HIGH PERFORMANCE UV FLAME DETECTOR
UV4SH is an high performance selected UV detector that can be
used for flame detection in gas, oil and mixed burners together
with suitable Burner Control Unit or Flame Amplifier Device.
The core component is a glass bulb filled with gas, containing
two electrodes. When appropriate voltage is applied between
electrodes, if an ultraviolet electromagnetic radiation hits the
phototube, electrons emitted by negative biased electrode can
be captured by positive biased electrode, starting an ionization
process leading an electric discharge between electrodes
producing a current flow.
UV4SH is a compact unit for industrial use, the body is made by
thermal isolating material to avoid sensor overheating when
applied on the burner head.
When the temperature at peepsight exceed 70°C it's advisable
to add a ¾” pipe spacer (up to 40 cm) between the burner and
the sensor and apply a cooling filtered air flow to the special
connection provided on the side of the probe.
Although UV4SH is blind to sunlight, some discharge lamps
produces UV emission that can be detected by the phototube.
SAFETY INFORMATION
Read and understand this manual before installing, operating, or servicing this unit. This unit must be installed
according to this manual and local regulations. The drawings may show units without covers or safety shields to
illustrate details. Disconnect power supply and follow all usual safety precautions before carrying out any operation
on the device. Be sure to reinstall covers or shields before operating any devices.
The device is not user serviceable, a faulty device must be put out of order and sent back for servicing.
CONTRIVE manufactures products used as components in a wide variety of industrial systems and equipment. The
selection and application of products remain the responsibility of the equipment manufacturer or end user.
CONTRIVE accepts no responsibility for the way its products are incorporated into the final system design. All
systems or equipment designed to incorporate a product manufactured by CONTRIVE must be supplied to the end
user with appropriate warnings and instructions as to the safe use and operation of that part.
Any warnings provided by CONTRIVE must be promptly provided to the end user.
CONTRIVE guarantees for two years from the date of manufacture of its product to replace, or, at its option, to
repair any product or part thereof (except fuses and with some limitations for tubes and photocells) which is found
defective in material or workmanship or which otherwise fails to conform to the description of its sales order.
CONTRIVE makes no warranty of merchantability or any other warranty express or implied. CONTRIVE assumes no
liability for any personal injury, property damage, losses, or claims arising from misapplication of its products.
RECEIVING
Please perform the following tasks after receiving the product:
Inspect the unit for damage. If the product appears damaged upon receipt, contact the shipper immediately.
If you have received the wrong model or the device does not function properly, contact your supplier.
Store the product in a dry place, see technical specification for temperature limit.

© 2000 CONTRIVE • B1450.EN 06172www.contrive.it
[mm]
WIRING DIAGRAM
1POSITIVE TERMINAL
USUALLY CONNECTED TO GROUND
2NEGATIVE TERMINAL
USUALLY CONNECTED TO AMPLIFIER INPUT
CONNECTION WITH REVERSED POLARITY DOES NOT DAMAGE
THE DETECTOR BUT PRODUCES NO USEFUL FLAME SIGNAL
CLASS II DEVICE
CONNECTION TO PROTECTION GROUND IS NOT REQUIRED
TECHNICAL DATA
SPECTRAL RESPONSE 185 … 260 nm
OPERATING VOLTAGE 200 … 280 VAC
DISCHARGE CURRENT 1 mA
PEAK DISCHARGE CURRENT 30 mA
RECOVERY TIME 2Oµs @ 10% DUTY CYCLE
OPERATING TEMPERATURE -20 … +90°C
UV TUBE TEMPERATURE 125°C MAX
PROTECTION CLASS IP65
OPERATING LIFE 1> 10.000 hours @ 50°C / 1mA
VIBRATION 0,5 G MAX
RELATIVE HUMIDITY NON CONDENSING 10 … 90%
MOUNTING POSITION 2 ANY 1
WEIGHT 150 g MAX
1UP TO 100.000 hours @25°C
2DO NOT INSTALL ON TOP IN VERTICAL POSITION WHEN
COMBUSTION PRODUCTS CAN FILL THE VOLUME IN FRONT
OF THE SENSOR
DIMENSIONS
THERMAL INSULATING CASE Ø 35 x 80 mm
1DIN43650 – ISO4400 CONNECTOR
2 POLES + EARTH – PG11
2DIN43650 – ISO4400 SOCKET
2 POLES + EARTH
3OPTIONAL COOLING
CONNECTION ¼“
4BURNER HEAD
CONNECTION ¾”
FRONT SIDE OF THE SENSOR IS SEALED WITH EPOXY RESIN
THERE IS NO NEED FOR ADDITIONAL QUARTZ GLASS
NOTICE
When Contrive products are combined with equipment manufactured by others and/or integrated into systems
designed or manufactured by others, the Contrive warranty pertains only to Contrive products and not to any other
equipment or to the combined system or its overall performance. Certification invalid or not applicable in such cases.

