Cooper WaveLinx Wired SC-UN User manual

Risk of Fire, Electrical Shock, Cuts or other Casualty Hazards- Installation and maintenance of this product must be
performed by a qualied electrician. This product must be installed in accordance with the applicable installation code
by a person familiar with the construction and operation of the product and hazards involved. For continued protection
against shock hazard replace all covers and guards after eld wiring is completed.
Risk of Fire and Electric Shock- Before installing or performing any service, the power MUST be turned OFF.
All installations should be in compliance with the National Electric Code and all state and local codes.
Risk of Burn- Disconnect power and allow product to cool before handling or servicing.
Risk of Personal Injury- Due to sharp edges, handle with care.
Failure to comply with these instructions may result in death, serious bodily injury and property damage.
DISCLAIMER OF LIABILITY: Cooper Lighting Solutions assumes no liability for damages or losses of any kind that may arise
from the improper, careless, or negligent installation, handling or use of this product.
IMPORTANT: Read carefully before installing product. Retain for future reference.
NOTICE: Product may become damaged and/or unstable if not installed properly.
Note: Specications and dimensions subject to change without notice.
ATTENTION Receiving Department: Note actual product description of any shortage or noticeable damage on delivery receipt.
File claim for common carrier (LTL) directly with carrier. Claims for concealed damage must be led within 15 days of delivery.
All damaged material, complete with original packing must be retained.
NOTICE: All new wiring must be fully veried before applying power.
NOTICE: Designed for indoor installation and use only. Dry location rated.
Please Read This First
The Universal Source Controllers are designed, built and tested to strict safety regulations. By following the steps listed below and elsewhere within this
guide, you can ensure safe installation and operation of these controller units.
• The Universal Source Controllers must be installed only by a qualified electrician
• The installation must comply with the appropriate electrical codes and regulations in force in your area
• The Universal Source Controllers are designed for indoor installation and use only. The units can, however, be used to control appropriately certified
exterior lighting fixtures
• Ensure that all wiring used conforms fully to local specifications and is sufficiently rated for the installation
• All new wiring must be fully verified before applying power
• The high voltage supply should be fed to the Universal Source Controller via an external isolation breaker with sufficient capacity for the planned
installation
• All Universal Source Controllers exceed the weight limit for one person lifting - always use at least two people when lifting and mounting the units
• Do not mix load types within a single channel (e.g. 120V tungsten and low voltage ballast control)
• Ensure that the supply is fully isolated at an external breaker before removing the chassis covers. Test that power has been removed before starting
to handle conductors
• Ensure that high voltage and low voltage wiring remains separate
Important Points For Consideration
• The Universal Source Controllers must be mounted flush with the wall, do not recess the controller chassis
• Upper and lower raceways must not be located within 8 inches (200 mm) of the upper and lower panels of the Universal Source Controller. Use
suitable conduits and couplers to link the raceways to the controller chassis
• Allow adequate space for future maintenance of the unit. Do not install in a location that will later be difficult to access
• The Universal Source Controllers are designed to be mounted vertically
• During operation, the Universal Source Controllers will produce audible noise caused by electrical noise suppression circuitry and also the circuit
relays within the unit. The noise is a low level buzz that varies with the level of dimming and also clicks when relays are energised. Take these
matters into consideration when deciding on a suitable mounting position.
• The hinged cover must be unscrewed and removed from the front cover when the Universal Source Controller operates at full load in a high ambient
environment
Universal Source Controller
WARNING
WaveLinx Wired
Installation Instructions
Model # SC-UN

Contents
Description Page
Introduction 3
Welcome 3
Range Overview 3
Cabinet Dimensions 3
Specifications 5
Safety 5
Please Read this First 5
Important Points for Consideration 5
Ambient Atmosphere Requirements 6
Mounting 6
Location and Spacing 6
Mounting Holes 7
Standard Weights 7
Accessing the Mounting Holes 8
Supply Wiring 8
Wiring Flow 8
Single Phase Supply 9
Connecting the Supply 9
Max. Wire Gauge for Input Lugs (1 Phase) 9
Three Phase Supply 9
Connecting the Supply 9
Max. Wire Gauge for Input Lugs (3 Phase) 9
Phase Distribution to Circuits 10
Supply to Internal Circuitry 10
Load Wiring 10
High Voltage Load Wiring 10
Total Load Per Channel 11
Load Wire Gauges 11
Earth Connections 11
High Voltage Load Wiring Flows 11
Typical Load Connections 11
Low Voltage Load Wiring 12
Low Voltage Load Wiring Flows 12
Indicators 12
Control Wiring 13
Multiple Control Protocols 13
Termination 13
Control Panel Operation 14
Using The Control Panel 14
Accessing the Operation Menu 15
Menu Navigation 15
Overriding Channels 15
Setting the Time and Date 15
Viewing Power Data Readings 16
Setting Communications Options 16
Changing the Operation Menu Password 16
Universal Source ControllerWaveLinx Wired
MN503104ML page 2
February 2021
www.cooperlighting.com

