
iom-clim-cf-eng www.clima-ex.com
12
FLOW SWITCH
All chillers require a chilled water flow switch to verify that there
is adequate water flow through the evaporator and to shut down
the unit if necessary to prevent evaporator freeze-up under low or
no flow conditions.
A factory-installed thermal dispersion flow switch will be installed
on packaged models. On remote evaporator models, the flow
switch can be supplied separately in the field, or optionally
shipped loose for field installation. Terminals for field mounting
and wiring of the water flow switch are provided in the unit control
center.
Wire from the Y and R terminals on the switch to the terminals
on the unit control panel shown in the field wiring diagrams, page
23 through page 34. Mount the flow switch on the outlet water
line to shut off the unit when water flow is interrupted. A flow
switch is an equipment protection control and should never be
used to cycle the unit. Installation should be in accordance with
the manufacturer’s instructions included with the switch. Flow
switches should be calibrated to shut the unit off when operating
below the minimum flow rate.
There is also a set of paddle switch contacts on the switch that
can be used for an indicator light or alarm to indicate when a “no
flow” condition exists. Protect any flow switch that is installed
outdoors from freezing. It is not recommended that differential
pressure switches be installed outdoors. They may freeze and
not indicate a no-flow condition.
Protect any flow switches that are installed outdoors from freezing.
It is not recommended to install differential pressure switches
outdoors. They may freeze and not indicate a no-flow condition.
GLYCOL SOLUTIONS
The use of glycol can affect system performance depending on
its concentration and should be taken into account during initial
system design. When glycol is added to the chilled water system
to protect against freezing, it should be noted that the refrigerant
suction pressure will be lower, the cooling performance will
be lower and the water side pressure drop will be higher. The
reduction in performance depends on the glycol concentration
and temperature. Test the coolant with a clean and accurate
glycol refractometer to determine the freezing point.
! CAUTION !
The installed glycol level must match the nominal glycol
percentage indicated on the submitted chiller technical data
sheet. Failure to meet the nominal glycol percentage may
result in damage to the unit and loss of unit warranty.
! CAUTION !
Do not use automotive grade antifreeze. Industrial grade
glycols should be used. Automotive antifreeze contains
inhibitors that will cause plaque formation on the cooler
evaporator copper tubes. The type and handling of the glycol
used should be consistent with local codes.
If the chiller is not allowed to control the pump, the following
problems may occur:
1. If the chiller attempts to start without first starting the pump,
the chiller will lock out with the no flow alarm and require a
manual restart.
2. If the chiller evaporator water temperature drops below the
“freezing set point”, the chiller will attempt to start the water
pumps to prevent the evaporator from freezing.
3. If the chiller does not have the ability to start the pumps, the
chiller will alarm for lack of water flow.
4. If the chiller does not have the ability to control the pumps
and the water system must not be drained in sub-zero tem-
peratures or contain glycol, the chiller may be subject to ca-
tastrophic evaporator failure due to freezing. The evaporator
freeze-up rate is based on the evaporator heater and pump
operation. The external brazed plate heater alone may not
be able to adequately protect the evaporator from freezing
without water circulation.
The standard CLIM Series chiller coils have an aluminum
alloy microchannel design with a series of flat tubes containing
multiple parallel flow microchannels placed between the coolant
manifolds. The microchannel coils are designed to withstand the
synthetic acidified seawater acidified (SWAAT) mist test of over
1000 hours (ASTM G85-02) at 120°F (49°C) with 0% loss and
without developing leaks.
Epoxy coating: is an extremely flexible and durable water-based
polymer coating that is uniformly applied to all coil surfaces by
a multi-step electrostatic submerged coating process. Epoxy-
coated coils offer ASTM B117-90 salt spray resistance of more
than 10,000 hours, applied to both the coil and the coil heads.
Epoxy-coated coils also receive a UV-resistant urethane topcoat
to provide superior resistance to degradation from direct sunlight.
Table 3. Coil and liner selection matrix
Coil Option Non-
corrosive¹
Unpolluted
marine² Industrial³
Combined
marine-
Standard
Microchannel +++ - - -
Epoxy
Coated coils +++ +++ +++ ++
NOTES:
1. Non-corrosive environments can be estimated by the
appearance of existing equipment in the immediate area
where the chiller is to be placed.
2. -
mity to the coast, as well as the prevailing wind direction.
3. Industrial contaminants can be general or localized, de-
pending on the immediate source of contamination (e.g.
4. The marine-industrial combination is influenced by
proximity to the coast, prevailing winds, and general and
localized sources of pollution.
Considerations