Danfoss Termix AT BTD User manual

Operatingguide
TermixATBTD
1.0TableofContents
1.0TableofContents.............................................1
2.0Functionaldescription......................................2
3.0Safetynotes.....................................................3
3.1SafetyNotes–general............................................3
4.0Mounting........................................................4
4.1Mounting...........................................................4
4.2Start-up..............................................................5
5.0MountinginstructionsTermixATBTDwall
cabinet............................................................6
5.1Mounting...........................................................6
6.0Design.............................................................8
6.1DesignTermixATBTD5pipes...................................8
6.2SchematicdiagramTermixATBTD5Pipes....................9
6.3DesignTermixATBTD4pipes...................................10
6.4SchematicdiagramTermixATBTD4Pipes....................11
7.0Controls..........................................................12
7.1DHWtemperaturecontrol........................................12
7.2Other.................................................................13
7.3Maintenance........................................................14
8.0Troubleshooting..............................................15
8.1Troubleshootingingeneral......................................15
8.2TroubleshootingDHW............................................15
8.3Disposal.............................................................16
9.0Declaration......................................................19
9.1Declarationofconformity........................................19
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT1

OperatingguideTermixATBTD
2.0Functionaldescription
Districtheatingsubstationwithtankfordomestichotwater
preparationandwiththermostaticcontrol.Designedfor
wall-mounting.
Application
TheTermixATBTDsubstationisacompletesolutionforhot
water.TheTermixATBTDisapplicableforsingle-familyhouses
orapartments.
Domestichotwater(DHW)
Thedomestichotwatercircuitconsistsofahotwatertankwithcoil
andself-actingthermostaticcontrolvalve.Thehotwatertankand
coilareenamelledandthetankcontainsamagnesiumanode.The
substationisdeliveredwithabuiltinsafetyvalve.
2DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
3.0Safetynotes
3.1SafetyNotes–general
Thefollowinginstructionsrefertothestandarddesignof
substation.Specialversionsofsubstationsareavailableon
request.
Thisoperatingmanualshouldbereadcarefullybeforeinstallation
andstart-upofthesubstation.Themanufactureracceptsno
liabilityfordamageorfaultsthatresultfromnon-compliancewith
theoperatingmanual.Pleasereadandfollowalltheinstructions
carefullytopreventaccidents,injuryanddamagetoproperty.
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleasecomplywiththeinstructionsissuedbythesystem
manufacturerorsystemoperator.
Corrosionprotection
Allpipesandcomponentsaremadeofstainlesssteelandbrass.
Themaximumchloridecompoundsoftheowmediumshouldnot
behigherthan150mg/l.
Theriskofequipmentcorrosionincreasesconsiderablyifthe
recommendedlevelofpermissiblechloridecompoundsis
exceeded.
Energysource
Thesubstationisdesignedfordistrictheatingastheprimary
sourceofenergy.However,alsootherenergysourcescanbeused
wheretheoperatingconditionsallowitandalwaysarecomparable
todistrictheating.
Application
Thesubstationisdesignedtobeconnectedtothehouse
installationinafrost-freeroom,wherethetemperaturedoesnot
exceed50°Candthehumiditydoesnotexceed60%.Donotcover
orwallupthesubstationorinanyotherwayblocktheentrance
tothestation.
Choiceofmaterial
Choiceofmaterialsalwaysincompliancewithlocallegislation.
Safetyvalve(s)
Werecommendmountingofsafetyvalve(s),however,alwaysin
compliancewithlocalregulations.
Connection
Thesubstationmustbeequippedwithfeaturesthatensurethat
thesubstationcanbeseparatedfromallenergysources(also
powersupply).
Emergency
Incaseofdangeroraccidents-re,leaksorotherdangerous
circumstances-interruptallenergysourcestothestationif
possible,andseekexperthelp.
Incaseofdiscolouredorbad-smellingdomestichotwater,closeall
shut-offvalvesonthesubstation,informtheoperatingpersonnel
andcallforexperthelpimmediately.
Storage
Anystorageofthesubstationwhichmaybenecessarypriorto
installationshouldbeinconditionswhicharedryandheated.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
Pleaseobserveinstructionscarefully
Toavoidinjurytopersonsanddamagetothedevice,itisabsolutely
necessarytoreadandobservetheseinstructionscarefully.
Warningofhighpressureandtemperature
Beawareoftheinstallation’spermissiblesystempressureand
temperature.
Themaximumtemperatureoftheowmediuminthesubstationis
120°C.
Themaximumoperatingpressureofthesubstationis10bar.PN16
versionsareavailableonenquiry.
Theriskofpersonsbeinginjuredandequipmentdamagedincreases
considerablyiftherecommendedpermissibleoperatingparameters
areexceeded.
Thesubstationinstallationmustbeequippedwithsafetyvalves,
however,alwaysinaccordancewithlocalregulations.
Warningofhotsurface
Thesubstationhasgothotsurfaces,whichcancauseskinburns.
Pleasebeextremelycautiousincloseproximitytothesubstation.
Powerfailurecanresultinthemotorvalvesbeingstuckinopen
position.Thesurfacesofthesubstationcangethot,whichcancause
skinburns.Theballvalvesondistrictheatingsupplyandreturnshould
beclosed.
Warningoftransportdamage
Beforesubstationinstallation,pleasemakesurethatthesubstation
hasnotbeendamagedduringtransport.
IMPORTANT-Tighteningofconnections
Duetovibrationsduringtransportallangeconnections,screwjoints
andelectricalclampandscrewconnectionsmustbecheckedand
tightenedbeforewaterisaddedtothesystem.Afterwaterhasbeen
addedtothesystemandthesystemhasbeenputintooperation,
re-tightenALLconnections.
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT3