Introduction
Welcome
The iLumin Universal Source Controller range from Eaton’s
Cooper Controls Business has been designed to provide
maximum flexibility in both installation and operation. Every
model in the range can accept a variety of industry standard
control options, from iCANbus to DMX, from ethernet to
RS-485. Similarly, every model can drive a wide range of lighting
loads, from incandescents to dimmable fluorescents, from non-
dim apparatus to DALI digital modules.
Much care and attention has been applied to the installation
and maintenance of the Universal Source Controllers. Each
model provides clear, logical cable routing and every high
voltage channel is controlled by an individual, easy to replace
circuit.
Range Overview
Each model is specified using a part number in the following
format:
Model Number Supply
Voltage
Supply
Type Circuits Feed Maximum
Load
SC120-06-UN-1P-
ML-20
120 VAC
1 Phase
6
Main Lugs 16A per
Channel
SC120-12-UN-1P-
ML-20 12
SC120-06-UN-3P-
ML-20
3 Phase
6
SC120-12-UN-3P-
ML-20 12
SC120-24-UN-3P-
ML-20 24
SC277-06-UN-1P-
ML-20
277 VAC
1 Phase 6
SC277-06-UN-3P-
ML-20
3 Phase
6
SC277-12-UN-3P-
ML-20 12
SC277-24-UN-3P-
ML-20 24
Cabinet Dimensions
Three overall cabinet sizes are available as shown on this and
the following two pages.
6 Circuit Cabinet
Weight
Packed: 100 lbs (45 Kg)
Unpacked: 88 lbs (40 Kg)
4.13 in.
(105 mm)
37.2 in. (945
mm)
4.13 in.
(105 mm)
9.78 in.
(248.5 mm)
4.45 in.
(113 mm)
7.6 in.
(193 mm)
20.3 in.
(517 mm)
Ø 0.89 in.
(22.5 mm)
0.98 in.
(25 mm)
4.53 in.
(115 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
13.76 in.
(349.5 mm)
Knockouts for Supply and
Load Wiring Only
Knockouts for Low
Voltage Control
Wiring Only
Ø 2.42 in.
61.5 mm
SC 120 06 UN 1P ML 20
Product
SC = Source Controller
Supply Voltage
120 = 120 VAC 277 = 277 VAC
Type
UN = Universal
Circuit Breaker
Rating
20 = 20A
Channels
06, 12, 24 Phase
1P = Single Phase
3P = Three Phase
Panel Feed
ML = Main Lugs
Universal Source Controller WaveLinx Wired
MN503104ML page 3
February 2021
www.cooperlighting.com

12 Circuit Cabinet
Weight
Packed: 160 lbs (72 Kg)
Unpacked: 132 lbs (60 Kg)
24 Circuit Cabinet
Weight
Packed (24): 220 lbs (100 Kg)
Unpacked (24): 200 lbs (90 Kg)
4.13 in.
(105 mm)
4.13 in.
(105 mm)
56.7 in.
(1440 mm)
56.7 in.
(1440 mm)
4.13 in.
(105 mm)
4.13 in.
(105 mm)
9.78 in.
(248.5 mm) 9.78 in.
(248.5 mm)
4.45 in.
(113 mm) 4.45 in. (113 mm)
7.6 in.
(193 mm)
7.6 in.
(193 mm)
20.3 in.
(517 mm)
27.8 in.
(707 mm)
Ø 0.89 in.
(22.5 mm)
Ø 0.89 in.
(22.5 mm)
0.98 in.
(25 mm)
0.98 in.
(25 mm)
4.53 in.
(115 mm)
4.53 in.
(115 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
1.1 in.
(28 mm)
13.76 in.
(349.5 mm)
13.76 in.
(349.5 mm)
Knockouts for Supply and
Load Wiring Only Knockouts for Supply and
Load Wiring Only
Knockouts for Low
Voltage Control
Wiring Only
Knockouts for Low
Voltage Control Wiring
Only
Ø 2.42 in. Ø 2.42 in.
61.5 mm 61.5 mm
Universal Source ControllerWaveLinx Wired
MN503104ML page 4
February 2021
www.cooperlighting.com

