Daikin Altherma EBLQ011CA3V3 How to use

Installer reference guide
Daikin Altherma low temperature monobloc English
Installer reference guide
Daikin Altherma low temperature monobloc
EBLQ011CA3V3
EBLQ014CA3V3
EBLQ016CA3V3
EBLQ011CA3W1
EBLQ014CA3W1
EBLQ016CA3W1
EDLQ011CA3V3
EDLQ014CA3V3
EDLQ016CA3V3
EDLQ011CA3W1
EDLQ014CA3W1
EDLQ016CA3W1
EKCB07CAV3
EK2CB07CAV3

Table of Contents
Installer reference guide
2
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Table of Contents
1 General safety precautions 3
1.1 About the documentation .......................................................... 3
1.1.1 Meaning of warnings and symbols.............................. 3
1.2 For the installer.......................................................................... 4
1.2.1 General ....................................................................... 4
1.2.2 Installation site ............................................................ 4
1.2.3 Refrigerant .................................................................. 4
1.2.4 Brine............................................................................ 5
1.2.5 Water .......................................................................... 5
1.2.6 Electrical ..................................................................... 5
2 About the documentation 6
2.1 About this document.................................................................. 6
2.2 Installer reference guide at a glance ......................................... 6
3 About the box 7
3.1 Overview: About the box ........................................................... 7
3.2 Outdoor unit............................................................................... 7
3.2.1 To unpack the outdoor unit ......................................... 7
3.2.2 To handle the outdoor unit.......................................... 7
3.2.3 To remove the accessories from the outdoor unit....... 7
3.3 Control box ................................................................................ 8
3.3.1 To unpack the control box........................................... 8
3.3.2 To remove the accessories from the control box ........ 8
3.4 Option box ................................................................................. 8
3.4.1 To unpack the option box............................................ 8
3.4.2 To remove the accessories from the option box......... 9
4 About the units and options 9
4.1 Overview: About the units and options...................................... 9
4.2 Identification .............................................................................. 9
4.2.1 Identification label: Outdoor unit ................................. 9
4.2.2 Identification label: Control box................................... 9
4.2.3 Identification label: Option box.................................... 9
4.3 Combining units and options ..................................................... 10
4.3.1 Possible combinations of outdoor unit and options..... 10
4.3.2 Possible options for the outdoor unit........................... 10
4.3.3 Possible options for the control box............................ 11
4.3.4 Possible options for the option box............................. 12
5 Application guidelines 12
5.1 Overview: Application guidelines............................................... 12
5.2 Setting up the space heating/cooling system ............................ 12
5.2.1 Single room................................................................. 13
5.2.2 Multiple rooms – OneLWT zone ................................ 15
5.2.3 Multiple rooms – TwoLWT zones............................... 17
5.3 Setting up the domestic hot water tank ..................................... 18
5.3.1 System layout – Standalone DHW tank...................... 18
5.3.2 Selecting the volume and desired temperature for
the DHW tank.............................................................. 18
5.3.3 Setup and configuration – DHW tank.......................... 19
5.3.4 DHW pump for instant hot water................................. 19
5.3.5 DHW pump for disinfection ......................................... 19
5.3.6 DHW pump for tank preheating .................................. 19
5.4 Setting up the energy metering ................................................. 19
5.4.1 Produced heat............................................................. 20
5.4.2 Consumed energy....................................................... 20
5.4.3 Normal kWh rate power supply................................... 20
5.4.4 Preferential kWh rate power supply ............................ 21
5.5 Setting up an external temperature sensor ............................... 21
6 Preparation 21
6.1 Overview: Preparation............................................................... 21
6.2 Preparing the installation site .................................................... 21
6.2.1 Installation site requirements of the outdoor unit ........ 21
6.2.2 Additional installation site requirements of the
outdoor unit in cold climates ........................................ 22
6.2.3 Installation site requirements of the control box........... 23
6.2.4 Installation site requirements of the option box............ 23
6.3 Preparing water piping ............................................................... 23
6.3.1 Water circuit requirements ........................................... 23
6.3.2 Formula to calculate the expansion vessel pre-
pressure ....................................................................... 24
6.3.3 To check the water volume and flow rate .................... 25
6.3.4 Changing the pre-pressure of the expansion vessel.... 26
6.3.5 To check the water volume: Examples ........................ 26
6.4 Preparing electrical wiring .......................................................... 26
6.4.1 About preparing electrical wiring.................................. 26
6.4.2 About preferential kWh rate power supply ................... 26
6.4.3 Overview of electrical connections except external
actuators ...................................................................... 26
6.4.4 Overview of electrical connections for external and
internal actuators ......................................................... 27
7 Installation 28
7.1 Overview: Installation ................................................................. 28
7.2 Opening the units ....................................................................... 28
7.2.1 About opening the units ............................................... 28
7.2.2 To open the outdoor unit.............................................. 28
7.2.3 To open the switch box cover of the outdoor unit ........ 29
7.2.4 To open the backup heater switch box cover of the
outdoor unit .................................................................. 29
7.2.5 To open the control box ............................................... 29
7.2.6 To open the option box ................................................ 29
7.3 Mounting the outdoor unit........................................................... 30
7.3.1 About mounting the outdoor unit.................................. 30
7.3.2 Precautions when mounting the outdoor unit............... 30
7.3.3 To provide the installation structure ............................. 30
7.3.4 To install the outdoor unit............................................. 30
7.3.5 To provide drainage ..................................................... 30
7.3.6 To prevent the outdoor unit from falling over ............... 31
7.4 Mounting the control box ............................................................ 31
7.4.1 Precautions when mounting the control box ................ 31
7.4.2 To install the control box .............................................. 31
7.5 Mounting the option box ............................................................. 32
7.5.1 Precautions when mounting the option box................. 32
7.5.2 To install the option box ............................................... 32
7.6 Connecting the water piping....................................................... 32
7.6.1 About connecting the water piping............................... 32
7.6.2 Precautions when connecting the water piping............ 32
7.6.3 To connect the water piping......................................... 32
7.6.4 To protect the water circuit against freezing ................ 33
7.6.5 To fill the water circuit .................................................. 34
7.6.6 To fill the domestic hot water tank ............................... 34
7.6.7 To insulate the water piping ......................................... 34
7.7 Connecting the electrical wiring.................................................. 34
7.7.1 About connecting the electrical wiring.......................... 34
7.7.2 Precautions when connecting the electrical wiring ...... 34
7.7.3 Guidelines when connecting the electrical wiring ........ 35
7.7.4 To connect the electrical wiring on the outdoor unit..... 35
7.7.5 To connect the main power supply .............................. 36
7.7.6 To connect the backup heater power supply ............... 37
7.7.7 To connect the user interface ...................................... 37
7.7.8 To connect the shut-off valve....................................... 38
7.7.9 To connect the domestic hot water pump .................... 39
7.7.10 To connect the electrical wiring on the control box ...... 39
7.7.11 To connect the control box power supply .................... 39
7.7.12 To connect the interconnection cable between
control box and outdoor unit ........................................ 39
7.7.13 To connect the electrical wiring on the option box ....... 40
7.7.14 To connect the option box power supply ..................... 40
7.7.15 To connect the interconnection cable between option
box and control box...................................................... 40
7.7.16 To connect the electrical meters .................................. 40
7.7.17 To connect the alarm output ........................................ 41