OperatingguideTermixATBTD
4.0Mounting
4.1Mounting
Installationmustbeincompliancewithlocalstandardsand
regulations.
Districtheating(DH)-Inthefollowingsections,DHreferstothe
heatsourcewhichsuppliesthesubstations.Avarietyofenergy
sources,suchasoil,gasorsolarpower,couldbeusedasthe
primarysupplytoDanfosssubstations.Forthesakeofsimplicity,
DHcanbetakentomeantheprimarysupply.
Connectionsizes:
Allconnections:G¾”(int.thread)
Dimensions(mm):
Withcover:
100L:H1180xW540xD520
150L:H1510xW540xD520
Weight(approx.):85–100kg
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
TermixATBTD5pipes
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
TermixATBTD4pipes
Thepipeplacementcandeviatefromtheshowndrawing.Pleasenote
themarkingsonthestation.
4DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
4.1.1Installation
Mounting:
Adequatespace
Pleaseallowadequatespacearoundthesubstationformounting
andmaintenancepurposes.
Orientation
Thestationmustbemountedsothatcomponents,keyholes
andlabelsareplacedcorrectly.Ifyouwishtomountthestation
differentlypleasecontactyoursupplier.
Drillings
Wheresubstationsaretobewall-mounted,drillingsareprovided
inthebackmountingplate.Floormountedunitshavesupport.
Labelling
Eachconnectiononthesubstationislabelled.
Beforeinstallation:
Cleanandrinse
Priortoinstallation,allsubstationpipesandconnectionsshouldbe
cleanedandrinsed.
Tightening
Duetovibrationduringtransport,allsubstationconnectionsmust
becheckedandtightenedbeforeinstallation.
Unusedconnections
Unusedconnectionsandshut-offvalvesmustbesealedwitha
plug.Shouldtheplugsrequireremoval,thismustonlybedoneby
anauthorizedservicetechnician.
Installation:
Strainer
Ifastrainerissuppliedwiththestationitmustbettedaccording
toschematicdiagram.Pleasenotethatthestrainermaybe
suppliedloose.
Connections
Internalinstallationanddistrictheatingpipesconnectionsmustbe
madeusingthreaded,angedorweldedconnections.
4.2Start-up
Start-up,Directheating
Theshut-offvalvesshouldbeopenedandtheunitobservedas
itentersservice.Visualcheckingshouldconrmtemperatures,
pressures,acceptablethermalexpansionandabsenceofleakage.
Iftheheatexchangeroperatesinaccordancewithdesign,itcanbe
puttoregularuse.
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
Re-thightenconnections
Afterwaterhasbeenaddedtothesystemandthesystemhasbeen
putintooperation,re-tightenALLconnections.
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT5

OperatingguideTermixATBTD
5.0MountinginstructionsTermixATBTDwallcabinet
5.1Mounting
Wallbracket
MounttheWallbracketaccordingtotheDrawing.
UseAtocenterthetankonthebracket.
B-AllpipethreadsareISO½” .
Mountthecontainerunitinthewallbracket.
6DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
Sideplates
Fastentherightandleftsideplatesbyplacingthekeyholesover
thescrewsonthesidesofthewallbracket.
1Bottompanel
Slidetheslotsinthebottompanelontothe2bushesintheside
plates,andfastenthepanelwiththe2screwsinthefront.
2Topplate
Mountthetopplate.
3Frontcover
Mountthefrontcoverbyloweringthekeyholesontothescrews
inthesideplates.
4Clockpanel
Mounttheclockpanelbyloweringthekeyholesontothescrews
inthesideplates.
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT7