Specications
The numerous models within the Universal Source Controller
range share the following key specifications. Information
specific to each cabinet model are provided elsewhere
throughout this guide.
• All channels provide switched (non-dim) and dimmed high
voltage load control as standard
• Leading-edge triac dimmer engines capable of withstanding
repetitive inrush currents of 50 times operating current
without impacting lifetime
• All dimming and switching circuitry for every channel
located on individual boards for quick and easy swap out, if
necessary
• Voltage and frequency compensation to maintain light level
during supply fluctuations
• All channels protected by thermal magnetic circuit breakers
• Power monitoring for each circuit, phase and the total panel
• Bypass jumpering fitted as standard to protect circuits and
allow work lighting during installation
• Selectable low voltage load control available per channel for
dimmable ballast control
• Low maintenance and quiet operation thanks to fanless,
convection cooled operation
• Support for multiple control protocols: iCAN for links
to multiple control sources; DMX512A for links with
entertainment systems; RS-485 for integration with building
management schemes and ethernet for connection to a
variety of systems
• Dual volt-free switch inputs, with programmable responses,
for integration with emergency control devices, building
management systems, etc
• Compact wall mounted design with easy access to all
internal items and lockable front panel door for added
security
• Intuitive control panel provides straightforward programming
and configuration of the system. The control panel allows
a base level installation to be configured without the use of
separate PC programming
Safety
Please Read This First
The Universal Source Controllers are designed, built and
tested to strict safety regulations. By following the steps listed
below and elsewhere within this guide, you can ensure safe
installation and operation of these controller units.
• The Universal Source Controllers must be installed only by a
qualified electrician
• The installation must comply with the appropriate electrical
codes and regulations in force in your area
• The Universal Source Controllers are designed for indoor
installation and use only. The units can, however, be used to
control appropriately certified exterior lighting fixtures
• Ensure that all wiring used conforms fully to local
specifications and is sufficiently rated for the installation
• All new wiring must be fully verified before applying power
• The high voltage supply should be fed to the Universal
Source Controller via an external isolation breaker with
sufficient capacity for the planned installation
• All Universal Source Controllers exceed the weight limit for
one person lifting - always use at least two people when
lifting and mounting the units
• Do not mix load types within a single channel (e.g. 120V
tungsten and low voltage ballast control)
• Ensure that the supply is fully isolated at an external breaker
before removing the chassis covers. Test that power has
been removed before starting to handle conductors
• Ensure that high voltage and low voltage wiring remains
separate
Important Points For Consideration
• The Universal Source Controllers must be mounted flush with
the wall, do not recess the controller chassis
• Upper and lower raceways must not be located within 8
inches (200 mm) of the upper and lower panels of the
Universal Source Controller. Use suitable conduits and
couplers to link the raceways to the controller chassis
• Allow adequate space for future maintenance of the unit. Do
not install in a location that will later be difficult to access
• The Universal Source Controllers are designed to be mounted
vertically
• During operation, the Universal Source Controllers will
produce audible noise caused by electrical noise suppression
circuitry and also the circuit relays within the unit. The noise
is a low level buzz that varies with the level of dimming and
also clicks when relays are energised. Take these matters
into consideration when deciding on a suitable mounting
position.
• The hinged cover must be unscrewed and removed from the
front cover when the Universal Source Controller operates at
full load in a high ambient environment
Universal Source Controller WaveLinx Wired
MN503104ML page 5
February 2021
www.cooperlighting.com

Ambient Atmosphere Requirements
Temperature 320 F to 1040 F (00 C to +400 C)
Humidity 0 to 95% non-condensing
Mounting
Location and Spacing
The Universal Source Controller models are all fully convection
cooled, therefore it is vitally important to ensure that each
unit is installed in a ventilated location that permits sufficient
airflow and provides the correct ambient conditions.
Ensure that the minimum distances to walls and other
equipment shown in the diagrams below are maintained.
Also ensure that the stated ambient atmosphere requirements
are not exceeded.
Refer to ‘Important points for consideration’ when choosing a
mounting location.
Upper Raceway
Lower Raceway
Airow
Airow
Airow
Main
Supply
Isolator
8 in.
(200 mm)
Minimum
8 in.
(200 mm)
Minimum
5 in.
(130 mm)
Minimum
14 in.
(360 mm)
Minimum
Distance to
Ceiling
14 in.
(360 mm)
Minimum for
Door Access and
Cooling
5 in.
(130 mm)
Minimum
Universal Source ControllerWaveLinx Wired
MN503104ML page 6
February 2021
www.cooperlighting.com

Mounting Holes
All models within the Universal Source Controller range are
NEMA Type 1 IP20 rated for indoor use only. Four mounting
holes are provided within the rear of each chassis for
attachment to a suitable wall.
Ensure that the mounting wall is able to safely support the
weight of the unit plus all wiring hardware and that it complies
with local codes. Reinforce where necessary.
Ensure also that the mounting bolts and fixings used are of
sufficient strength and quality to safely hold the unit.
ES C
12
0ENT
3
456
789
#
1.2 in.
(30 mm)
1.2 in.
(30 mm)
1.2 in.
(30 mm)
34.8 in.
(885 mm)
54.32 in.
(1379.8 mm)
54.32 in.
(1379.8 mm)
13.4 in.
(340 mm)
13.4 in.
(340 mm)
18.73 in.
(475.8 mm)
4.6 in.
(116 mm)
4.6 in.
(116 mm)
4.6 in.
(116 mm)
1.2 in.
(30 mm)
1.2 in.
(30 mm)
1.2 in.
(30 mm)
ote: N The mounting holes (for all
models) have diameters of
0.41 in (10.5 mm).
Standard Weights
Cabinet Unpacked Weight
6 Circuit 88 lbs (40 Kg)
12 Circuit 132 lbs (60 Kg)
24 Circuit 200 lbs (90 Kg)
6 Circuit Models 12 Circuit Models 24 Circuit Models
Universal Source Controller WaveLinx Wired
MN503104ML page 7
February 2021
www.cooperlighting.com