1 General safety precautions
Installer reference guide
3
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
7.7.18 To connect the space cooling/heating ON/OFF
output .......................................................................... 41
7.7.19 To connect the changeover to external heat source... 41
7.8 Finishing the outdoor unit installation ........................................ 41
7.8.1 To close the outdoor unit ............................................ 41
7.9 Finishing the control box installation ......................................... 41
7.9.1 To close the control box.............................................. 41
7.10 Finishing the option box installation .......................................... 41
7.10.1 To close the option box............................................... 41
8 Configuration 42
8.1 Overview: Configuration ............................................................ 42
8.1.1 To connect the PC cable to the switch box................. 42
8.1.2 To access the most used commands ......................... 42
8.1.3 To copy the system settings from the first to the
second user interface.................................................. 43
8.1.4 To copy the language set from the first to the second
user interface .............................................................. 44
8.1.5 Quick wizard: Set the system layout after first power
ON............................................................................... 44
8.2 Basic configuration .................................................................... 44
8.2.1 Quick wizard: Language / time and date..................... 44
8.2.2 Quick wizard: Standard............................................... 44
8.2.3 Quick wizard: Options ................................................. 46
8.2.4 Quick wizard: Capacities (energy metering) ............... 48
8.2.5 Space heating/cooling control..................................... 48
8.2.6 Domestic hot water control ......................................... 52
8.2.7 Contact/helpdesk number ........................................... 53
8.3 Advanced configuration/optimization......................................... 53
8.3.1 Space heating/cooling operation: advanced............... 53
8.3.2 Domestic hot water control: advanced........................ 57
8.3.3 Heat source settings ................................................... 61
8.3.4 System settings........................................................... 62
8.4 Menu structure: Overview user settings .................................... 65
8.5 Menu structure: Overview installer settings............................... 66
9 Commissioning 67
9.1 Overview: Commissioning......................................................... 67
9.2 Precautions when commissioning ............................................. 67
9.3 Checklist before commissioning................................................ 67
9.4 Checklist during commissioning ................................................ 67
9.4.1 To check the minimum flow rate ................................. 68
9.4.2 Air purge function........................................................ 68
9.4.3 To perform a test run .................................................. 69
9.4.4 To perform an actuator test run .................................. 69
9.4.5 Underfloor heating screed dryout................................ 69
10 Hand-over to the user 70
10.1 About locking and unlocking...................................................... 71
Possible function locks .............................................................. 71
To check if locking is active....................................................... 71
To activate or deactivate a function lock ................................... 71
To activate or deactivate button lock......................................... 71
11 Maintenance and service 71
11.1 Overview: Maintenance and service ......................................... 71
11.2 Maintenance safety precautions................................................ 71
11.2.1 Opening the outdoor unit ............................................ 71
11.2.2 Opening the control box.............................................. 71
11.2.3 Opening the option box............................................... 71
11.3 Checklist for yearly maintenance of the outdoor unit ................ 71
12 Troubleshooting 72
12.1 Overview: Troubleshooting........................................................ 72
12.2 Precautions when troubleshooting ............................................ 72
12.3 Solving problems based on symptoms...................................... 72
12.3.1 Symptom: The unit is NOT heating or cooling as
expected ..................................................................... 72
12.3.2 Symptom: The compressor does NOT start (space
heating or domestic water heating)............................. 73
12.3.3 Symptom: The pump is making noise (cavitation) ...... 73
12.3.4 Symptom: The pressure relief valve opens................. 74
12.3.5 Symptom: The water pressure relief valve leaks ......... 74
12.3.6 Symptom: The space is NOT sufficiently heated at
low outdoor temperatures ............................................ 74
12.3.7 Symptom: The pressure at the tapping point is
temporarily unusually high ........................................... 74
12.3.8 Symptom: Decoration panels are pushed away due
to a swollen tank .......................................................... 74
12.3.9 Symptom: Tank disinfection function is NOT
completed correctly (AH-error)..................................... 74
12.3.10 Symptom: The energy metering (produced heat) is
NOT working correctly ................................................. 75
12.4 Solving problems based on error codes ..................................... 75
12.4.1 Error codes: Overview ................................................. 75
13 Disposal 78
13.1 Overview: Disposal..................................................................... 78
13.2 To pump down............................................................................ 78
13.3 To start and stop forced cooling ................................................. 78
14 Technical data 79
14.1 Service space: Outdoor unit ....................................................... 79
14.2 Piping diagram: Outdoor unit...................................................... 80
14.3 Wiring diagram: Outdoor unit ..................................................... 80
14.4 ESP curve: Outdoor unit............................................................. 84
15 Glossary 85
16 Field settings table 86
1 General safety precautions
1.1 About the documentation
▪ The original documentation is written in English. All other
languages are translations.
▪ The precautions described in this document cover very important
topics, follow them carefully.
▪ The installation of the system, and all activities described in the
installation manual and the installer reference guide MUST be
performed by an authorised installer.
1.1.1 Meaning of warnings and symbols
DANGER
Indicates a situation that results in death or serious injury.
DANGER: RISK OF ELECTROCUTION
Indicates a situation that could result in electrocution.
DANGER: RISK OF BURNING
Indicates a situation that could result in burning because of
extreme hot or cold temperatures.
DANGER: RISK OF EXPLOSION
Indicates a situation that could result in explosion.
WARNING
Indicates a situation that could result in death or serious
injury.
WARNING: FLAMMABLE MATERIAL
CAUTION
Indicates a situation that could result in minor or moderate
injury.

1 General safety precautions
Installer reference guide
4
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
NOTICE
Indicates a situation that could result in equipment or
property damage.
INFORMATION
Indicates useful tips or additional information.
Symbol Explanation
Before installation, read the installation and
operation manual, and the wiring instruction sheet.
Before performing maintenance and service tasks,
read the service manual.
For more information, see the installer and user
reference guide.
1.2 For the installer
1.2.1 General
If you are NOT sure how to install or operate the unit, contact your
dealer.
NOTICE
Improper installation or attachment of equipment or
accessories could result in electric shock, short-circuit,
leaks, fire or other damage to the equipment. Only use
accessories, optional equipment and spare parts made or
approved by Daikin.
WARNING
Make sure installation, testing and applied materials
comply with applicable legislation (on top of the
instructions described in the Daikin documentation).
CAUTION
Wear adequate personal protective equipment (protective
gloves, safety glasses,…) when installing, maintaining or
servicing the system.
WARNING
Tear apart and throw away plastic packaging bags so that
nobody, especially children, can play with them. Possible
risk: suffocation.
DANGER: RISK OF BURNING
▪ Do NOT touch the refrigerant piping, water piping or
internal parts during and immediately after operation. It
could be too hot or too cold. Give it time to return to
normal temperature. If you must touch it, wear
protective gloves.
▪ Do NOT touch any accidental leaking refrigerant.
WARNING
Provide adequate measures to prevent that the unit can be
used as a shelter by small animals. Small animals that
make contact with electrical parts can cause malfunctions,
smoke or fire.
CAUTION
Do NOT touch the air inlet or aluminium fins of the unit.
NOTICE
▪ Do NOT place any objects or equipment on top of the
unit.
▪ Do NOT sit, climb or stand on the unit.
NOTICE
Works executed on the outdoor unit are best done under
dry weather conditions to avoid water ingress.
In accordance with the applicable legislation, it might be necessary
to provide a logbook with the product containing at least: information
on maintenance, repair work, results of tests, stand-by periods,…
Also, at least, following information MUST be provided at an
accessible place at the product:
▪ Instructions for shutting down the system in case of an emergency
▪ Name and address of fire department, police and hospital
▪ Name, address and day and night telephone numbers for
obtaining service
In Europe, EN378 provides the necessary guidance for this logbook.
1.2.2 Installation site
▪ Provide sufficient space around the unit for servicing and air
circulation.
▪ Make sure the installation site withstands the unit's weight and
vibration.
▪ Make sure the area is well ventilated. Do NOT block any
ventilation openings.
▪ Make sure the unit is level.
Do NOT install the unit in the following places:
▪ In potentially explosive atmospheres.
▪ In places where there is machinery that emits electromagnetic
waves. Electromagnetic waves may disturb the control system,
and cause malfunction of the equipment.
▪ In places where there is a risk of fire due to the leakage of
flammable gases (example: thinner or gasoline), carbon fibre,
ignitable dust.
▪ In places where corrosive gas (example: sulphurous acid gas) is
produced. Corrosion of copper pipes or soldered parts may cause
the refrigerant to leak.
1.2.3 Refrigerant
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure refrigerant piping installation complies with
applicable legislation. In Europe, EN378 is the applicable
standard.
NOTICE
Make sure the field piping and connections are NOT
subjected to stress.
WARNING
During tests, NEVER pressurize the product with a
pressure higher than the maximum allowable pressure (as
indicated on the nameplate of the unit).
WARNING
Take sufficient precautions in case of refrigerant leakage. If
refrigerant gas leaks, ventilate the area immediately.
Possible risks:
▪ Excessive refrigerant concentrations in a closed room
can lead to oxygen deficiency.
▪ Toxic gas may be produced if refrigerant gas comes
into contact with fire.