© 2000 CONTRIVE • B1450.EN 06173www.contrive.it
ANGULAR SENSITIVITY
Minimum angular sensitivity for the complete assembly, when installed without limitation on sight window.
HORIZONTAL DIRECTIVITY
VERTICAL DIRECTIVITY
ORDERING GUIDE
1450.00.00 UV4SH
UV FLAME SENSOR, COMPLETE UNIT
1450.21.00 C18211N21
SPARE CONNECTOR 2 POLE + EARTH WITH PG11 CABLE GLAND

© 2000 CONTRIVE • B1450.EN 06174www.contrive.it
SPECTRAL RESPONSE vs LIGHT SOURCES
UV4SH sensitivity is restricted to a very narrow region of ultraviolet rays, and exhibits no response at all in the visible
region. Gas and oil flames produces radiation that can be easily detected by UV4SH. The following diagram shows
spectral response of UV4SH and spectral emission for flames, sunlight and lamps.
SENSITIVITY vs SUPPLY VOLTAGE
The flame detector increase his sensitivity with higher operating voltages, the relationship is shown in the above
diagram. It's very important to keep the applied voltage within the recommended range to avoid malfunctions and
damages.
CONTRIVE S.r.l. I-24040 SUISIO (Bergamo) via Enrico Fermi 18
ANY ILLUSTRATIONS, PHOTOGRAPHS, OR EXAMPLES USED IN THIS MANUAL ARE PROVIDED AS EXAMPLES ONLY AND MAY NOT APPLY TO ALL PRODUCTS TO
WHICH THIS MANUAL IS APPLICABLE. THE PRODUCTS AND SPECIFICATIONS DESCRIBED IN THIS MANUAL OR THE CONTENT AND PRESENTATION OF THE
MANUAL MAY BE CHANGED WITHOUT NOTICE TO IMPROVE THE PRODUCT AND/OR THE MANUAL.
PRODUCT NAMES, CORPORATE NAMES, OR TITLES USED WITHIN THIS DOCUMENT MAY BE TRADEMARKS OR REGISTERED TRADEMARKS OF OTHER COMPANIES,
AND ARE MENTIONED ONLY IN AN EXPLANATORY MANNER TO THE READERS’ BENEFIT, AND WITHOUT INTENTION TO INFRINGE.
WHILE EVERY EFFORT HAS BEEN MADE TO MAKE SURE THE INFORMATION IN THIS DOCUMENT IS CORRECT, CONTRIVE CAN NOT BE LIABLE FOR ANY DAMAGES
WHATSOEVER FOR LOSS RELATING TO THIS DOCUMENT.
© COPYRIGHT 2016 CONTRIVE SRL ITALY. ALL RIGHT RESERVED.
This manual suits for next models
1
Table of contents
Popular Security Sensor manuals by other brands

dtec
dtec GJD 350 Installation & setup guide

Thermo Scientific
Thermo Scientific Dionex UltiMate 3000 Series operating instructions

Visonic
Visonic NEXT PG2 - installation instructions

Lightning Protection International
Lightning Protection International Stormaster ESE 15 installation manual

ActSafe
ActSafe PMX How to use

MegaTec
MegaTec NetFeeler 2 user manual

Steelman
Steelman ChassisEAR 06600 Operating information

3M
3M DBI-SALA ExoFit NEX Inspection Notice

PCB Piezotronics
PCB Piezotronics ICP RHM240A01 Installation and operating manual

CAME
CAME 001SIR215WL manual

B.E.G.
B.E.G. LUXOMAT PD1-M-DIM Installation and operating instruction

Olympus
Olympus EPOCH 6LT User Interface Guide