Accessing the Mounting Holes
The mounting holes are located within the rear panel of the
Source Controller. To access the mounting holes (and circuit
wiring terminals) it is necessary to remove the front panels.
To Remove the Front Panels
CAUTION: If removing panels on a previously installed Source
Controller, ensure that all power inputs are isolated first.
1. Open the main panel door.
2. Remove the two upper and two lower screws that hold
the main panel in place and carefully lift off the complete
panel.
3. Now remove the single upper and single lower screw
holding the right side panel in place. Carefully lift off the
panel.
4. For 24 circuit models, repeat step 3 for the left side panel.
To Replace the Front Panels
1. Replace the side panel(s) first. Place the right side panel
onto the chassis and replace the upper and lower fixing
screws.
2. For 24 circuit models, repeat step 1 for the left side panel.
3. Place the main panel onto the chassis and open the door.
Replace the two upper and two lower fixing screws.
Supply Wiring
Wiring Flow
The Universal Source Controller range has been designed to
provide a clear layout and logical progression for all power
circuits.
The main supply conductors enter at the top panel and connect
directly to the input lugs. Input power is then fed to a central
bank of breakers and distributed from there to each of the
individual circuit cards.
Two vertical wireways (one for 6 and 12 circuit models) provide
clear routes from the circuit card outputs up to the earth
terminals and the exit knockouts within the top panel of the
chassis.
The diagram shown below indicates a typical wiring flow with
the high voltage load wiring from the various channels (and
their earth connections) exiting from the top panel.
1
2
3
4
5
6
7
8
9
10
11
12
24
23
22
21
20
19
18
17
16
15
14
13
1 2 3 4 5 6
13 14 15 16 17 18
19 20 21 22 23 24
7 8 9 10 11 12
ESC
12
0EN T
3
456
789
#
SUPPLY
Lower Screw for
Right Side Panel
Earth Terminal Earth Terminal
Vertical Wireways
Lower Screws
for Central Panel
Load Wiring
Universal Source ControllerWaveLinx Wired
MN503104ML page 8
February 2021
www.cooperlighting.com

Single Phase Supply
The Universal Source Controllers are available in single phase
supply variants.
ote: N Check the stated voltage rating of the controller before
connecting to the supply and check that it matches the
supply voltage.
Connecting the Supply
The suggested entry point for the supply wiring is via the
center knockout on the top panel of the chassis. This provides
immediate access to the supply lugs below and also leaves the
two knockouts either side for exiting load wiring. Use a suitable
conduit and coupler to feed the source wiring safely into the
chassis.
See the diagram below for connection details. The main earth
terminal is located near to the neutral lug. The earth connection
is bonded to the main backplane of the chassis and the outer
panels.
Please consult the table below for details about the maximum
permissible supply wire gauges for the various controller
models.
Top panel knockouts: 3 x 2.42 inches (61.5 mm).
Maximum Wire Gauge for Input Lugs (Single Phase)
The figures shown below provide the maximum wire gauges
that can be used with the input lugs within each Source
Controller model. The actual gauges of supply wiring that
should be used in any particular installation will depend upon
the connected loads, the wire type used, expected ambient
temperatures and codes in force within your locality.
Source
Controller Hot Neutral Earth
6 circuit 120V 2/0 AWG (70 mm2)2/0 AWG (70 mm2)2 AWG
(35 mm2)
12 circuit 120V 350 MCM (185 mm2)350 MCM (185
mm2)2 AWG
(35 mm2)
6 circuit 277V 2/0 AWG (70 mm2)2/0 AWG (70 mm2)2 AWG
(35 mm2)
SUPPLY
EARTH
HOT
NEUTRAL
Three Phase Supply
The Universal Source Controllers are available in three phase
supply variants.
ote: N Check the stated voltage rating of the controller before
connecting to the supply and check that it matches the
(phase to neutral) supply voltage.
Connecting the Supply
The suggested entry point for the supply wiring is via the
center knockout on the top panel of the chassis. This provides
immediate access to the supply lugs below and also leaves the
two knockouts either side for exiting load wiring. Use a suitable
conduit and coupler to feed the source wiring safely into the
chassis.
See the diagram below for connection details. The main earth
terminal is located near to the neutral lug. The earth connection
is bonded to the main backplane of the chassis and the outer
panels.
Please consult the table below for details about the maximum
permissible supply wire gauges for the various controller
models.
Top panel knockouts: 3 x 2.42 in (61.5 mm).
Maximum Wire Gauge For Input Lugs
(Three Phase)
The figures shown below provide the maximum wire gauges
that can be used with the input lugs within each Source
Controller model. The actual gauges of supply wiring that
should be used in any particular installation will depend upon
the connected loads, the wire type used, expected ambient
temperatures and codes in force within your locality.
SUPPLY
EARTH
NEUTRAL
PHASE 3
PHASE 2
PHASE 1
Knockout size: 2.42 in
(61.5 mm) See pages 3
and 4 for full dimensions
Knockout size: 2.42 in
(61.5 mm) See pages 3
& 4 for full dimensions
Universal Source Controller WaveLinx Wired
MN503104ML page 9
February 2021
www.cooperlighting.com

