I. Installation
Clearances
•A CWS must have unobstructed space above and below the unit for piping connections. 2’
(61cm) clearance on the front is required.
•A CGS must have unobstructed space above and clearance on the sides for piping and
electrical connections. 3’ (91cm) clearance on the front is required.
Mounting
•A CWS must be mounted on a wall. Use appropriate anchors to support the weight of the unit.
•A CGS must be mounted on the floor and secured to a wall. Use appropriate anchors to
prevent any risk of tipping over.
•Leveling legs are provided with the CGS. Adjust as necessary.
Piping
•Comply with local codes for proper piping.
•Use copper piping or reinforced EPDM hose and use non-ferrous materials.
•Insulate piping to minimize condensation.
•Ensure piping is clean and free of flux at solder joints.
•Connect piping to the unit according to the labels on the connections.
Electrical Power
•Contact a licensed electrician to perform the electrical installation.
•Refer to the nameplate label for electrical requirements.
•Use a dedicated service disconnect switch and circuit breaker or time delay fusing according to
the nameplate.
Filling the Unit
•With the unit switched off, run fluid from the main cooling source through the unit.