1 General safety precautions
Installer reference guide
5
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
DANGER: RISK OF EXPLOSION
Pump down – Refrigerant leakage. If you want to pump
down the system, and there is a leak in the refrigerant
circuit:
▪ Do NOT use the unit's automatic pump down function,
with which you can collect all refrigerant from the
system into the outdoor unit. Possible consequence:
Self-combustion and explosion of the compressor
because of air going into the operating compressor.
▪ Use a separate recovery system so that the unit's
compressor does NOT have to operate.
WARNING
ALWAYS recover the refrigerant. Do NOT release them
directly into the environment. Use a vacuum pump to
evacuate the installation.
NOTICE
After all the piping has been connected, make sure there is
no gas leak. Use nitrogen to perform a gas leak detection.
NOTICE
▪ To avoid compressor breakdown, do NOT charge more
than the specified amount of refrigerant.
▪ When the refrigerant system is to be opened,
refrigerant MUST be treated according to the applicable
legislation.
WARNING
Make sure there is no oxygen in the system. Refrigerant
may only be charged after performing the leak test and the
vacuum drying.
▪ In case re-charge is required, refer to the nameplate of the unit. It
states the type of refrigerant and necessary amount.
▪ The unit is factory charged with refrigerant and depending on pipe
sizes and pipe lengths some systems require additional charging
of refrigerant.
▪ Only use tools exclusively for the refrigerant type used in the
system, this to ensure pressure resistance and prevent foreign
materials from entering into the system.
▪ Charge the liquid refrigerant as follows:
If Then
A siphon tube is present
(i.e., the cylinder is marked with
"Liquid filling siphon attached")
Charge with the cylinder upright.
A siphon tube is NOT present Charge with the cylinder upside
down.
▪ Open refrigerant cylinders slowly.
▪ Charge the refrigerant in liquid form. Adding it in gas form may
prevent normal operation.
CAUTION
When the refrigerant charging procedure is done or when
pausing, close the valve of the refrigerant tank
immediately. If the valve is NOT closed immediately,
remaining pressure might charge additional refrigerant.
Possible consequence: Incorrect refrigerant amount.
1.2.4 Brine
If applicable. See the installation manual or installer reference guide
of your application for more information.
WARNING
The selection of the brine MUST be in accordance with the
applicable legislation.
WARNING
Take sufficient precautions in case of brine leakage. If
brine leaks, ventilate the area immediately and contact
your local dealer.
WARNING
The ambient temperature inside the unit can get much
higher than that of the room, e.g. 70°C. In case of a brine
leak, hot parts inside the unit can create a hazardous
situation.
WARNING
The use and installation of the application MUST comply
with the safety and environmental precautions specified in
the applicable legislation.
1.2.5 Water
If applicable. See the installation manual or installer reference guide
of your application for more information.
NOTICE
Make sure water quality complies with EU directive
98/83EC.
1.2.6 Electrical
DANGER: RISK OF ELECTROCUTION
▪ Turn OFF all power supply before removing the
switch box cover, connecting electrical wiring or
touching electrical parts.
▪ Disconnect the power supply for more than 1 minute,
and measure the voltage at the terminals of main circuit
capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you
can touch electrical components. For the location of the
terminals, see the wiring diagram.
▪ Do NOT touch electrical components with wet hands.
▪ Do NOT leave the unit unattended when the service
cover is removed.
WARNING
If NOT factory installed, a main switch or other means for
disconnection, having a contact separation in all poles
providing full disconnection under overvoltage category III
condition, MUST be installed in the fixed wiring.

2 About the documentation
Installer reference guide
6
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
WARNING
▪ ONLY use copper wires.
▪ Make sure the field wiring complies with the applicable
legislation.
▪ All field wiring MUST be performed in accordance with
the wiring diagram supplied with the product.
▪ NEVER squeeze bundled cables and make sure they
do NOT come in contact with the piping and sharp
edges. Make sure no external pressure is applied to the
terminal connections.
▪ Make sure to install earth wiring. Do NOT earth the unit
to a utility pipe, surge absorber, or telephone earth.
Incomplete earth may cause electrical shock.
▪ Make sure to use a dedicated power circuit. NEVER
use a power supply shared by another appliance.
▪ Make sure to install the required fuses or circuit
breakers.
▪ Make sure to install an earth leakage protector. Failure
to do so may cause electric shock or fire.
▪ When installing the earth leakage protector, make sure
it is compatible with the inverter (resistant to high
frequency electric noise) to avoid unnecessary opening
of the earth leakage protector.
NOTICE
Precautions when laying power wiring:
▪ Do NOT connect wiring of different thicknesses to the
power terminal block (slack in the power wiring may
cause abnormal heat).
▪ When connecting wiring which is the same thickness,
do as shown in the figure above.
▪ For wiring, use the designated power wire and connect
firmly, then secure to prevent outside pressure being
exerted on the terminal board.
▪ Use an appropriate screwdriver for tightening the
terminal screws. A screwdriver with a small head will
damage the head and make proper tightening
impossible.
▪ Over-tightening the terminal screws may break them.
Install power cables at least 1metre away from televisions or radios
to prevent interference. Depending on the radio waves, a distance of
1metre may not be sufficient.
WARNING
▪ After finishing the electrical work, confirm that each
electrical component and terminal inside the electrical
components box is connected securely.
▪ Make sure all covers are closed before starting up the
unit.
NOTICE
Only applicable if the power supply is three‑phase, and the
compressor has an ON/OFF starting method.
If there exists the possibility of reversed phase after a
momentary black out and the power goes on and off while
the product is operating, attach a reversed phase
protection circuit locally. Running the product in reversed
phase can break the compressor and other parts.
2 About the documentation
2.1 About this document
Target audience
Authorised installers
Documentation set
This document is part of a documentation set. The complete set
consists of:
▪General safety precautions:
▪ Safety instructions that you must read before installing
▪ Format: Paper (in the box of the outdoor unit)
▪Outdoor unit installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the outdoor unit)
▪Control box installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the control box)
▪Option box installation manual:
▪ Installation instructions
▪ Format: Paper (in the box of the option box)
▪Installer reference guide:
▪ Preparation of the installation, good practices, reference data,…
▪ Format: Digital files on http://www.daikineurope.com/support-
and-manuals/product-information/
▪Addendum book for optional equipment:
▪ Additional info about how to install optional equipment
▪ Format: Paper (in the box of the outdoor unit) + Digital files on
http://www.daikineurope.com/support-and-manuals/product-
information/
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
Technical engineering data
▪ A subset of the latest technical data is available on the regional
Daikin website (publicly accessible).
▪ The full set of latest technical data is available on the Daikin
extranet (authentication required).
2.2 Installer reference guide at a
glance
Chapter Description
General safety
precautions
Safety instructions that you must read
before installing
About the documentation What documentation exists for the
installer
About the box How to unpack the units and remove
their accessories
About the units and
options
▪ How to identify the units
▪ Possible combinations of units and
options
Application guidelines Various installation setups of the system
Preparation What to do and know before going
on‑site

