Daikin EKAC120A User manual

INSTALLATION MANUAL
Address card
EKAC120A

43
705 5
GROUND
RX+/TX+
RX-/TX-
M1
JS2
GROUND
RX+/TX+
RX-/TX-
BA
198 199197
197198 199
1
3
2

1
Address card Installation manual
READ THIS MANUAL ATTENTIVELY BEFORE
STARTING UP THE UNIT. DO NOT THROW IT AWAY.
KEEP IT IN YOUR FILES FOR FUTURE REFERENCE.
IMPROPER INSTALLATION OR ATTACHMENT OF
EQUIPMENT OR ACCESSORIES COULD RESULT IN
ELECTRIC SHOCK, SHORT-CIRCUIT, LEAKS, FIRE OR
OTHER DAMAGE TO EQUIPMENT. BE SURE ONLY TO
USE ACCESSORIES MADE BY DAIKIN THAT ARE
SPECIFICALLY DESIGNED FOR USE WITH THE
EQUIPMENT AND HAVE THEM INSTALLED BY A
PROFESSIONAL.
IF UNSURE OF INSTALLATION PROCEDURES OR
USE, ALWAYS CONTACT YOUR DAIKIN DEALER FOR
ADVICE AND INFORMATION.
INTRODUCTION
Thank you for purchasing the EKAC120A address card kit. This
kit will enable you to communicate with your chiller through a
Building Management System or supervisory system. Please refer
to the Gateway Installation Manual for more information and a
detailed overview of how the communication works.
CHILLER RANGE
This specific address card is designed to function with chillers of
the ranges EUWA*80~120**, EUWA*160~200** and
EUW*120~200**. Since these chillers contain two PCBs, you will
need one kit of two address cards per chiller.
* = A, B, C, ...., Z
** = KA, KAX, KX, LZ, ....
YOUR ADDRESS CARD KIT
The kit you have just purchased consists of:
■2 address cards (type EKAC120A) with connectors
■1 connection wire to field rail
■1 connection wire for connecting PCB A and PCB B
DESCRIPTION OF THE ADDRESS CARD
Measurements
(refer to figure 1)
Connection to the chiller
The connection is made automatically when you insert the
address cards into the PCB. The connection occurs through three
pins:
Pin Meaning
1 ground
2 RX+/TX+
3 RX–/TX–
BEFORE YOU HANDLE THE ADDRESS CARD
If handled inappropriately, your address card may suffer damage.
Hold your address card by the edges. Never touch the rear end of
the card with your hands.
Before starting up the unit for the first time, make sure that
it has been properly installed. It is therefore necessary to
read the installation manual supplied with the unit and the
recommendations listed in “Checks before initial start-up”
carefully.
HOW TO INSTALL THE ADDRESS CARDS?
TURN THE POWER OFF BEFORE INSTALLING THE
ADDRESS CARD.
This unit has a double circuit. This means that there are two
PCBs. You have to install an address card on each PCB.
Install the address cards
Follow these instructions to install the address card on PCB A.
1 Take the address card by the edges.
2 Carefully place the adress card with the socket over the 7-pin
PCB header as in figure 2.
3 Repeat steps 1 and 2 to install the address card on PCB B.
4 Connect the address card of PCB A to the address card of PCB
B as listed below. Use the same screw connectors.
PCB A Wire PCB B
GROUND red wire GROUND
RX+/TX+ white wire RX+/TX+
RX-/TX- brown wire RX-/TX-
Connect the address card of PCB B to the field rail
(refer to figure 3)
Connect as listed below. Use the same screw connectors as with
the connection of both address cards.
Screw connector Wire Terminal
GROUND red wire terminal 197
RX+/TX+ white wire terminal 198
RX-/TX- brown wire terminal 199
Connect the field rail to the gateway or to the other
address card
You have two possibilities:
■If the chiller is the first in line or the only one to connect to a
gateway, connect it to the gateway directly.
■If the chiller is a chiller in line and not the first one in line,
connect it to another chiller.
Read more on this in the installation manual of the gateway.
EKAC120A