Source
Controller Hot Neutral Earth
6 circuit 120V 2/0 AWG (70 mm2)2/0 AWG (70 mm2)2 AWG (35 mm2)
12 circuit 120V 2/0 AWG (70 mm2) 2/0 AWG (70 mm2)2 AWG (35 mm2)
24 circuit 120V 4/0 AWG (120 mm2)350 MCM (185
mm2)2 AWG (35 mm2)
6 circuit 277V 2/0 AWG (70 mm2)2/0 AWG (70 mm2)2 AWG (35 mm2)
12 circuit 277V 2/0 AWG (70 mm2) 2/0 AWG (70 mm2)2 AWG (35 mm2)
24 circuit 277V 4/0 AWG (120 mm2)350 MCM (185
mm2)2 AWG (35 mm2)
Torque Value
SC-UN Model Line
Torque in lbs.
Neutral
Torque in lbs.
SC120-06-UN-1P-ML-20 120 120
SC120-06-UN-3P-ML-20 120 120
SC120-12-UN-1P-ML-20 375 375
SC120-12-UN-3P-ML-20 120 120
SC120-24-UN-3P-ML-20 200 375
SC277-06-UN-1P-ML-20 120 120
SC277-06-UN-3P-ML-20 120 120
SC277-12-UN-1P-ML-20 375 375
SC277-12-UN-3P-ML-20 120 120
SC277-24-UN-3P-ML-20 200 375
Phase Distribution to Circuits
The available circuits within each Universal Source Controller
are evenly distributed between the three phases, as listed here:
6 Circuit Controllers
Phase 1: Circuits 1, 4
Phase 2: Circuits 2, 5
Phase 3: Circuits 3, 6
12 Circuit Controllers
Phase 1: Circuits 1, 4, 7, 10
Phase 2: Circuits 2, 5, 8, 11
Phase 3: Circuits 3, 6, 9, 12
24 Circuit Controllers
Phase 1: Circuits 1, 4, 7, 10, 13, 16, 19, 22
Phase 2: Circuits 2, 5, 8, 11, 14, 17, 20, 23
Phase 3: Circuits 3, 6, 9, 12, 15, 18, 21, 24
Supply to Internal Circuitry
The internal power supply that feeds the control panel and
associated circuitry can draw its power from any and all phases
so that it will still operate in the event that not all supply phases
are available.
Load Wiring
High Voltage Load Wiring
Each load channel is served by a dedicated control card
fed from a designated circuit breaker. For each card, load
connections are made using a four-way rapid connection block.
Available at the connection block are a permanent Hot (subject
to circuit breaker status), Switched hot (via relay control),
Dimmed hot (via triac control) and Neutral - see diagram below.
ote: N Earth connections for each channel are made using the
connector blocks located at the top of each
wireway.
When supplied, a red 3-way bypass jumper is installed within
each connection block to serve three purposes:
• To bind the three outputs in order to protect each channel
card from load faults during installation
• To energize each channel output (subject to the status of the
associated circuit breaker) for use as work lighting control
during installation and
• To assist with circuit testing during commissioning
IMPORTANT: The bypass jumper must remain in place on each
channel until the commissioning process is complete.
Dimmed
Hot Neutral
Switched
Hot
Hot (Live)
Bypass
Jumper
Maximum Wire Gauges
Solid Wire: 10 AWG (6 mm2)
Stranded Wire: 12 AWG (4 mm2)
Universal Source ControllerWaveLinx Wired
MN503104ML page 10
February 2021
www.cooperlighting.com