3 About the box
Installer reference guide
7
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Chapter Description
Installation What to do and know to install the
system
Configuration What to do and know to configure the
system after it is installed
Commissioning What to do and know to commission the
system after it is configured
Hand‑over to the user What to give and explain to the user
Maintenance and service How to maintain and service the units
Troubleshooting What to do in case of problems
Disposal How to dispose of the system
Technical data Specifications of the system
Glossary Definition of terms
Field settings table Table to be filled in by the installer, and
kept for future reference
Note: There is also an installer settings
table in the user reference guide. This
table has to be filled in by the installer
and handed over to the user.
3 About the box
3.1 Overview: About the box
This chapter describes what you have to do after the boxes with the
outdoor unit, control box and/or option box are delivered on-site.
It contains information about:
▪ Unpacking and handling the units
▪ Removing the accessories from the units
Keep the following in mind:
▪ At delivery, the unit MUST be checked for damage. Any damage
MUST be reported immediately to the carrier's claims agent.
▪ Bring the packed unit as close as possible to its final installation
position to prevent damage during transport.
▪ Prepare the path along which you want to bring the unit inside in
advance.
3.2 Outdoor unit
3.2.1 To unpack the outdoor unit
1
4
5
2
3
4×
3.2.2 To handle the outdoor unit
Carry the unit slowly as shown:
157~160 kg
CAUTION
To avoid injury, do NOT touch the air inlet or aluminium
fins of the unit.
3.2.3 To remove the accessories from the
outdoor unit
1Open the outdoor unit.

3 About the box
Installer reference guide
8
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
1×
2×
2×
2Remove the accessories.
ENERG IJAY
IAIE ENERG IJAY
IAIE
1×
1× 1× 1× 1×
a b c d
2×2× fe g
aGeneral safety precautions
bAddendum book for optional equipment
cOutdoor unit installation manual
dOperation manual
eSealing ring for shut-off valve
fShut-off valve
gEnergy label
3.3 Control box
NOTICE
Control box EKCB07CAV3 is an option and cannot be
used standalone.
3.3.1 To unpack the control box
1
2
3.3.2 To remove the accessories from the
control box
1Open the control box.
2Remove the accessories.
2× 2× 2×
abc
aM4 bolts for user interface
bM4 nuts for user interface
cWires for domestic hot water booster heater relay
3.4 Option box
NOTICE
▪ Option box EK2CB07CAV3 is an option and cannot be
used standalone.
▪ To be able to use the option box, it is required that
optional control box EKCB07CAV3 is part of the
system.
3.4.1 To unpack the option box
1

4 About the units and options
Installer reference guide
9
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
2
3.4.2 To remove the accessories from the
option box
1Open the option box.
2Remove the accessories.
2×
a
aConnectors for interconnection cable between the option
box and control box EKCB07CAV3.
4 About the units and options
4.1 Overview: About the units and
options
This chapter contains information about:
▪ Identifying the outdoor unit
▪ Identifying the control box (if applicable)
▪ Identifying the option box (if applicable)
▪ Combining the outdoor unit with options
▪ Combining the control box with options
▪ Combining the option box with options
▪ Possible combinations of outdoor unit and domestic hot water tank
4.2 Identification
NOTICE
When installing or servicing several units at the same time,
make sure NOT to switch the service panels between
different models.
4.2.1 Identification label: Outdoor unit
Location
Model identification
Example: EB/DLQ14CA3V3/W1
Code Explanation
E European monobloc outdoor heat pump
B
D
B=Reversible (heating+cooling)
D=Heating only
L Low water temperature – ambient zone: −10~
−25°C
Q Refrigerant R410A
14 Capacity class
CA3 Model series
V3
W1
V3=Power supply: 1~, 220~240 V, 50 Hz
W1=Power supply: 3N~, 380~415 V, 50 Hz
4.2.2 Identification label: Control box
Location
Model identification
Example: EKCB07 CA V3
Code Description
EK European kit
CB Control box
07 Capacity class
CA Model series
V3 Power supply
4.2.3 Identification label: Option box
Location
Model identification
Example: EK2CB07 CA V3
Code Description
EK European kit
2 Optional
CB Control box
07 Capacity class
CA Model series

4 About the units and options
Installer reference guide
10
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Code Description
V3 Power supply
4.3 Combining units and options
4.3.1 Possible combinations of outdoor unit
and options
FHL1 FHL2 FHL3
a b ce d fg
h
i
aOutdoor unit (EBLQ+EDLQ011~016CA(3)V3+W1)
bRefrigerant part of the outdoor unit
cHydro part of the outdoor unit
dValve kit EKMBHBP1
eBackup heater
fControl box EKCB07CAV3
gOption box EK2CB07CAV3
hDomestic hot water tank
iSpace heating circuit
Option System components required for that option
Outdoor unit EBLQ
+EDLQ011~016CA3V3+W1
Control box
EKCB07CAV3
Option box
EK2CB07CAV3
Valve kit EKMBHBP1
Optional equipment
User interface (EKRUCBL*)
(mandatory)
O
Simplified user interface
(EKRUCBS)
O
Domestic hot water tank O O O
Remote outdoor sensor
(EKRSCA1)
O
PC updater tool
(EKPCCAB)
O
Room thermostat
(EKRTWA, EKRTR1)
O O
Remote sensor for wireless
thermostat (EKRTETS)
O O
Heat pump convector
(FWXV)
O O
Remote indoor sensor
(KRCS01-1)
O O O
Field-supplied components
Space heating/cooling
operation control (or
shut‑off valve)
O
Preferential kWh rate
power supply (voltage‑free
contact)
O O
Domestic hot water pump O O
Electric meter O O O
Alarm output O O O
Space cooling/heating ON/
OFF output
O O O
Changeover to external
heat source
O O O
4.3.2 Possible options for the outdoor unit
User interface (EKRUCBL*)
The user interface and a possible additional user interface are
available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the control box,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.