2
HOW TO OPERATE THE ADDRESS CARDS?
For more information, consult the following documents:
■The chiller operation manual: installing BMS address card +
defining the BMS settings.
■Installation manual of gateway.
■Operation manual of gateway.
THE VARIABLES DATABASE
The BMS or supervisory system and the address card
communicate through a fixed set of variables, also called address
numbers. Hereafter, you will find the information you need about
the digital, integer and analogue variables that the BMS or
supervisory system can read from or write to the chiller’s address
card.
Digital variables
A
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
B
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Air cooled 80~120HP Air cooled 160~200HP Water cooled 120~200HP
PCB B:
-
PCB B:
-
PCB B:
-
PCB B:
-
-
-
-
-
-
Note
These chillers have two PCBs: PCB A & B.
PCB A: general parameters and circuit 1 parameters
PCB B: circuit 2 parameters
If a parameter is marked with X in column of PBC A or B, then the
parameter is present on the marked PCB.
Address Read/
Write
Description Comments
Unit status
Enable remote on-off
Unit safety active
Digital input 1
Digital input 2
Digital input 3
Digital input 4
Digital input 5
Digital input 6
Digital input 7
Digital input 8
Digital input 9
Digital input 10
Digital input 11
Digital output 1
Digital output 2
Digital output 3
Digital output 4
Digital output 5
Digital output 6
Digital output 7
Digital output 8
Digital output 9
Digital output 10
Digital output 11
Digital output 12
Digital output 13
Circuit safety active
Guard timer active
Start up timer active
Anti-recycling timer active
Load up timer active
Load down timer active
On-off command
High-pressure setback active
Digital input 12
25% is installed
V-a meter installed
DICN OPTION: Network
safety active
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
r
w
r
r
r
r
r
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
36
37
38
39
40
1=on 0=off
1=yes 0=no
1=yes 0=no
Low pressure switch
High pressure switch
Reverse phase protector
Overcurrent
Discharge thermal protector
Compressor thermal protector
PCB A:
Flow-switch
PCB B:
Enable/
Disable C1
PCB A:
Flow-switch
PCB A:
Flow-switch
PCB A:
Bypass
PCB B:
Enable/
disable C2
PCB A:
Bypass
PCB A:
Bypass:
Dual setpoint
Digital input remote on-off
Emergency
Star
Delta
Compressor status
Pump
General situation of alarm
12%
25%
40%
Fan 1
Fan 2
Fan 3
Evaporator heater
Fan 1
Fan 2
Fan 3
Evaporator heater
70%
1=yes 0=no
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
1=not zero 0=zero
If 1 is written, then toggle status of the unit.
After this action the controller resets this parameter.
0=not active 1=Active
Enable/disable capacity
limitation
Enable/disable capacity
limitation
0=no 1=yes
0=no 1=yes
0=no 1=yes

3
Air cooled 80~120HP Air cooled 160~200HP
Water cooled 120~200HP
A
X
X
X
X
X
X
X
B
X
X
X
X
X
0=R134a 1=R22 2=407C
Integer variables
Address Read/
Write
Description Comments
Enable write BMS
Running hours compressor
(higher part)
Running hours compressor
(lower part)
Actual fanstep
Status of compressor (if on) for
readout in mask
Status of compressor (if off) for
readout in mask
Unit type
User settings
0=off,1=low,2=med,3=high
0=ON 12 star
1=ON 12% delta
2=ON 25% delta
3=ON 40% delta
4=ON 70% delta
5=ON 100% delta
0=OFF can startup
1=OFF timers busy
2=OFF disabled (contact)
3=OFF safety active
4=OFF bypass mode
0=OFF can startup
1=OFF timers busy
2=OFF 0% (limit)
3=OFF safety active
4=OFF bypass mode
0=OFF can startup
1=OFF timers busy
2=OFF 0% (limit)
3=OFF safety active
4=OFF bypass mode
First digit
Second digit
Third digit
Fourth digit
Fifth digit
Sixth digit
Seventh digit
User settings manual mode
If 25% is installed
0=0%, 1=25%, 2=40%,
3=70%, 4=100%
If 25% not installed
0=0%, 1=40%,
2=70%, 3=100%
1
2
3
4
5
6
7
r
r
r
r
r
r
r
(00000)
(00000)
V2.012
0=EUWA*80J*
1=EUWA*100J*
2=EUWA*120J*
3=EUWA*80K*
4=EUWA*100K*
5=EUWA*120K*
Above V2.012
0=AC 80HP CO
1=AC 100HP CO
2=AC 120HP CO
V2.012
0=EUW*120K*
1=EUW*140K*
2=EUW*160K*
3=EUW*180K*
4=EUW*200K*
5=EUWA*160K*
6=EUWA*180K*
7=EUWA*200K*
Above V2.012
9=AC 160HP
10=AC 180HP
11=AC 200HP
12=AC 220HP
13=AC 240HP
14=AC 260HP
15=AC 280HP
V2.012
0=EUW*120K*
1=EUW*140K*
2=EUW*160K*
3=EUW*180K*
4=EUW*200K*
5=EUWA*160K*
6=EUWA*180K*
7=EUWA*200K*
Above V2.012
0=WC 120HP
1=WC 140HP
2=WC 160HP
3=WC 180HP
4=WC 200HP
5=WC 220HP
6=WC 240HP
7=WC 260HP
8=WC 280HP
0,1,2,3,4,5,6,7,8
7,8
User settings manual mode
0=off,1=low,2=med,3=high
User setting (thermostat)
User setting (thermostat)
User setting (thermostat)
User setting (thermostat)
Refrigeration type
Manufacturer number 1
Manufacturer number 2
Manufacturer number 3
Manufacturer number 4
Manufacturer number 5
Manufacturer number 6
Manufacturer number 7
Actual thermostat step
Maximum number of thermostat
step
Manual setting of compressor
Manual setting of fans
Load up time in outlet control
Load down time in outlet control
Load up time in inlet control
Load down time in inlet control
Running mode
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
r
r
r
r
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
r/w
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24 0=inlet
1=outlet
2=manual
0=inlet
1=outlet
2=manual
0=cooling inlet
1=cooling outlet
2=cooling manual
3=heating intlet
4=heating manual
5=double thermostat
inlet
6=double thermostat
manual
For units with DICN OPTION
0=inlet 1=outlet 2=manual

