DANLERS CZ HB ND 10VDC Quick start guide

Installation notes
DANLERS Limited, Vincients Road, CHIPPENHAM, Wiltshire, SN14 6NQ, UK.
Telephone: +44 (0)1249 443377 Fax: +44 (0)1249 443388
Company Registered Number 2570169 VAT Registration Number 543 5491 38
Products available from DANLERS
• PIR occupancy switches • Daylight linked dimmers • Manual high frequency dimmers
• Photocells • Radio remote controls • Time lag switches • Outdoor security switches
• Dimmers • Heating, ventilation and air-conditioning controls • Bespoke / O.E.M. products
Please call for more information or a free catalogue, or visit our website.
This product conforms to BS EN 60669-2-1, BS EN 55015 and BS EN 60730.
Please ensure the most recent edition of the appropriate local wiring regulations are observed
and suitable protection is provided (protected with the appropriate MCB) 1kV over voltage.
Please ensure that this device is disconnected from the supply if an insulation test is made.
This product is covered by a warranty which extends to 5 years from the date of manufacture.
Precautions and Warranty
15/09/16 INS315 CZ HB (xx) 10VDC
ControlZAPP high bay controls for 1-10VDC ballasts
CZ HB ND 10VDC CZ HB SP 10VDC CZ HB WD 10VDC
ControlZAPP high bay passive infra-red occupancy switches (PIR) can be mounted
directly onto solid ceilings or onto a range of different mounting boxes (diagram
A). These PIR switches incorporate a passive infra-red quad sensor to detect
movement of a warm body within their detection zone (diagram B) and a photocell
to monitor the ambient light level.
ALL adjustments are made via a freely downloadable ControlZAPP App
available from the DANLERS website.
If the control is set as PIR with LUX input, upon detecting movement, if the ambient
light is dark enough, the ControlZAPP device will turn the load ON. The ambient
threshold can be set to between approximately 30 lux to 1000 lux and innite lux
(photocell inactive) via the ‘Respond to Daylight’ settings on the ControlZAPP App.
If no more movement is detected within a pre-selected time as determined by the
ControlZAPP App, then the ControlZAPP device will turn the load off. This ‘Time
Off Timeout’ or time lag can be set via the ControlZAPP App adjuster between
10sec and 23hrs 59min 59sec.
These high bay controls are available in three types - each with a particular
detection pattern which is optimised for particular applications.
CZ HB ND 10VDC: Narrow Detection version is ideal for covering storage aisles.
CZ HB SP 10VDC Spot Detection version is ideal for smaller areas,
such as the entrances to storage aisles.
CZ HB WD 10VDC: Wide Detection version is ideal for large open areas,
such as factories, sports halls and entrance halls.
Loading
The controls are suitable for switching and dimming 1-10VDC ballasts. They can
control up to 20mA, eg. 20 ballasts at 1mA (varies according to make and model of
ballasts). They can also switch up to:
• 10 amps (3000W) of resistive loads
• 6 amps (1500W) uorescent lamps, high frequency or switch start,
incandescent or mains halogen lamps (recommended with integral safety fuse)
• 3 amps (750W) of electronic or wire wound transformers.
• 2 amps (500W) of low energy lamps: CFL, LED, 2D etc.
• 1 amp (250W) of fans or most metal halide lamps.
Start-up and default settings
When the control is powered up, it will take 1 minute for the circuitry to stabilise
(detection LED ashing) and ensure the output is off, the control will then enter its
Default Operating Mode.
Please Note: When in the Default Operating Mode the control is set up as an
occupancy switch with a 20 minute turn OFF timeout (time lag) and photocell
disabled.
Variants
DANLERS design and manufacture other ControlZAPP high bay variants, coded by
the following order codes:
CZ HB (xx) Suitable for mains switching
CZ HB (xx) 1DALI Suitable for DALI ballasts
Troubleshooting
The load will not switch on:
• The LUX setting as specied by the ControlZAPP App is set too low and is
inhibiting the switch.
• The moving body is not emitting more IR than the background.
(Person wearing insulating clothing in a warm environment)
• Person is too far from the PIR switch, see detection diagram.
• Person is moving unusually slowly (perhaps when testing).