4 About the units and options
Installer reference guide
11
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Following user interfaces are available:
▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or
copied from an user interface to the other.
For installation instructions, see "7.7.7 To connect the user
interface"on page37.
INFORMATION
▪ If control box EKCB07CAV3 is NOT part of the system,
connect the user interface directly to the outdoor unit.
▪ If control box EKCB07CAV3 is part of the system, you
can also connect the user interface to the control box.
Simplified user interface (EKRUCBS)
▪ The simplified user interface can only be used in combination with
the main user interface.
▪ The simplified user interface acts as room thermostat and needs
to be installed in the room that you want it to control.
For installation instructions, see the installation and operation
manual of the simplified user interface.
Domestic hot water tank
For providing domestic hot water, a domestic hot water tank can be
connected to the outdoor unit.
For installation instructions, see the installation manual of the
domestic hot water tank and addendum book for optional equipment.
INFORMATION
▪ The domestic hot water tank can only be connected if
control box EKCB07CAV3 and valve kit EKMBHBP1 is
part of the system.
▪ The domestic hot water tank is connected to the hydro
part of the outdoor unit, and wired to control box
EKCB07CAV3.
Remote outdoor sensor (EKRSCA1)
By default the sensor inside the outdoor unit will be used to measure
the outdoor temperature.
As an option the remote outdoor sensor can be installed to measure
the outdoor temperature on another location (e.g. to avoid direct
sunlight) to have an improved system behaviour.
For installation instructions, see the installation manual of the remote
outdoor sensor and the addendum book for optional equipment.
INFORMATION
You can only connect either the remote indoor sensor or
the remote outdoor sensor.
Heat pump convector (FWXV)
For providing space heating/cooling, it is possible to use heat pump
convectors (FWXV).
For installation instructions, refer to the installation manual of the
heat pump convectors, and the addendum book for optional
equipment.
LAN adapter for smartphone control + Smart Grid applications
(BRP069A61)
You can install this LAN adapter to:
▪ Control the system via a smartphone app.
▪ Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN
adapter.
INFORMATION
▪ If control box EKCB07CAV3 is NOT part of the system,
connect the LAN adapter directly to the outdoor unit.
▪ If control box EKCB07CAV3 is part of the system, you
can also connect the LAN adapter to the control box.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a
smartphone app.
For installation instructions, see the installation manual of the LAN
adapter.
INFORMATION
▪ If control box EKCB07CAV3 is NOT part of the system,
connect the LAN adapter directly to the outdoor unit.
▪ If control box EKCB07CAV3 is part of the system, you
can also connect the LAN adapter to the control box.
4.3.3 Possible options for the control box
User interface (EKRUCBL*)
The user interface and a possible additional user interface are
available as an option.
The additional user interface can be connected:
▪ To have both:
▪ control close to the control box,
▪ room thermostat functionality in the principal space to be
heated.
▪ To have an interface containing other languages.
Following user interfaces are available:
▪ EKRUCBL1 contains following languages: German, French,
Dutch, Italian.
▪ EKRUCBL2 contains following languages: English, Swedish,
Norwegian, Finnish.
▪ EKRUCBL3 contains following languages: English, Spanish,
Greek, Portuguese.
▪ EKRUCBL4 contains following languages: English, Turkish,
Polish, Romanian.
▪ EKRUCBL5 contains following languages: German, Czech,
Slovenian, Slovakian.
▪ EKRUCBL6 contains following languages: English, Croatian,
Hungarian, Estonian.
▪ EKRUCBL7 contains following languages: English, German,
Russian, Danish.
Languages on the user interface can be uploaded by PC software or
copied from an user interface to the other.
For installation instructions, see "7.7.7 To connect the user
interface"on page37.

5 Application guidelines
Installer reference guide
12
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
INFORMATION
▪ If control box EKCB07CAV3 is NOT part of the system,
connect the user interface directly to the outdoor unit.
▪ If control box EKCB07CAV3 is part of the system, you
can also connect the user interface to the control box.
Simplified user interface (EKRUCBS)
▪ The simplified user interface can only be used in combination with
the main user interface.
▪ The simplified user interface acts as room thermostat and needs
to be installed in the room that you want it to control.
For installation instructions, see the installation and operation
manual of the simplified user interface.
Room thermostat (EKRTWA, EKRTR1, RTRNETA)
You can connect an optional room thermostat to control box
EKCB07CAV3. This thermostat can either be wired (EKRTWA) or
wireless (EKRTR1 and RTRNETA). Thermostat RTRNETA can only
be used in heating-only systems.
For installation instructions, see the installation manual of the room
thermostat and addendum book for optional equipment.
Remote sensor for wireless thermostat (EKRTETS)
You can use a wireless indoor temperature sensor (EKRTETS) only
in combination with the wireless thermostat (EKRTR1).
For installation intructions, see the installation manual of the room
thermostat and addendum book for optional equipment.
PC configurator (EKPCCAB)
The PC cable makes a connection between the switch box of the
outdoor unit (or that of control box EKCB07CAV3) and a PC. It gives
the possibility to upload different language files to the user interface,
and parameters to the outdoor unit. For the available language files,
contact your local dealer.
The software and corresponding operating instructions are available
on http://www.daikineurope.com/support-and-manuals/software-
downloads/.
For installation instructions, see the installation manual of the PC
cable, the "8Configuration"on page42 chapter, and the addendum
book for optional equipment.
LAN adapter for smartphone control + Smart Grid applications
(BRP069A61)
You can install this LAN adapter to:
▪ Control the system via a smartphone app.
▪ Use the system in various Smart Grid applications.
For installation instructions, see the installation manual of the LAN
adapter.
INFORMATION
▪ If control box EKCB07CAV3 is NOT part of the system,
connect the LAN adapter directly to the outdoor unit.
▪ If control box EKCB07CAV3 is part of the system, you
can also connect the LAN adapter to the control box.
LAN adapter for smartphone control (BRP069A62)
You can install this LAN adapter to control the system via a
smartphone app.
For installation instructions, see the installation manual of the LAN
adapter.
INFORMATION
▪ If control box EKCB07CAV3 is NOT part of the system,
connect the LAN adapter directly to the outdoor unit.
▪ If control box EKCB07CAV3 is part of the system, you
can also connect the LAN adapter to the control box.
4.3.4 Possible options for the option box
Remote indoor sensor (KRCS01-1)
By default the internal user interface sensor will be used as room
temperature sensor.
As an option the remote indoor sensor can be installed to measure
the room temperature on another location.
The remote indoor sensor is connected to option box
EK2CB07CAV3. For installation instructions, see the installation
manual of the remote indoor sensor and the addendum book for
optional equipment.
INFORMATION
▪ The remote indoor sensor can only be used in case the
user interface is configured with room thermostat
functionality.
▪ You can only connect either the remote indoor sensor
or the remote outdoor sensor.
5 Application guidelines
5.1 Overview: Application guidelines
The purpose of the application guidelines is to give a glance of the
possibilities of the Daikin heatpump system.
NOTICE
▪ The illustrations in the application guidelines are meant
for reference only, and are NOT to be used as detailed
hydraulic diagrams. The detailed hydraulic
dimensioning and balancing are NOT shown, and are
the responsibility of the installer.
▪ For more information about the configuration settings to
optimize heatpump operation, see "8Configuration"on
page42.
This chapter contains application guidelines for:
▪ Setting up the space heating/cooling system
▪ Setting up an auxiliary heat source for space heating
▪ Setting up the domestic hot water tank
▪ Setting up the energy metering
▪ Setting up an external temperature sensor
5.2 Setting up the space heating/
cooling system
The heatpump system supplies leaving water to heat emitters in one
or more rooms.
Because the system offers a wide flexibility to control the
temperature in each room, you need to answer the following
questions first:
▪ How many rooms are heated or cooled by the Daikin heatpump
system?
▪ Which heat emitter types are used in each room and what is their
design leaving water temperature?
Once the space heating/cooling requirements are clear, Daikin
recommends to follow the setup guidelines below.

5 Application guidelines
Installer reference guide
13
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
INFORMATION
In case an external room thermostat is used and room frost
protection needs to be guaranteed in all conditions, then
you have to set auto emergency [A.6.C] to 1.
5.2.1 Single room
Underfloor heating or radiators – Wired room
thermostat
Setup
B
A
a
b
c
AMain leaving water temperature zone
BOne single room
aUser interface used as room thermostat
bControl box
cBackup heater
▪ The underfloor heating or radiators are directly connected to the
outdoor unit.
▪ The room temperature is controlled by the user interface, that is
connected to control box EKCB07CAV3. Possible installations:
▪ Control box EKCB07CAV3 is installed in the room and the user
interface is used as room thermostat.
▪ Control box EKCB07CAV3 is installed indoors, close to the
outdoor unit + user interface installed in the room and used as
room thermostat.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
▪Cost effective. You do NOT need an additional external room
thermostat.
▪Highest comfort and efficiency. The smart room thermostat
functionality can decrease or increase the desired leaving water
temperature based on the actual room temperature (modulation).
This results in:
▪ Stable room temperature matching the desired temperature
(higher comfort)
▪ Less ON/OFF cycles (more quiet, higher comfort and higher
efficiency)
▪ Lowest possible leaving water temperature (higher efficiency)
▪Easy. You can easily set the desired room temperature via the
user interface:
▪ For your daily needs, you can use preset values and schedules.
▪ To deviate from your daily needs, you can temporarily overrule
the preset values and schedules, use the holiday mode…
Underfloor heating or radiators – Wireless room
thermostat
Setup
B
A
e
d
a
b
c
AMain leaving water temperature zone
BOne single room
aUser interface
bControl box
cBackup heater
dReceiver for wireless external room thermostat
eWireless external room thermostat
▪ The underfloor heating or radiators are directly connected to the
outdoor unit.
▪ The room temperature is controlled by the wireless external room
thermostat (optional equipment EKRTR1).
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
▪ #: [A.2.2.E.5]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
▪Wireless. The Daikin external room thermostat is available in a
wireless version.
▪Efficiency. Although the external room thermostat only sends ON/
OFF signals, it is specifically designed for the heatpump system.

