
Installation and Wiring
5
2.4 Power Connections
Standard units are powered by either 115 VAC or 230
VAC volts or by optional battery pack units.
2.4.1 AC Units
Units are powered by standard AC power. The AC
power cord must be plugged into a 3-prong polarized
AC wall socket.
VAC Conversion
The UMC222 can be converted from 115VAC to
230VAC. The following steps are necessary to
complete this conversion.
Before beginning, disconnect the
AC power source. Failure to do so
can result in injury or death.
1. Disconnect the power source from the unit.
2. Remove rear outer case of the UMC222.
3. Remove rear connector bracket and four
standoffs.
4. Remove the CPU board.
5. Remove the protective insulator panel from the
solder side of the CPU board.
6. Cut circuit traces between E3/E4 and E5/E6 as
indicated with a sharp instrument like a razor
blade or an x-acto knife. Refer to Figure 2-2.
Figure 2-2. Circuit Trace Setup
7. Add jumper, E4 to E6 using a properly insulated
wire with a minimum size of #22 AWG.
8. Replace the protective insulator panel.
9. Reassemble the unit, test, and label unit for
230VAC.
10. Change the power cord.
2.5 Board Removal
If you must remove the UMC222 CPU board, use the
following procedure:
1. Disconnect power to the indicator. Loosen cord
grips and remove enclosure as described in
Section 2.2.
2. Unplug all connections to the CPU board. See
Figure 2-1 on page 4 for connector locations.
3. Remove the four nuts from the corners of the
CPU board.
4. Remove the CPU board from the enclosure.
To replace the CPU board, reverse the above procedure.
Be sure to reinstall cable ties to secure all cables inside
the indicator enclosure. Replace enclosure and torque
screws.
2.6 Replacement Parts
Table 2-2 lists the replacement parts for the UMC222.
2.7 Instrument Setup
The UMC222 operates with the EPROM program
KDK 1921. To verify the program installed in the
indicator, turn on the indicator and observe the
displayed value at the EP prompt (see Figure 2-3). The
EP prompt displays the family, set, and version level of
the installed EPROM.
Figure 2-3. EPROM Display
To ensure that the UMC222 is in proper operating
condition, the indicator can be tested with a load cell
simulator. The input signal should be as close as
possible to the normal system millivolt value.
Figure 2-5 on page 6 shows the simulator-to-indicator
wiring connection in a six-wire configuration. See
Section 2.8 for more information.
NOTE:
Six-wire configuration requires that the +SEN
lead be shorted to +EXC and the –SEN lead be shorted
to –EXC at the simulator only.
Warning
E3 E4 E6 E5
Jumper E4 to E6
Cut between
E3 and E4 Cut between
E5 and E6
Circuit Side of CPU Board
Converting from 115V AC to 220V AC
Part Number Description
56649 Thumbscrew
64983 Membrane keypad
59784 Front panel
63926 CPU board w/ EPROM
55257 Tilt stand w/ wing knobs
15337 Wing knob
64745 ESD supressor board
Table 2-2. UMC222 Replacement Parts
EP–1.12
EPROM Set 1 Version 12