
10 GG-VL2-R
Specications
Input Power: +24 VDC, 85 mA
Detection Principle: Solid-state
Detection Method: Diusion
Gas: CFC / HFC / HCFC refrigerants (R11, R12, R22,
R134a, R404a, R410a, R434a, R507a, etc.)
Range: 0/1% (10,000 ppm)
Output Signal:
Linear 4/20 mA (max input impedance: 700 Ohms)
Deadband: 12 mA or 50% full-scale
Response Time: T90 = less than 30 seconds
Accuracy: +/- 5% of full-scale
Zero Drift: Less than 1% per month
Span Drift: Less than 1% of full-scale per month
Linearity: +/- 5% of full-scale
Repeatability: +/- 5% of full-scale
Wiring Connections:
3-conductor, shielded, stranded, 20 AWG cable
(General Cable C2525A or equivalent) up to 1500 ft.
Terminal Block Plug (Field Wiring): 26-16 AWG,
torque 4 lbs-in.
Enclosure: 18 gauge stainless steel housing. Captive
screw in hinged lid. For non-classied areas.
Mounting Kit: Schedule 80 NPT pipe ttings
Temperature Range: -46°F to +140°F (-46°C to +60°C)
Dimensions: 5.48” high x 4.90” wide x 2.93” deep
Weight: 4 lbs (includes mounting kit)
Certication:
SGS Listed:
Conforms to UL 61010-1
Certied to CSA C22.2 No. 61010-1
Troubleshooting
Sensor Fault: (low signal reading)
Indications: (any or all)
• Red LED on transmitter lit.
• Voltage signal at testpoints is 5 mVdc (.5 mA output).
• PLC displays negative value (e.g. -2150 ppm).
• Controller indicates sensor fault or sensor failure
Possible Cause / Solution:
• Sensor exposed to liquid. Replace sensor element
(see page 9 for more info).
• Loose connection. Check and tighten sensor wires.
Constant or Intermittent high signal or alarms:
Indications:
• Erratic or constant high concentration reading at
controller or PLC.
Possible Cause / Solution:
• Weeping relief valve. Check valve by drawing a
sample from the header with an accurate portable
refrigerant detector. Be sure to sample 1’ to 3’ from
inside the header to ensure a good reading.
• or loosen union nut and remove sensor assembly
from header. If signal returns to normal in fresh air,
investigate relief valve(s) and replace if necessary.
• Condenser steam. Re-install the ½“ plug or install
pipe in its place, lowered below the condenser
steam level to allow a fresh-air vent to the sensor.
• Sensor aged beyond its useful life (hypersensitive).
Replace sensor element (see page 9 for more info).