Total Load Per Channel
The load on each channel must not exceed 16A.
Load Wire Gauges
Load wiring must be sized according to the nature of the
channel load(s) and with strict regard to regulations and codes
in force within your locality. The maximum permissible wire
gauges accepted by the connector blocks are:
Solid wire: 10 AWG (6 mm2)
Stranded wire: 12 AWG (4 mm2)
Earth Connections
Earth connections for each channel are available at the
connector blocks located at the top of each wireway:
To Insert a Wire
1. Strip roughly a quarter inch (6 mm) of insulation from the
wire end.
2. Place a small flat blade screwdriver all the way into the
upper rectangular hole (keep the tip of the screwdriver
against the top edge of the hole).
3. Press the screwdriver tip downwards towards the base of
the connection block and push the stripped wire into the
large circular hole.
4. When the wire is in place, release the screwdriver and
check that the wire is firmly held by the internal spring clip.
High Voltage Load Wiring Flows
A knockout (diameter 2.42 inchs /61.5 mm) is provided above
each load wireway within the top panel of the chassis. Use
suitable conduits and couplers. Please see the wiring flow
diagram on page 8.
Typical Load Connections
The examples below show some of the most typical loads and
the way in which they are connected to a Source Controller
circuit.
Dening Load Types
The type of load placed upon each channel must be defined
within the Configuration menu of the control panel. For further
details on how to do this, please refer to the accompanying
System manual.
Standard Dimmable Load
Non-Dim Load
Constant Load
2 Wire Fluorescent Dimmable Ballast (E.g. Advance
Mark X™)
3 Wire Fluorescent Dimmable Ballast (E.g. Lutron® Hi-
Lume® Or Eco-10™)
4 Wire Fluorescent Dimmable Ballast (E.g. 0-10 VDC
Control)
Load Earth Connector Blocks
[Neutral - White]
[Neutral - White]
[Neutral - White]
[Neutral - White]
[Neutral - White]
[Neutral - White]
Ballast
Lutron®
Ballast
0-10V
Ballast
Lamp
Lamp
Lamp
[Dimmed Hot - Black]
[Dimmed Hot - Black]
[Dimmed Hot - Black]
[Dimmed Hot - Black]
[Channeled Hot - Black]
0-10V Control Output - Violet
0-10V Common - Grey
[Dimmed Hot - Orange]
[Dimmed Hot - Black]
Neutral
Neutral
Neutral
Neutral
Neutral
Neutral
Dimmed Hot
Dimmed Hot
Dimmed Hot
Dimmed Hot
Dimmed Hot
Dimmed Hot
Switched Hot
Switched Hot
Switched Hot
Switched Hot
Switched Hot
Switched Hot
Hot
Hot
Hot
Hot
Hot
Hot
Small Flatblade
Screwdriver
Universal Source Controller WaveLinx Wired
MN503104ML page 11
February 2021
www.cooperlighting.com

Low Voltage Load Wiring
Each channel can be individually configured to support any of
the following low voltage load control standards: 0-10V, DSI
or broadcast DALI (DSI and DALI - Canada and Mexico Only).
The high voltage sections for each channel continue to provide
switched hot outputs to power the controlled loads.
ote: N Support for multiple low voltage load control
standards may not be permissible in certain
countries. In such cases, the required control
standard must be stated when ordering.
The low voltage load wiring circuits are located just below the
control panel, accessible either through a removable mini panel
or when the complete casing is removed.
Connections are made easy by using removable plug blocks
which snap into terminals mounted on the circuit boards shown
below:
signal
signal
signal
signal
17
13 19
28
14 20
39
15 21
41
0
16 22
51
1
17 23
61
2
18 24
0V
0V
0V
0V
signal
signal
signal
signal
0V
0V
0V
0V
signal
signal
signal
signal
0V
0V
0V
0V
signal
signal
signal
signal
0V
0V
0V
0V
signal
signal
signal
signal
0V
0V
0V
0V
signal
signal
signal
signal
0V
0V
0V
0V
For each circuit, the low voltage control protocol to be used is
selected using the configuration menu on the control panel.
The programming of the Source Controller channels is covered
within the accompanying System Manual.
ote: N DALI signals for each channel are output in broadcast
mode only - it is not possible to individually address mul-
tiple DALI luminaires on the same control wire.
The low voltage load control circuits are PELV (Protected Extra
Low Voltage).
Low Voltage Load Wiring Flows
The casing provides four knockouts on the base panel for use
by exiting low voltage load cables as well as control wiring.
Each knockout is 0.89 inches (22.5 mm) in diameter.
Use appropriate conduits and couplers to link with raceways or
cable runs, as necessary.
IMPORTANT: Low voltage load wiring should be installed with a
suitable separation to parallel high voltage cables, according to
local and national codes.
Indicators
An indicator is assigned to each low voltage output channel
to provide quick visual feedback. In each case, the indicator
(located next to the output connectors) will mimic the dimmed
status of the associated channel, from zero to full brightness.
Indicators
Universal Source ControllerWaveLinx Wired
MN503104ML page 12
February 2021
www.cooperlighting.com

