24 Volt AC, 1.25 Amp, GP, Use in Class 2 (Thermostat) Circuit Only 6 ft. 18 AWG Lead Wire
ENVIRONMENTALLY FRIENDLY MAINTENANCE
Nu Line® A/C Condensate Drain Cleaner
Prevents drain line buildup. Ready to use, no mixing. Will not harm drain pans,
pipes or pumps. It is recommended that the switch/cap assembly be removed
and cleaned every three months.
1. Turn o power to unit at main panel and lit switch/cap assembly
out of the fitting.
2. Pour Nu Line into fitting opening.
3. Clean switch, float, stem and inside of fitting.
4. Replace switch/cap assembly.
Mighty Pump™
Manually Vacuum or Push-Out
Clogs in A/C Condensate Drain Lines.
Product# 97795
WIRING (see g. 3)
1. WARNING: Disconnect power to unit at main panel prior to performing electrical work.
2. If not present, it is recommended that an inline fuse be installed to protect 24-volt circuit and time
delay to avoid rapid cycling of equipment.
3. Locate 24-volt thermostat cable entering the air handler unit.
4. Disconnect or cut the red wire and connect to switch lead using wire nut. Connect other switch lead
to air handler terminal. Incorporating switch in red circuit shuts down entire unit. If placed in the
yellow circuit, fan continues to run (inhibits mold during long absences.)
5. Test switch by liting float while unit is running. If wired correctly, unit will stop when float is lited.
WARNING: This device must be installed strictly in accordance with manufacturer’s instructions (to ensure proper operation) and in accordance
with all applicable local plumbing, drainage and electrical codes.
WARNING: Electric shock hazard. Disconnect power supply before installing this product to avoid electrical shock and/or equipment damage. Use
in Class 2 (thermostat) circuit only, not to exceed 24-volts, 1.25 amps to avoid damage or fire hazard.
CAUTION: This device will not detect clogs occurring upstream from the installation point.
CAUTION: If not present, it is recommended that a fuse and time delay be installed, to protect the 24-volt circuit and avoid rapid cycling of
equipment, prior to installing this product.
CAUTION: When installing this device in plugged configuration on auxiliary drain outlets, it is essential that PVC plug is closed o and water-tight.
CAUTION: This product is intended for use in water only. Not for use in the presence of flammable liquids or vapors.
CAUTION: Refer to the appropriate HVAC equipment operation manual prior to installing this product.
CAUTION: Do not use on dual compressor systems.
INLINE INSTALLATION FOR HORIZONTAL CEILING (PANCAKE) UNITS (See Fig. 2)
NOTE: Primary drain (inline) installation is also recommended on First Company® horizontal ceiling (pancake) units as some floodin g may occur
if installed on auxiliary outlets, due to the closeness of the outlet to the top of the pan.
1. Glue ¾” stub to primary pan outlet.
2. Glue ¾” Tee onto stub with Tee stem positioned horizontally away from the unit and plumb.
3. Follow steps 3-9 under INLINE INSTALLATION FOR WALL UNITS, above.
Furnace / A.C.
Figure 3: Wiring Diagram for Unit Shutdown
Red
White
Green
Yellow
From Thermostat
To Switch
Wire Nut
Technical Support Call 1-800-231-3345
RectorSeal®• 2601 Spenwick Drive, Houston, TX 77055, USA • 713-263-8001 • rectorseal.com
A CSW Industrials Company. RectorSeal, the logos and other trademarks are property of RectorSeal, LLC, its aliates or its licensor’s and are protected by copyright, trademark and other intellectual
property laws, and may not be used without permission. RectorSeal reserves the right to change specifications without prior notice. ©2022 RectorSeal. All rights reserved. R50109 1022
8 oz - Product #97685
32 oz - Product #97690