
I0050001revG.DOC ©Copyright Conveyor Components, Co. 2012 Page 5 of 6
6. Note: Typically, the motor contactor is wired in series with one of the N.O. output contacts; and an
alarm is wired with one of the N.C. output contacts.
FOR USE AS AN OVER SPEED SWITCH:
1. Select the speed range required by changing the switch to LOW for 2 to 120 PPM, MEDIUM for
20 to 1200 PPM, and HIGH for 200 to 12000 PPM.
2. Turn the set point potentiometer to the counterclockwise stop. With motion present on the input
shaft and at normal operating rpm, the yellow pulse indicator L.E.D. should blink. The green relay
indicator L.E.D. should turn on indicating that the output relay is energized.
3. Slowly turn the set point adjustment screw clockwise until the output relay de-energizes and the
green L.E.D. turns off. (A "click" will occur at this point). With the potentiometer on that setting, if
the speed increases the output relay will energize.
4. Note: Typically, the motor contactor is wired in series with one of the N.O. output contacts; and an
alarm is wired with one of the N.C. output contacts.
FOR USE AS A ZERO SPEED SWITCH:
1. Select the HIGHEST speed range by changing the switch to HIGH for 20 to 12000 PPM.
2. Turn the set point potentiometer slightly under the current running speed, as indicated by the
green LED turning on, and then adjust the potentiometer slightly under this setting. If the speed
drops below this set point, the output relay will de-energize.
3. Typically, the motor contact is wired in series with one of the N.O. output contacts, and an alarm is
wired with one of the N.C. output contacts. NOTE: very slow speeds will cause a mechanical
delay in the sensor operation, resulting in a longer time lapse before response.
4. Time delay setting
The model RMS-G motion sensing control has a start up delay that is adjustable up to 45 seconds.
This setting should be set, depending on the application and the length of time it takes for the
conveyor to reach its normal operating speed. This time delay takes effect upon power-up of the
model RMS-G after shutdown. AC power to the model RMS-G must be interrupted for timer to be
reset. This delay only affects start up, avoiding nuisance start up alarms.
Figure 3: Sensor Mounting Examples.