5 Application guidelines
Installer reference guide
14
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
▪Comfort. In case of under floor heating, the wireless external
room thermostat prevents condensation on the floor during cooling
operation by measuring the room humidity.
Heatpump convectors
Setup
B
A
d
a
b
c
AMain leaving water temperature zone
BOne single room
aUser interface
bControl box
cBackup heater
dRemote controller of the heatpump convectors
▪ The heat pump convectors are directly connected to the outdoor
unit.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on control box EKCB07CAV3 (X2M/1 and X2M/2)
▪ The space operation mode is sent to the heatpump convectors by
one digital output on control box EKCB07CAV3 (X8M/6 and
X8M/7).
INFORMATION
When using multiple heat pump convectors, make sure
each one receives the infrared signal from the remote
controller of the heatpump convectors.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
▪ #: [A.2.2.E.5]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
▪Cooling. The heat pump convector offers, besides heating
capacity, also excellent cooling capacity.
▪Efficiency. Optimal energy efficiency because of the interlink
function.
▪Stylish.
Combination: Underfloor heating + Heatpump
convectors
▪ Space heating is provided by:
▪ The underfloor heating
▪ The heatpump convectors
▪ Space cooling is provided by the heatpump convectors only. The
underfloor heating is shut off by the shut-off valve.
Setup
B
A
d
M1
a
c
b
AMain leaving water temperature zone
BOne single room
aUser interface
bControl box
cBackup heater
dRemote controller of the heatpump convectors
▪ The heat pump convectors are directly connected to the outdoor
unit.
▪ A shut-off valve (field supply) is installed before the under floor
heating to prevent condensation on the floor during cooling
operation.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The space heating/cooling demand signal is sent to one digital
input on control box EKCB07CAV3 (X2M/1 and X2M/2)
▪ The space operation mode is sent by one digital output (X8M/6
and X8M/7) on control box EKCB07CAV3 to:
▪ The heatpump convectors
▪ The shut-off valve
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
External room thermostat for the
main zone:
▪ #: [A.2.2.E.5]
▪ Code: [C-05]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition.
Benefits
▪Cooling. Heat pump convectors provide, besides heating
capacity, also excellent cooling capacity.
▪Efficiency. Under floor heating has the best performance with
Altherma LT.

5 Application guidelines
Installer reference guide
15
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
▪Comfort. The combination of the two heat emitter types provides:
▪ The excellent heating comfort of the underfloor heating
▪ The excellent cooling comfort of the heatpump convectors
5.2.2 Multiple rooms – OneLWT zone
If only one leaving water temperature zone is needed because the
design leaving water temperature of all heat emitters is the same,
you do NOT need a mixing valve station (cost effective).
Example: If the heat pump system is used to heat up one floor
where all the rooms have the same heat emitters.
Underfloor heating or radiators – Thermostatic
valves
If you are heating up rooms with underfloor heating or radiators, a
very common way is to control the temperature of the main room by
using a thermostat (this can either be the user interface connected to
control box EKCB07CAV3, or an external room thermostat), while
the other rooms are controlled by so-called thermostatic valves (field
supply), which open or close depending on the room temperature.
Setup
T
B C
A
a
b
c
AMain leaving water temperature zone
BRoom 1
CRoom 2
aUser interface
bControl box
cBackup heater
▪ The underfloor heating of the main room is directly connected to
the outdoor unit.
▪ The room temperature of the main room is controlled by the user
interface used as thermostat.
▪ A thermostatic valve is installed before the underfloor heating in
each of the other rooms.
INFORMATION
Mind situations where the main room can be heated by
another heating source. Example: Fireplaces.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
▪Cost effective. You do NOT need an additional external room
thermostat.
▪Easy. Same installation as for one room, but with thermostatic
valves.
Underfloor heating or radiators – Multiple external
room thermostats
Setup
B C
A
e e
d
M1 M2
c
a
b
AMain leaving water temperature zone
BRoom 1
CRoom 2
aUser interface
bControl box
cBackup heater
dBypass valve
eExternal room thermostat
▪ For each room, a shut-off valve (field supplied) is installed to avoid
leaving water supply when there is no heating or cooling demand.
▪ A bypass valve must be installed to make water recirculation
possible when all shut-off valves are closed. To guarantee reliable
operation, provide a minimum water flow as described in table "To
check the water volume and flow rate" in "6.3 Preparing water
piping"on page23.
▪ The main user interface (connected to control box EKCB07CAV3)
decides the space operation mode. Mind that the space operation
mode of the additional user interfaces (used as room thermostat)
must be set to match that of the main user interface.
▪ The room thermostats are connected to the shut-off valves, and
do NOT have to be connected to the outdoor unit. The outdoor
unit will supply leaving water all the time, with the possibility to
program a leaving water schedule.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
0 (LWT control): Unit operation is
decided based on the leaving
water temperature.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
Compared with underfloor heating or radiators for one room:
▪Comfort. You can set the desired room temperature, including
schedules, for each room via the room thermostats.

5 Application guidelines
Installer reference guide
16
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
Heatpump convectors – Multiple rooms
Setup
B
A
d d
C
b
a
c
AMain leaving water temperature zone
BRoom 1
CRoom 2
aUser interface
bControl box
cBackup heater
dRemote controller of the heatpump convectors
▪ The desired room temperature is set via the remote controller of
the heatpump convectors.
▪ The main user interface (connected to control box EKCB07CAV3)
decides the space operation mode.
▪ The heating demand signals of each heat pump convector are
connected in parallel to the digital input on control box
EKCB07CAV3 (X2M/1 and X2M/2). The outdoor unit will only
supply leaving water temperature when there is an actual
demand.
INFORMATION
To increase comfort and performance, Daikin recommends
to install the valve kit option EKVKHPC on each heatpump
convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
1 (Ext RT control): Unit operation
is decided by the external
thermostat.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main
Benefits
Compared with heatpump convectors for one room:
▪Comfort. You can set the desired room temperature, including
schedules, for each room via the remote controller of the
heatpump convectors.
Combination: Underfloor heating + Heatpump
convectors – Multiple rooms
Setup
e
B C
A
d
M1
M1
b
a
c
AMain leaving water temperature zone
BRoom 1
CRoom 2
aUser interface
bControl box
cBackup heater
dExternal room thermostat
eRemote controller of the heatpump convectors
▪ For each room with heat pump convectors: The heat pump
convectors are directly connected to the outdoor unit.
▪ For each room with underfloor heating: Two shut-off valves (field
supply) are installed before the underfloor heating:
▪ A shut-off valve to prevent hot water supply when the room has
no heating demand
▪ A shut-off valve to prevent condensation on the floor during
cooling operation of the rooms with heatpump convectors.
▪ For each room with heat pump convectors: The desired room
temperature is set via the remote controller of the heat pump
convectors.
▪ For each room with under floor heating: The desired room
temperature is set via the external room thermostat (wired or
wireless).
▪ The main user interface (connected to control box EKCB07CAV3)
decides the space operation mode. Mind that the operation mode
of each external room thermostat and heat pump convector
remote controller must be set to match that of the main user
interface.
INFORMATION
To increase comfort and performance, Daikin recommends
to install the valve kit option EKVKHPC on each heatpump
convector.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
0 (LWT control): Unit operation is
decided based on the leaving
water temperature.
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
0 (1 LWT zone): Main

