must remove jumper JP1 for the door contact input to operate.
Page 18 of 48 Document #: 6055672, Re 1.0 D1c
Figure 12: Wiring the Alarm Shunt Relay

IEI MiniMax 3 Installation/Programming Manual Section 2: Installation
2.11 Wire the Door Ajar Relay
The Door Ajar Relay output alerts personnel that the door is being held, or propped open, after a valid access or REX. For this feature
to operate you must wire a dedicated door contact switch to the door terminals on TS6 (door contact switch input) as shown below.
Once the door contact switch input is opened, the Door Ajar timer begins. When the time reaches the time programmed in the Door
Ajar Time (command 44), the relay energizes and remains energized until the door contacts are closed. Remember you must remove
jumper JP1 for the door contact input to operate.
The diagram below shows how switch positive power (V+) to an alarm device. The Relay is rated to handle Amp of current at either
2 or 24 Volts AC/DC. Alarm device(s) are not included with IEI equipment.
Programming the Door Ajar Time:
The command sequence belows shows how to program the Door Ajar Time. The default value is 30 seconds.
Action Press
Enter Program Mode 99 # Master Code *
Program Door Ajar Time 44 # time # 0 # **
(time = 0 to 990 seconds)
Exit Program Mode *
Document #: 6055672, Re 1.0 D1c Page 19 of 48
Figure 13: Wiring the Door Ajar Relay

Section 2: Installation IEI MiniMax 3 Installation/Programming Manual
2.12 Wire the Forced Door Relay
The Forced Door Relay Output alerts personnel that the door was opened without authorization. For this feature to operate you must
wire a dedicated door contact switch to the door terminals on TS6 (door contact switch input) as shown below. Remember you must
remove jumper JP1 for the door contact input to operate. If these door contacts are opened without a valid access or REX, the Forced
Door Relay energizes immediately. It remains energized until either a valid code is entered or card presented to the Front End Reader,
a valid code is entered on the Max 3 Module or the Forced Time (command 45) expires.
The diagram below shows how to switch positive power (V+) to an alarm device. The Relay is rated to handle Amp of current at
either 2 or 24 Volts AC/DC. Alarm device(s) are not included with IEI equipment.
Programming the Forced Door Time:
The command sequence belows shows how to program the Forced Door Time. The default value is 0 seconds.
Action Press
Enter Program Mode 99 # Master Code *
Program Forced Door Time 45 # time # 0 # **
(time = 0 to 990 seconds)
Exit Program Mode *
Page 20 of 48 Document #: 6055672, Re 1.0 D1c
Figure 14: Wiring the Forced Door Relay
Table of contents
Popular Control Panel manuals by other brands

NAPCO
NAPCO Gemini GEM-P9600 Programming instructions

Philips
Philips RSAT 2 Customer's manual

Menvier Security
Menvier Security TS790+ Installation and programming manual

Bosch
Bosch D9412GV2 troubleshooting guide

Risco
Risco GardTec 350+ installation instructions

Haes
Haes FUSION 0832-CPD-1431 quick start guide

Trikdis
Trikdis FLEXi SP3 user manual

Geberit
Geberit 147044001 user manual

Honeywell
Honeywell Notifier ST.PL4+ Installation and user manual

RIB
RIB KS2 manual

Global Fire
Global Fire Gekko Installation & commissioning manual

Paradox Hellas S.A.
Paradox Hellas S.A. DEVELOPED Neon 2 Installation and operation manual