OperatingguideTermixATBTD
6.0Design
6.1DesignTermixATBTD5pipes
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
EHotwatertankwithcoil4Safetyvalve
SSiphon20Filling/drainvalve
1ABallvalve,DVGW41AFittingpiece,coldwatermains
2Singlecheckvalve59Differentialpressure/temperatureregulatorwithowlimiting
8DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
6.2SchematicdiagramTermixATBTD5Pipes
DHW
DCW
CWM
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
EHotwatertankwithcoil4Safetyvalve
1Ballvalve20Filling/drainvalve
1ABallvalve,DVGW41AFittingpiece,coldwatermains
2Singlecheckvalve59Differentialpressure/temperatureregulatorwithowlimiting
DHW:DomesticHotWater
DCW:DomesticColdWater
CWM:Coldwatermains
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT9

OperatingguideTermixATBTD
6.3DesignTermixATBTD4pipes
Yoursubstationmightlookdifferentthanthesubstationshown.
Designdescription
EHotwatertankwithcoil4Safetyvalve
SSiphon20Filling/drainvalve
1ABallvalve,DVGW59Differentialpressure/temperatureregulatorwithowlimiting
2Singlecheckvalve
10DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
6.4SchematicdiagramTermixATBTD4Pipes
DHW
DCW
DH
Supply
DH
Return
Yoursubstationmightlookdifferentthantheschematicdiagramshown.
Schematicdescription
EHotwatertankwithcoil4Safetyvalve
1Ballvalve20Filling/drainvalve
1ABallvalve,DVGW59Differentialpressure/temperatureregulatorwithowlimiting
2Singlecheckvalve
DHW:DomesticHotWater
DCW:DomesticColdWater
DHSupply:DistrictHeatingSupply
DHReturn:DistrictHeatingReturn
6.4.1Technicalparameters
Technicalparameters
Nominalpressure:PN10
Max.DHsupplytemperature:T–max=95°C
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT11

OperatingguideTermixATBTD
7.0Controls
7.1DHWtemperaturecontrol
DHWtemperaturecontrol
TherearevarioustypesofDHWtemperaturecontrolusedin
Danfosssubstations.
DHWtemperatureshouldbeadjustedto45-50°C,asthisprovides
optimalutilisationofDHwater.AtDHWtemperaturesabove55°C,
thepossibilityoflimescaledepositsincreasessignicantly.
7.1.1AB-QMcontroller(45–60°)
QTisaself-actingthermostaticactuatordesignedtobeused
asreturntemperaturecontrolthermostatinone-pipeheating
systems.
QTisdedicatedtobeusedwithAB-QMautomaticbalancing&
controlvalve.
AB-QMDN10-20(45-60°C)
QTSensorsetting(turns)
Temperaturesetting0123456
20%48,050,553,055,558,060,563,0
30%47,049,552,054,557,059,562,0
40%46,048,551,053,556,058,561,0
50%45,047,550,052,555,057,560,0
60%44,046,549,051,554,056,559,0
70%43,045,548,050,553,055,558,0
80%42,044,547,049,552,054,557,0
90%41,043,546,048,551,053,556,0
AB-QM(ow
setting)
100%40,042,545,047,550,052,555,0
Thevaluesareintendedasaguide.
12DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
7.2Other
7.2.1Coldwatermeterttingpiece
Thesubstationisequippedwithattingpieceforcoldwatermeter.
Assemblyofcoldwatermeter:
1:Closeballvalves
Closetheballvalvesoncoldwater,ifthereiswateronthesystem.
2:Loosennuts
Loosenthenutsonthettingpiece.
3:Removettingpiece
Removethettingpieceandreplaceitwiththecoldwatermeter.
Donotforgetthegaskets.
4:Tightenconnections
Aftermountingofthecoldwatermeterremembertocheckand
tightenallthreadedconnections.
7.2.2Siphon
PlacedtheSiphondirectlyundertheSafetyvalve.
Ensurethatthedrainpipehasaminimuminternaldiameterof
32mm.
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT13