5 Application guidelines
Installer reference guide
17
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
5.2.3 Multiple rooms – TwoLWT zones
If the heat emitters selected for each room are designed for different
leaving water temperatures, you can use different leaving water
temperature zones (maximum 2).
In this document:
▪ Main zone = Zone with the lowest design temperature in heating,
and the highest design temperature in cooling
▪ Additional zone = Zone with the highest design temperature in
heating, and the lowest design temperature in cooling.
NOTICE
If there are two leaving water temperature zones, and an
external room thermostat is used, then cooling operation is
NOT possible.
CAUTION
When there is more than one leaving water zone, you must
ALWAYS install a mixing valve station in the main zone to
decrease (in heating)/increase (in cooling) the leaving
water temperature when the additional zone has demand.
Typical example:
Room (zone) Heat emitters: Design
temperature
Living room (main zone) Underfloor heating: 35°C
Bed rooms (additional zone) Heatpump convectors: 45°C
Setup
B
A
f f
C
E
D
a
e
d
b
c
AAdditional leaving water temperature zone
BRoom 1
CRoom 2
DMain leaving water temperature zone
ERoom 3
aUser interface
bControl box
cBackup heater
dPressure-regulating valve
eMixing valve station
fRemote controller of the heatpump convectors
INFORMATION
A pressure regulating valve should be implemented before
the mixing valve station. This is to guarantee the correct
water flow balance between the main leaving water
temperature zone and the additional leaving water
temperature zone in relation to the required capacity of
both water temperature zones.
▪ For the main zone:
▪ A mixing valve station is installed before the underfloor heating.
▪ The room temperature is controlled by the user interface, which
is used as room thermostat.
NOTICE
Daikin is NOT responsible for the operation of the mixing
valve station pump. It is the responsibility of the installer to
guarantee pump operation.
▪ For the additional zone:
▪ The heat pump convectors are directly connected to the
outdoor unit.
▪ The desired room temperature is set via the remote controller of
the heatpump convectors for each room.
▪ The heating or cooling demand signals of each heat pump
convector are connected in parallel to the digital input on control
box EKCB07CAV3 (X2M/1 and X2M/2). The outdoor unit will
only supply the desired additional leaving water temperature
when there is an actual demand.
▪ The main user interface (connected to control box EKCB07CAV3)
decides the space operation mode. Mind that the operation mode
of each heat pump convector remote controller must be set to
match that of the main user interface.
Configuration
Setting Value
Unit temperature control:
▪ #: [A.2.1.7]
▪ Code: [C-07]
2 (RT control): Unit operation is
decided based on the ambient
temperature of the user interface.
Note:
▪ Main room = user interface
used as room thermostat
functionality
▪ Other rooms = external room
thermostat functionality
Number of water temperature
zones:
▪ #: [A.2.1.8]
▪ Code: [7-02]
1 (2 LWT zones): Main +
additional
In case of heatpump convectors:
External room thermostat for the
additional zone:
▪ #: [A.2.2.5]
▪ Code: [C-06]
1 (Thermo ON/OFF): When the
used external room thermostat or
heatpump convector can only
send a thermo ON/OFF
condition. No separation between
heating or cooling demand.
Shut‑off valve If the main zone must be shut off
during cooling mode to prevent
condensation on the floor, set it
accordingly.
At the mixing valve station Set the desired main leaving
water temperature for heating
and/or cooling.
Benefits
▪Comfort.
▪ The smart room thermostat functionality can decrease or
increase the desired leaving water temperature based on the
actual room temperature (modulation).
▪ The combination of the two heat emitter systems provides the
excellent heating comfort of the under floor heating, and the
excellent cooling comfort of the heatpump convectors.

5 Application guidelines
Installer reference guide
18
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
▪Efficiency.
▪ Depending on the demand, the outdoor unit supplies different
leaving water temperature matching the design temperature of
the different heat emitters.
▪ Underfloor heating has the best performance with Altherma LT.
5.3 Setting up the domestic hot water
tank
5.3.1 System layout – Standalone DHW tank
FHL1 FHL2 FHL3
M
a b ce
d
i
f
g
d
h
j
k
aOutdoor unit
bHeat exchanger
cPump
dShut‑off valve
eBackup heater (option)
fControl box
gUser interface
hMotorised 3‑way valve
iDomestic hot water tank
jHeat exchanger coil
kCollector (field supply)
FHL1...3 Underfloor heating
5.3.2 Selecting the volume and desired
temperature for the DHW tank
People experience water as hot when its temperature is 40°C.
Therefore, the DHW consumption is always expressed as equivalent
hot water volume at 40°C. However, you can set the DHW tank
temperature at a higher temperature (example: 53°C), which is then
mixed with cold water (example: 15°C).
Selecting the volume and desired temperature for the DHW tank
consists of:
1 Determining the DHW consumption (equivalent hot water
volume at 40°C).
2 Determining the volume and desired temperature for the DHW
tank.
Determining the DHW consumption
Answer the following questions and calculate the DHW consumption
(equivalent hot water volume at 40°C) using typical water volumes:
Question Typical water volume
How many showers are needed
per day?
1shower = 10min×10l/min =
100l
How many baths are needed per
day?
1bath = 150l
How much water is needed at the
kitchen sink per day?
1sink = 2min×5l/min = 10l
Are there any other domestic hot
water needs?
—
Example: If the DHW consumption of a family (4 persons) per day
is as follows:
▪ 3 showers
▪ 1 bath
▪ 3 sink volumes
Then the DHW consumption = (3×100l)+(1×150l)+(3×10l)=480l
Determining the volume and desired temperature for the DHW
tank
Formula Example
V1=V2+V2×(T2−40)/(40−T1) If:
▪ V2=180l
▪ T2=54°C
▪ T1=15°C
Then V1=280l
V2=V1×(40−T1)/(T2−T1) If:
▪ V1=480l
▪ T2=54°C
▪ T1=15°C
Then V2=307l
V1DHW consumption (equivalent hot water volume at 40°C)
V2Required DHW tank volume if only heated once
T2DHW tank temperature
T1Cold water temperature
Possible DHW tank volumes
Type Possible volumes
Standalone DHW tank ▪ 150l
▪ 180l
▪ 200l
▪ 250l
▪ 300l
▪ 500l
Energy saving tips
▪ If the DHW consumption differs from day to day, you can program
a weekly schedule with different desired DHW tank temperatures
for each day.
▪ The lower the desired DHW tank temperature, the more cost
effective. By selecting a larger DHW tank, you can lower the
desired DHW tank temperature.
▪ The heatpump itself can produce domestic hot water of maximum
55°C (50°C if outdoor temperature is low). The electrical
resistance integrated in the heat pump can increase this
temperature. However, this consumes more energy. Daikin
recommends to set the desired DHW tank temperature below
55°C to avoid using the electrical resistance.
▪ The higher the outdoor temperature, the better the performance of
the heatpump.
▪ If energy prices are the same during the day and the night,
Daikin recommends to heat up the DHW tank during the day.
▪ If energy prices are lower during the night, Daikin recommends
to heat up the DHW tank during the night.
▪ When the heatpump produces domestic hot water, it cannot heat
up a space. In case you need domestic hot water and space
heating at the same, Daikin recommends to produce the domestic
hot water during the night when there is lower space heating
demand.

