CSW RECTORSEAL RSH-60 VMD User manual

INSTALLATION INSTRUCTIONS
Surge Protective Device (SPD) & Voltage Monitoring
Device (VMD) for Single-Phase System
Installation
1. To assure proper installation, measure the voltage on
each phase and ensure the correct device is installed.
2. Turn off power to the circuit where surge protector is to
be installed.
3. Mount device to keep conductor length as short as
possible. Cut wires to length and connect to circuit per
wiring diagram below avoiding sharp bends or looping.
4. Splice the included Rectorseal RSH60-VMD 24V
thermostat control wires into the Y1 terminal
thermostat wire.
5. Reinstall covers, restore power and confirm diagnostic
LED is illuminated.
ALTERNATIVE WIRING METHOD:
This SPD can be also be installed by splicing into the wires of the
WIP, within the disconnect box or by using a double lug adapter.
Device Ratings
Normal Voltage
Per Leg Max. Operating Voltage
(MCOV) Per Leg Max. Discharge
Current (IMAX)
120 VAC 150 VAC 60kA
240 VAC DIAGRAM
Split-Phase System: 1 Ph, 2W + G 240 VAC 2-Pole
Disconnect Diagram
Para instrucciones en español visite www.rectorseal.com
Technical Support Call 1-800-648-6802
All surge protection devices require a good ground connection for effective operation
Black Black
Green
Ground
120 VAC DIAGRAM
Single-Phase System: 1 Ph, 2W + G
BLACK
GREEN
BLACK
120 VAC
RSH-60 VMD
24 VAC
Y1
Y1
BLACK
GREEN
BLACK
RSH-60 VMD
24 VAC
Y1
Y1
240 VAC
120 VAC
120 VAC
LINE 2
LINE 1
LED VERDECONDICIÓN LED ROJO ALARMA AUDIBLE
Protección contra
sobretensiones
Sin protección contra
sobretensiones
Bajo Voltaje
Protección de ciclo corto
ENCENDIDO
APAGADO
––
DESTELLO
APAGADO
ENCENDIDO
––
––
––
––
ENCENDIDO
––
Diagnostic Operations
GREEN LEDCONDITION RED LED AUDIBLE ALARM
Surge Protection
No Surge Protection
Under Voltage
Short Cycle Protection
ON
OFF
––
OFF
ON
––
––
––
––
ON
LED VERTÉTAT LED ROUGE ALARME AUDITIVE
Protection Contre
Les Surtensions
Non Protection Contre
Les Surtensions
Sous Tension
Protection Du
Cycle Court
ALLUMÉ
ÉTEINDRE
––
FLASH
ÉTEINDRE
ALLUMÉ
––
––
––
––
ALLUMÉ
––
Opérations de diagnostic
Operaciones de diagnóstico
FLASH ––

RectorSeal, LLC • 2601 Spenwick Drive, Houston, TX 77055, USA • 800-231-3345 • Fax 800-441-0051 • rectorseal.com
A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its affiliates or its licensor’s and are protected by copyright, trademark and other intellectual prop-
erty laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice. ©2019 RectorSeal. All rights reserved. R50366-1019
Coverage for the Surge Protective Device (SPD) & Voltage Monitoring Device (VMD) for Single-Phase System
Limited Lifetime Product Warranty
PSP Products, Inc. (“Manufacturer”) will, at its sole discretion, repair or replace any RSH-60 Surge Protection Device (SPD) that is defective or is damaged by an electrical surge
(including those caused by lightning) for the lifetime of the product from the date of installation by the original owner or owner of record of the premises (User) at no cost to the User.
Connected Equipment Warranty
Manufacturer will, at its sole discretion, for a period of 5 years from the date of installation, repair or replace heating, ventilation and air conditioning equipment that is damaged as a result of
SPD failure during a surge event. Coverage is applicable only if the SPD (1) was fully functional immediately prior to the claim event; (2) was properly installed per the installation instructions;
and (3) sustained surge damage as a result of the claim event.
Damage claims must be made within 14 days of the occurrence and the SPD returned to Manufacturer within 30 days of the occurrence with the original purchase receipts of the SPD. Returned
SPDs require an RMA number and a completed Warranty Claim Form (contact Warranty Assistance for details), and the SPD must be determined to have failed based on Manufacturer's test
procedures.
This coverage is secondary to any applicable warranties, service contracts and all other insurance. If the claim is found to be valid, Manufacturer will pay up to the deductible amount of the
home owners insurance or the cost of the damage, whichever is less, subject to a $5000.00 limit per occurrence. All of the above items must be met in order to have a valid claim.
The above coverage applies to the User only and is the exclusive remedy under this warranty, whether based on contract, tort, including negligence, or otherwise. Manufacturer reserves the
right to audit the damages, site and/or cost of repairs and may require a notarized proof of loss. This warranty does not cover damage associated with sustained over voltages, vandalism, theft,
normal wear and tear, obsolescence, abuse, unauthorized modication or alteration, misuse, improper installation or catastrophic events including direct lightning hit.
Except as expressly provided by this warranty, Manufacturer disclaims liability for any incidental, indirect, special or consequential damages arising out of the sale or use of SPDs (including
without limitation: lost business prots, loss of data and all freight, mileage, travel time and insurance charges associated with warranty coverage claims). Some states do not allow the
exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you. This warranty gives you specic legal rights and you may have other
rights which vary from state to state. This warranty is valid in the United States and Canada only.
Caution: Effective surge suppression requires correct wiring and all SPDs must be properly grounded for this warranty to be honored.
For Warranty Assistance call 800-648-6802 or (703) 368-8376 • PO Box 4108, Manassas, VA 20110
Completely read the instructions before installing the unit.
Installation and service must be performed by a qualied licensed service professional
Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
This product is intended for indoor or outdoor use.
Installation and/or wiring must be in accordance with national and local electrical code (NEC) and/or Canadian Electrical Code (CEC) requirements.
Improper wiring could cause equipment damage, re, injury, and/or death.
This unit contains no serviceable parts.
Popular Measuring Instrument manuals by other brands

Axis Industries
Axis Industries QALCOSONIC HEAT 1 Technical description, installation and user instructions

Hanna Instruments
Hanna Instruments PCA 310 instruction manual

Shark
Shark 100B quick start guide

ISA
ISA CBA1000 manual

TPI
TPI 265 instruction manual

Rohde & Schwarz
Rohde & Schwarz ZNA Series user manual