4
Air cooled 80~120HP Air cooled 160~200HP
Water cooled 120~200HP
Integer variables
Address Read/
Write
Description Comments
27
28
29
30
31
32
33
34
35
36
37
38
39
r
r
r
r
r
r
r
r
r
r/w
r/w
r
r/w
X
X
X
X
X
X
X
X
X
X
X
X
X
Water/air cooled unit
Cooling only/heat pump
Unique eprom parameter
Eprom version (higher part)
Eprom version (lower part)
DICN OPTION:
status of Master
DICN OPTION:
status of Slave 1
DICN OPTION:
status of Slave 2
DICN OPTION:
status of Slave 3
DICN OPTION:
Mode
DICN OPTION:
number of Slaves
DICN OPTION:
Master or Slave
DICN OPTION:
cooling/heating
mode
0=air-cooled unit
1=water-cooled unit
0=cooling only
1=heat pump
Example 12 (V1.012)
0=normal 1=standby 2=disconnected 3=C1 safety 4=C2 safety
5=unitsafety 6=not present (=empty line on screen)
0=normal 1=standby 2=disconnect
Network setting (only for unit defined as Master)
0=Master 1=Slave 1 2=Slave 2 3=Slave 3
2=AC 80~120HP
7=AC 80~120HP with DICN
OPTION
1=V1 (V1.012)
--0=cooling 1=heating
2=double thermostat
5=AC 160~280HP
10=AC 160~280HP
with DICN OPTION
4=WC 120~280HP
9=WC 120~280HP
with DICN OPTION
AB
A
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
B
X
X
X
X
X
X
X
PCB B
-
-
-
-
-
PCB B
-
Analog variables
Address Read/
Write
Description Comments
Analog input 2
Analog input 3
Analog input 1
Analog input 7
Analog input 8
Converted analog input 7
Converted analog input 8
Analog input 6
Analog input 5
Actual setpoint
Minimum outlet water
Inlet setpoint 1 cooling
Inlet setpoint 2 cooling
Outlet setpoint 1 cooling
Outlet setpoint 2 cooling
Step length in inlet control
Step difference in inlet control
Step length in outlet control
Step difference in outlet control
Inlet setpoint 1 heating
Inlet setpoint 2 heating
Analog input 4
Inlet evaporator temperature
PCB A
Outlet
evaporator
temp
Outlet evaporator
temp of circuit
Outlet evaporator temp
of circuit
PCB A
Ambient
temp
PCB A
Ambient
temp
PCB B
Mixed outlet
evaporator
temp
PCB A
Inlet
condenser
temp
PCB B
Mixed outlet
evaporator
temp
High pressure
Low pressure
High pressure converted in temperature
Low pressure converted in temperature
Voltage (only if V-A option is installed, if not, value 99.0 displays)
Current (only if V-A option is installed, if not, value 99.0 displays)
User setting (In/outlet setpoint 1 or 2)
Factory setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
User setting
r
r
r
r
r
r
r
r
r
r
r
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r/w
r
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
Air cooled 80~120HP Air cooled 160~200HP
Water cooled 120~200HP
DICN OPTION: common evaporator outlet temperature

Zandvoordestraat 300, B-8400 Oostende, Belgium 4PWE08534- 1A
Table of contents
Other Daikin Accessories For Chiller & Freezer manuals
Popular Accessories For Chiller & Freezer manuals by other brands

Haskris
Haskris CWS Installation and operation instruction

True
True TUR-24-R/L-OP-B install guide

Insignia
Insignia NS-BC48SS7 installation guide

Carrier
Carrier Pro-Dialog Plus 30HZ Installation, operation and maintenance instructions

Ingersoll-Rand
Ingersoll-Rand Trane CFAE16 Technical guide

Stulz
Stulz CyberCool 2 CSO 1102 ASN Original instructions