5 Application guidelines
Installer reference guide
19
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
5.3.3 Setup and configuration – DHW tank
▪ For large DHW consumptions, you can heat up the DHW tank
several times during the day.
▪ To heat up the DHW tank to the desired DHW tank temperature,
you can use the following energy sources:
▪ Thermodynamic cycle of the heatpump
▪ Electrical booster heater
▪ For more information about:
▪ Optimizing the energy consumption for producing domestic hot
water, see "8Configuration"on page42.
▪ Connecting the electrical wiring of the domestic hot water tank
to control box EKCB07CAV3, see the installation manual of the
domestic hot water tank.
▪ Connecting the water piping of the domestic hot water tank to
the outdoor unit, see the installation manual of the domestic hot
water tank.
5.3.4 DHW pump for instant hot water
Setup
c
e
a
f
d
b
h
g
aOutdoor unit
bDomestic hot water tank
cDomestic hot water pump
dControl box
eShower
fCold water
gDomestic hot water OUT
hRecirculation connection
▪ By connecting a DHW pump, instant hot water can be available at
the tap.
▪ The DHW pump and the installation are field supply and the
responsibility of the installer.
▪ For more information about the recirculation connection, see
"7.7.9To connect the domestic hot water pump"on page39, and
the installation manual of the domestic hot water tank.
Configuration
▪ For more information, see "8Configuration"on page42.
▪ You can program a schedule to control the DHW pump via the
user interface. For more information, see the user reference
guide.
5.3.5 DHW pump for disinfection
Setup
c
j
b
ad f
ie g
h
aOutdoor unit
bDomestic hot water tank
cDomestic hot water pump (field supply)
dHeater element (field supply)
eNon‑return valve (field supply)
fShower (field supply)
gCold water
hDomestic hot water OUT
iRecirculation connection
jControl box
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ The temperature of the DHW tank can be set to a maximum of
75°C (if [E-07]=0) or 80°C (if [E-07]=5). If the applicable legislation
requires a higher temperature for disinfection, you can connect a
DHW pump and heater element as shown above.
▪ If applicable legislation requires disinfection of the water piping
until the tapping point, you can connect a DHW pump and heater
element (if needed) as shown above.
▪ For more information about the recirculation connection, see
"7.7.9To connect the domestic hot water pump"on page39, and
the installation manual of the domestic hot water tank.
Configuration
The outdoor unit can control DHW pump operation. For more
information, see "8Configuration"on page42.
5.3.6 DHW pump for tank preheating
Setup
c
i
b
ae
hdf
g
aOutdoor unit
bDomestic hot water tank
cDomestic hot water pump (field supply)
dNon‑return valve (field supply)
eShower (field supply)
fCold water
gDomestic hot water OUT
hRecirculation connection
iControl box
▪ The DHW pump is field-supplied and its installation is the
responsibility of the installer.
▪ For the standalone DHW tank: If there is no electrical backup
heater in the space heating circuit, you must install a DHW pump
for tank preheating.
Configuration
The outdoor unit can control DHW pump operation. For more
information, see "8Configuration"on page42.
5.4 Setting up the energy metering
▪ Via the user interface, you can read out the following energy data:
▪ Produced heat
▪ Consumed energy
▪ You can read out the energy data:
▪ For space heating
▪ For space cooling
▪ For domestic hot water production
▪ You can read out the energy data:
▪ Per month
▪ Per year
INFORMATION
The calculated produced heat and consumed energy are
an estimation, the accuracy cannot be guaranteed.

5 Application guidelines
Installer reference guide
20
EBLQ+EDLQ011~016CA3V3+W1 + EK(2)CB07CAV3
Daikin Altherma low temperature monobloc
4P538847-1 – 2018.05
5.4.1 Produced heat
INFORMATION
The sensors used to calculate the produced heat are
calibrated automatically.
INFORMATION
If glycol is present in the system ([E‑0D]=1]), then the
produced heat will NOT be calculated, nor will it be
displayed on the user interface.
▪ Applicable for all models.
▪ The produced heat is calculated internally based on:
▪ The leaving and entering water temperature
▪ The flow rate
▪ The power consumption of the booster heater (if applicable) in
the domestic hot water tank
▪ Setup and configuration:
▪ No additional equipment needed.
▪ Only in case a booster heater is present in the system, measure
its capacity (resistance measurement) and set the capacity via
the user interface. Example: If you measure a booster heater
resistance of 17.1Ω, the capacity of the heater at 230 V is
3100W.
5.4.2 Consumed energy
You can use the following methods to determine the consumed
energy:
▪ Calculating
▪ Measuring
INFORMATION
You cannot combine calculating the consumed energy
(example: for backup heater) and measuring the
consumed energy (example: for outdoor unit). If you do so,
the energy data will be invalid.
Calculating the consumed energy
▪ The consumed energy is calculated internally based on:
▪ The actual power input of the outdoor unit
▪ The set capacity of the booster heater and the optional backup
heater
▪ The voltage
▪ Setup and configuration: To get accurate energy data, measure
the capacity (resistance measurement) and set the capacity via
the user interface for:
▪ The optional backup heater (step1 and step2)
▪ The booster heater
Measuring the consumed energy
▪ Preferred method because of higher accuracy.
▪ Setup and configuration:
▪ Requires option box EK2CB07CAV3.
▪ Requires external power meters.
▪ When using electrical power meters, set the number of pulses/
kWh for each power meter via the user interface.
INFORMATION
When measuring the electrical power consumption, make
sure ALL power input of the system is covered by the
electrical power meters.
5.4.3 Normal kWh rate power supply
General rule
One power meter that covers the entire system is sufficient.
Setup
▪ Install control box EKCB07CAV3 and option box EK2CB07CAV3.
▪ Connect the power meter to X2M/7 and X2M/8 of option box
EK2CB07CAV3.
Power meter type
In case of … Use a… power meter
Single-phase outdoor unit (V3) Single-phase
Three-phase outdoor unit (W1) Three-phase
Example
Single-phase power meter Three-phase power meter
b
580150
0
0
c c
fd g
A B C D
a
c
he
A Outdoor unit
B Control box
C DHW tank
D Option box
a Electrical cabinet (L1/N)
b Power meter (L1/N)
c Fuse (L1/N)
d Outdoor unit (L1/N)
e Backup heater (L1/N)
f Control box (L1/N)
g Booster heater (L1/N)
h Option box (L1/N)
b
580150
0
0
ge
B
d c
a
h
C
i
D
A
c
f
A Outdoor unit
B Control box
C DHW tank
D Option box
a Electrical cabinet (L1/L2/L3/N)
b Power meter (L1/L2/L3/N)
c Fuse (L1/N)
d Fuse (L1/L2/L3/N)
e Outdoor unit (L1/L2/L3/N)
f Backup heater (L1/N)
g Control box (L1/N)
h Booster heater (L1/N)
i Option box (L1/N)
Exception
▪ You can use a second power meter if:
▪ The power range of one meter is insufficient.
▪ The electrical meter cannot easily be installed in the electrical
cabinet.
▪ 230 V and 400 V three-phase grids are combined (very
uncommon), because of technical limitations of power meters.
▪ Connection and setup:
▪ Connect the second power meter to X2M/9 and X2M/10 of
option box EK2CB07CAV3.
▪ In the software the power consumption data of both meters is
added so you do NOT have to set which meter covers which
power consumption. You only need to set the number of pulses
of each power meter.
▪ See "5.4.4 Preferential kWh rate power supply" on page 21 for
an example with two power meters.
Other manuals for Altherma EBLQ011CA3V3
1
This manual suits for next models
13
Table of contents