Control Wiring
Multiple Control Protocols
To ensure maximum versatility, the Universal Source Controllers
provide full compatibility with a range of control protocols,
including:
• iCAN bus
• DMX512A
• RS-485
• Ethernet
Connections for the iCAN bus, DMX512A and RS-485 protocols
are made using removable plug blocks which snap into
terminals mounted on the control circuit board. A standard
RJ45 socket is provided for the ethernet connection.
In addition, a separate connector block (labeled ‘Contact
closure’) allows two volt-free switch inputs from external
systems. Subject to configuration menu settings, these inputs
can be used to affect selected channels.
The control connections are located just below the control
panel, accessible either through a removable mini panel or
when the complete casing is removed.
Termination
The iCAN, DMX and RS-485 are ‘daisy-chain’ protocols that all
require termination on the devices located at either end of the
chain.
The Switched Relay Controller provide jumper links adjacent
to the iCAN, DMX and RS-485 connectors. As standard, all of
these interfaces are terminated. To remove termination for a
particular bus, move the associated termination jumper from
the upper two pins to the lower two pins.
DMX+
RS-485- RS-485+
DMX- OV
OV
Shield
Shield
Ethernet Link
+12V
(Red)
CAN-H
(White)
Drain
(Gray)
CAN-L
(Blue)
0V
(Black)
DMX
Contact
Closure
iCAN
Switch
Input 1
Switch
Input 2
RS-485
TERM
Termination
ON
Device Device Device Universal
Source
Controller
T
T
Termination
OFF
TERM
Universal Source Controller WaveLinx Wired
MN503104ML page 13
February 2021
www.cooperlighting.com

Control Panel Operation
Using the Control Panel
Each Universal Source Controller provides a control panel
to make configuration and operation as straightforward as
possible.
iCAN DMX 485
ESC
ENT
#
1
4
789
56
2
0
3
DATA
Cooper Lighting Solutions
12:00 am
June 04, 2020
Device # 12345678
iCAN DMX 485 DATA
The main configuration procedures within the control panel are
covered within the accompanying System Manual. This section
provides a brief overview of the Operation menu.
OK
OK LINK
LINK
Numeric keypad plus
arrow keys, Escape
(ESC) button and Enter
(ENT) button for menu
navigation
Clear Text
Display Link and Status Indicators
Flashes Regularly
to Indicate Correct
System Operation
When ON, indicates that
the timeclock function is
enabled. Where multiple
SC-UN units are linked,
only one unit will light this
indicator
Illuminates when an
error condition occurs.The
display screen will provide
further information about
the nature of the fault Valid Ethernet Link
Detected
Flashes when data is
present on Ethernet
link
Flashes when data is
present on iCANbus
link
ON when RS-485
channel is enabled,
ashes when data
is present on RS-
485 link
ON when DMX
link is enabled,
ashes when
data is present
on DMX link
Universal Source ControllerWaveLinx Wired
MN503104ML page 14
February 2021
www.cooperlighting.com

Accessing the Operation Menu
During normal service of the Universal Source Controller, the
control panel screen shows only the time, date and device
number.
To Access the Operation Menu
1. Press the ENT button to display
the Select Access Level menu.
2. With the ‘Operation’ option
highlighted, press the ENT button.
3. If requested, enter the four digit
operation password and press
the ENT button.
ote: N When the unit is supplied, there
is initially no password - see the
section ‘Changing the operation
menu password’ to set one.
4. If the password is accepted, the
main ‘Operation Menu’ will be
displayed.
Menu Navigation
Within the control panel menu system, use the following
buttons to navigate:
Use the arrow buttons to move highlight bar
to the required option.
ENT Press to enter an option or to save your changes to an
item.
ESC Press to escape from an option to the previous level.
Operation Menu Contents
The operation menu provides the following options:
Overriding Channels
The override options allow you to alter the output levels on
channels directly from the control panel. You can choose to
alter all channels collectively, alter selected channels or request
a particular pre-programmed scene.
To Override Channels
1. From the ‘Operation’ menu, select the ‘Channel override’
option and press the ENT button. The screen will show the
three options:
Override - options
All channels
Each channel
Select scene
2. Highlight the required option and press the ENT button.
Depending on the chosen option you will be able to affect
outputs as follows:
All Channels - Use the and buttons to adjust the
output level (0 to 100%) for all channels. When the required
output level is displayed, press the ENT button.
Each Channel - Highlight the required channel number
using the and buttons, then press the ENT button.
For the chosen channel, use the and buttons
to adjust the output level (0 to 100%). When the required
output level is displayed, press the ENT button.
Select Scene - Highlight the required scene number using
the and buttons, then press the ENT button.
Setting the Time and Date
The Timeclock manager option contains numerous features
related to the time and date, including daylight saving time,
global coordinates and the selection of changes to channel
outputs at set times. For further information about the other
Timeclock manager features, please refer to the accompanying
System Manual.
To Adjust the Time and Date
1. From the ‘Operation’ menu, select the ‘Timeclock manager’
option and press the ENT button. The screen will show the
four options:
Timeclock manager
Time and Date
Events
Coordinates
DST
GUI help/Operation
Operation Menu
Channel Override Override - Options All Channels
Total Power
Time & Date
Coordinates
DST
Events
Each Channel
Display Power by Phase
Select Scene
Display Power by Channel
Timeclock Manager
Power Data
Communications
Operation Menu
GUI help/operation
Channel override
Timeclock manager
Power data
Select Access Level
Operation
Contact Cooper
Operation
Password
XXXX
Universal Source Controller WaveLinx Wired
MN503104ML page 15
February 2021
www.cooperlighting.com