OperatingguideTermixATBTD
7.3Maintenance
Thesubstationrequireslittlemonitoring,apartfromroutine
checks.Itisrecommendedtoreadtheenergymeteratregular
intervals,andtowritedownthemeterreadings.
RegularinspectionsofthesubstationaccordingtothisInstruction
arerecommended,whichshouldinclude:
Strainers
Cleaningofstrainers.
Meters
Checkingofalloperatingparameterssuchasmeterreadings.
Temperatures
Checkingofalltemperatures,suchasDHsupplytemperatureand
DHWtemperature.
Connections
Checkingallconnectionsforleakages.
Safetyvalves
Theoperationofthesafetyvalvesshouldbecheckedbyturning
thevalveheadintheindicateddirection.
Venting
Checkingthatthesystemisthoroughlyvented.
Inspectionsshouldbecarriedoutminimumeverytwoyears.
SparepartscanbeorderedfromDanfoss.Pleaseensurethatany
enquiryincludesthesubstationserialnumber.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
14DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
8.0Troubleshooting
8.1Troubleshootingingeneral
Intheeventofoperatingdisturbances,thefollowingbasicfeatures
shouldbecheckedbeforecarryingoutactualtroubleshooting:
•thesubstationisconnectedtoelectricity,
•thestrainerontheDHsupplypipeisclean,
•thesupplytemperatureoftheDHisatthenormallevel
(summer,atleast60°C-winter,atleast70°C),
•thedifferentialpressureisequaltoorhigherthanthenormal
(local)differentialpressureintheDHnetwork–ifindoubt,ask
theDHplantsupervisor,
•pressureonthesystem-checktheHEpressuregauge.
Authorizedpersonnelonly
Assembly,start-upandmaintenanceworkmustbeperformedby
qualiedandauthorizedpersonnelonly.
8.2TroubleshootingDHW
ProblemPossiblecauseSolution
Strainerinsupplyorreturnlineclogged.Cleanstrainer(s).
DHWcirculationpumpoutoforderorwith
toolowsetting.
Checkcirculationpump.
Defectiveorcloggednon-returnvalve.Replace–clean.
Noelectricity.Check.
Wrongsettingofautomaticcontrols,ifany.Toadjustanelectroniccontrollerfor
DHW,pls.noteenclosedinstructionsfor
electroniccontroller.
Scalingoftheplateheatexchanger.Replace–rinseout.
Defectivemotorizedvalve.Check(usemanualfunction)–replace.
Defectivetemperaturesensors.Check–replace.
ToolittleornoDHW.
Defectivecontroller.Check–replace.
DCWisbeingmixedwiththeDHW,e.g.in
adefectivethermostaticmixingvalve.
Check–replace. Hotwaterinsometapsbutnotinall.
Defectiveorcloggednon-returnvalveon
circulationvalve.
Replace–clean.
Taptemperaturetoohigh;DHWtapload
toohigh.
Thermostaticvalveadjustedtoatoohigh
level.
Check–set.
Scalingoftheplateheatexchanger.Replace–rinseout. Temperaturedropduringtapping.
LargerDHWowthanthesubstationhas
beendesignedfor.
ReduceDHWow.
ThermostaticcontrolvalvedoesnotcloseTemperaturedifferencebetweenDH
supplyandDHWsetpointtoolow.
Lowerthesetpointtemperatureor
increasetheDHsupplytemperature.
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT15

OperatingguideTermixATBTD
8.3Disposal
Disposal
Thisproductshouldbedismantledanditscomponents
sorted,ifpossible,invariousgroupsbeforerecycling
ordisposal.
Alwaysfollowthelocaldisposalregulations.
16DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT17

OperatingguideTermixATBTD
18DEN-GTVI.JV.Y3.02/LUK40692DanfossDistrictEnergy

OperatingguideTermixATBTD
9.0Declaration
9.1Declarationofconformity
Category0withoutelectricalequipment
DanfossDistrictEnergyVI.JV.Y3.02/LUK40692DEN-GT19

OperatingguideTermixATBTD
ProducedbyDanfossA/S©10/2017
Table of contents
Other Danfoss Boiler manuals
Popular Boiler manuals by other brands

Viessmann
Viessmann Vitodens 100-W manual

Viessmann
Viessmann VITODENS 200 WB2 Series installation instructions

Sime
Sime FORMAT DGT 25/55 manual

Sime
Sime RX 19 installation instructions

Hoval
Hoval Max-3 plus Series Technical information and assembly instructions

HydroTherm
HydroTherm HeatNet KN-16 Field assembly instructions

Protherm
Protherm 65 Manual for instruction and use

IBC
IBC DC Series User's information manual

Viessmann
Viessmann Vitodens 300 Service instructions

Laars
Laars newport Installation, operation and maintanance

HTP
HTP MODCON500 LP Installation, start-up, maintenance, parts, warranty

Orlanski
Orlanski ORLIGNO 100 MANUAL AND SERVICE MANUAL