• The control unit battery is not engaged (ON).
Switch RED dip switch next to the telejack connector on the CZ HB (xx) 10VDC
control unit towards the centre of the control (see diagram D).
The load switches on when nobody is present:
• Heater causing infra-red variations in a small cold room.
Resite the CZ HB (xx) 10VDC control away from heater.
• Please contact DANLERS for further technical support.

Installation procedure
1. Please read these notes carefully before commencing work. In case of doubt
please consult a qualied electrician. Ensure wires and cables are securely held
within the connection terminals.
IMPORTANT: The CZ HB (xx) 10VDC Control Unit clock battery must be
engaged (ON) prior to installation by switching the RED dip switch (see
diagram D) to the DOWN position.
2. POSITIONING: The CZ HB (xx) 10VDC switch should be installed to achieve
correct coverage of the area, see diagram B. If the photocell override facility
(enabled via ControlZAPP app) is required, the switch must be located above an
area where daylight can give greater illumination than the articial light. Avoid
locating this product where it is exposed to drafty conditions (exposed lobbies,
open ceiling voids or near fans) or near heat sources.
3. Disconnect the ControlZAPP device from the circuit before performing insulation
testing of the wiring circuit.
4. Do not connect on a circuit with large inductive loads, as induced spikes may
cause false triggering or damage the device.
5. CZ HB (xx) 10VDC must be connected to the ControlZAPP Power Supply (CZPS)
via the ControlZAPP communication cable (telejack)provided, for wiring see
diagrams C and D. NOTE: The use of non ControlZAPP connectors may damage
the CZ HB (xx) 10VDC or CZPS and will invalidate the warranty).
6. Knockout or drill the appropriate holes on the mounting plate for attaching
the plate to the ceiling or back box (if applicable). Feed telejack through the
appropriate (side or rear) entry hole. Screw the back mounting plate to the ceiling
or back box via the mounting holes. Push the telejack connector into the sensor
head terminal. Push the sensor head onto the mounting plate and align the side
clips with the slots on the sensor heads.
Settings and calibration
NOTE: ALL settings are adjusted by ControlZAPP App as specied in the
ControlZAPP App User Guide (downloadable from the DANLERS website)
including: MODE settings, SCHEDULER settings and photocell settings and
intelligent photocell calibration procedure.
MODE settings include: Detect Movement (enable or disable), Sensitivity, Short
Visit Mode (with timer), Turn ON automatically (Presence detection or Absence
detection), Turn OFF timeout (from10sec to 23hrs 59min 59sec), Respond to
Daylight (enabled or disabled) the calibration process must be run for the intelligent
photocell to work. Delay before ON or Delay before OFF timers, Scene Recall (ON
or OFF).
SCHEDULER settings include:
DAY TYPES (dening times for each of the different Modes to occur).
WEEKLY SCHEDULE (dening which Day Types are assigned to different days of
the week).
EXCEPTIONS (dening exceptions to the schedule such as holidays).
VIEW ON CALENDAR (overview of schedule).
L
N
100 - 260VAC
50/60Hz
CZ HB (XX) 10VDC
+
ballast
-
control lines
NSL
+
_
Optional
other load
+
ballast
-
+
ballast
-
SL
L
L
N
+
-
Telejack connector
Control Unit
Power Supply
Red dip switch (MUST be
switched towards centre of control)
to engage clock battery ON
IMPORTANT
ON
D: Connector diagram
Up to 5m
diameter
Up to 3m
NARROW
DETECTION (ND)
Mounting height
up to 12m
Perspective view -
ceiling mounted
Up
to
15m
SPOT
DETECTION (SP)
Mounting height
up to 20m
Perspective view -
ceiling mounted
Up to 28m
diameter
WIDE
DETECTION (WD)
Mounting height
up to 14m
Perspective view -
ceiling mounted
A: Detection diagrams
C: Mounting plate xing
B: Wiring diagram
Knock out mounting
holes or pre-drill
pilot holes.
For telejack entry from
above - knock out
central mounting hole
For side entry -
knock out side
mounting hole
Clip telejack into the device
then join device to mounting
plate via mounting clips
This manual suits for next models
2