2. Highlight the ‘Time and Date’ option and press the ENT
button. The current time and date settings will be displayed
with the hour entry highlighted:
Timeclock manager
Time and Date
13:26
2 June 2008
3. Use the up and down buttons to move the highlight to the
required item. Then use the left and right buttons to alter
the highlighted item.
4. Press the ENT button to save and return to the Timeclock
manager menu screen.
Viewing Power Data Readings
The Power data section provides useful feedback and
confirmation of the total power demanded by the controller as
a whole, the power demand on each phase and also the power
drawn on each channel.
To Access Power Data
1. From the ‘Operation’ menu, select the ‘Power data’ option
and press the ENT button. The screen will show the total
power currently being drawn as well as two options:
Power data
Total power 2.39kW
Display by phase
Display by channel
2. Highlight the ‘Display by phase’ option and press the ENT
button to view the phase power distribution:
Power data - Phase
P
hase A 1.75kW
P
hase B 1.65kW
P
hase C 0.95kW
Press the ESC button to return to the previous level.
3. Highlight the ‘Display by channel’ option and press the ENT
button to view the channel power distribution:
Power data - Channels
Channel 1: 0.101kW
Channel 2: 0.130kW
Channel 3: 0kW
Channel 4: 0.500kW
Press the button to view further channels and press the
ESC button to return to the previous level.
Setting Communications Options
The Communications options section allows you to determine
which control protocols should be enabled.
To Set Communications Options
1. From the ‘Operation’ menu, select the ‘Communications’
option and press the ENT button. The screen will show the
available control protocols and their current settings:
v
Communications - options
iCANnet On
Ethernet On
DMX On
RS485 On
2. Highlight the option that you wish to alter and then press
the button to change its ON/OFF status.
3. Press the ENT button to save your changes and exit.
Changing the Operation Menu Password
The unit uses two passwords, one for the operation menu and
another for the configuration menu. When the unit is supplied,
there are initially no passwords. You are strongly recommended
to set separate operation and configuration menu passwords at
the earliest opportunity. After doing so, ensure that the relevant
users are informed of the new passwords.
To Set/Change the Operation Menu Password
1. From the ‘Configuration’ menu, select the ‘Password
Manager’ option and press the ENT button. If a previous
password has been set, the screen will prompt you to enter
the current password:
Password manager
Enter current password
XXXX
Use the keypad to enter the current password. As you type, each
digit will be represented by an ‘X’.
If you enter a character incorrectly, press the ESC button to
erase it.
When you have entered the code, press the ENT button.
2. Highlight the required password to set/change: Operation
or Config, then press the ENT button.
Password manager
Choose password
Operation
Config
3. Enter your new code (4 digits) and press the ENT button.
Then re-enter the code again and press the ENT button.
If the two new codes match, you will be given the option to
save.
4. Highlight the ‘Yes’ option and press the ENT button.
Change password?
YesNo
Warranties and Limitation of Liability
Please refer to www.cooperlighting.com for our terms and conditions.
MN503104ML page 16
February 2021
Cooper Lighting Solutions
1121 Highway 74 South
Peachtree City, GA 30269
P: 770-486-4800
www.cooperlighting.com
For service or technical assistance:
1-800-553-3879
Canada Sales
5925 McLaughlin Road
Mississauga, Ontario L5R 1B8
P: 905-501-3000
F: 905-501-3172
© 2021 Cooper Lighting Solutions
All Rights Reserved.
Product availability, specifications,
and compliances are subject to
change without notice.
Universal Source Controller WaveLinx Wired
Table of contents
Popular Computer Hardware manuals by other brands

Bell
Bell Carte PC P720 Getting started guide

Cypress Semiconductor
Cypress Semiconductor CY7C1471BV25 Specification sheet

Cypress Semiconductor
Cypress Semiconductor CYV15G0100EQ Specification sheet

Analog Devices
Analog Devices EVAL-ADAU1772Z user guide

iXsystems
iXsystems TrueNAS ES60 Basic Setup Guide

burroughs
burroughs 205 Handbook