Data Aire dap4 touch User manual

DataAiredap4Controller
MODBUSTCP/IP
ProtocolIntegrationInstructions
DataAire,Inc.
230WestBlueRidgeAve,
Orange,CA92865
Documentnumber:600‐000‐961
November2012
Revision4.0

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.02
TableofContent
I. ModbusTCP/IP‐SetupProceduresfordap4EthernetCard………………………………page3
II. ModbusTCP/IPBMSPoints…………………………………………………………………………....page6

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.03
I. Modbus TCP/IP - Setup Procedures for dap4 Ethernet Card
Note: When connecting to the Ethernet card, a crossover cable must be used
1. Configure BMS PORT 1 into “BACnet TCP IP” protocol in menu G: Network Config of the
dap4 controller.
2. All Ethernet cards were set up for a DHCP server. You must give the card its factory IP
address to access the card and then switch it to the Ethernet protocol.
3. To do a factory reboot of the card, shut of power to the dap4 controller. Next, press and hold
the button on the card. Now, power on the dap4 controller. Wait approximately 20 seconds
until the status LED begins to blink red 3 times slowly. After the first Red blink, release the
push button. After releasing the button, wait approximately 50 seconds and the card is now
able to be communicated to.
4. The default settings for the card are as follows.
IP address – 172.16.0.1 Net Mask – 255.255.0.0 Device Inst - 77000
5. Once you have reset the Ethernet card, you must now configure your network card in your
PC to 172.16.0.*
* any value other then 1.
6. After your PC’s network card is configured, open Internet Explorer and enter the card’s IP
address (172.16.0.1.)
7. The following prompt will be displayed on your PC’s Screen (user name – admin, password –
fadmin)

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.04
8. After entering the correct information to log on to the Ethernet card, you will be taken to the
following screen.
9. Click the configuration tab on the left. Then click on the BACnet tab across the top of the screen.
10. This field is where you can change the settings for the card. The device instance of the card is
changed beside the pCOWeb Device Inst text. Each card must have its own unique device
instance.

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.05
11. The variable ranges can be set on the same page. Scroll to the bottom to change these ranges.
12. After you have set up your card, click Submit.
13. After your changes have been accepted, you may now change you IP address (if applicable.)
While still under the configuration tab, click network across the top of the screen.
14.
15. Under Eth0, change the IP address and Netmask to your desired values.
16. Scroll to the bottom of the screen and click submit.
17. It will take approximately 5 minutes for the IP address change to take
18. If there is no communication between the card and the BMS network, the Push Button can be
used to recall the factory setting configuration of the card: With the controller powered OFF,
turn the power ON while pressing and holding the push button. The status LED will blink red
and green rapidly for about 3 seconds, after that, it will stay as green. Wait for about 15
seconds, the LED will turn red. At this point, release the Push Button immediately. Lastly,
wait another 30 seconds for the controller to start up and establish the connection. When
started in this mode, the BMS card is reset to original factory setting temporarily; it will revert
to custom configuration (if any) after a reboot.

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.06
II. Modbus TCP/IP Points List
Note: 1.Dividethevalueby10forthedecimalvaluereading.
2.Allpointsinthislistareappliedtodap4softwareversion1.11orlater.Somepointsarenotapplied
ifyouhaveolderdap4softwareversion.
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
1 Temperature of return air R Ret_Air_Tmp A 30002
2 Maximum Return air temp in last 24hrs R Maximum A 30003
3 Minimum Return air temp in last 24hrs R Minumum A 30004
4 Temperature setpoint R/W Temp_Setpoint A 40005
5 Amount from setpoint before a comp is staged on R/W Temp_Deadband A 40006
6 Humidity Sensor Calibration R Ain_offs A 30007
7 Return Temperature Sensor Calibration R Ain_offs A 30008
8 Temperature of chilled water* R CW_Tmp A 30009
9 Temperature of discharge air* R Disch_Air_Tmp A 30010
10 Discharge Temperature Sensor Calibration - Optional discharge air
temperature sensor required (B9)* R Ain_offs A 30011
11 Chilled Water Temperature Sensor Calibration - Optional chilled water
temperature sensor required (B10)* R Ain_offs A 30012
12 Temperature setpoint for Energy saver chilled water* R/W EngSaver_Setpoint A 40013
13 Value of the analog input* R Opt1_Analog A 30014
14 Value of the analog input* R Opt2_Analog A 30015
15 Value of the Auxillary analog* R Opt3_Analog A 30016
16 Value of the analog input* R Opt4_Analog A 30017
17 Analog Sensor 1 Minimum Value* R Y1 A 30018
18 Analog Sensor 1 Maximum Value* R Y2 A 30019
19 Analog Sensor 1 Calibration* R Ain_offs A 30020
20 Analog Sensor 2 Minimum Value* R Y1 A 30021
21 Analog Sensor 2 Maximum Value* R Y2 A 30022
22 Analog Sensor 2 Calibration* R Ain_offs A 30023
23 Analog Sensor 3 Minimum Value* R Y1 A 30024
24 Analog Sensor 3 Maximum Value* R Y2 A 30025
25 Analog Sensor 3 Calibration* R Ain_offs A 30026
26 Analog Sensor 4 Minimum Value* R Y1 A 30027
27 Analog Sensor 4 Maximum Value* R/W Y2 A 40028
28 Offset for Outside Air Humidity sensor* R/W Ain_offs A 40029
29 Temperature setpoint for cooling in economizer mode* R/W Econ_Cl_Setpoint A 40030
30 Temperature deadband for cooling in economizer mode* R/W Econ_Cl_Deadband A 40031
31 Temperature setpoint for heating in economizer mode* R/W Econ_Ht_Setpoint A 40032

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.07
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
32 Temperature deadband for heating in economizer mode* R/W Econ_Ht_Deadband A 40033
33 Amount temp must change for each stage of heat/cool* R/W Stage_sp A 40034
34 Dewpoint setpoint for economizer* R/W Dewpoint_Hi_SP A 40035
35 deadband of dewpoint for economizer* R Dewpoint_Hi_Dband A 30036
36 Lower limit of dewpoint for economizer* R/W Dewpoint_Lo_SP A 40037
37 deadband of low dewpoint for economizer* R Dewpoint_Lo_Dband A 30038
38 deadband of enthalpy for economizer* R Enthalpy_Deadband A 30039
39 Offset for Outside Air Temperature probe* R/W Ain_offs A 40040
40 Temperature of the outside air* R Outside_Temp A 30041
41 Dew point of outside air* R Outside_Dewpt A 30042
42 Dew point of return air* R Ret_Air_Dewpt A 30043
43 Setpoint for fan modulation by return or rack temperature* R/W RA_Fan_Setpoint A 40044
44 Amount from setpoint before fan starts ramping up* R/W RA_Fan_Deadband A 40045
45 The highest of the rack temp sensors connected to this unit* R Rack_Temp A 30046
46 The highest rack temp of all units in this zone* R Zone_Rack_Temp A 30047
47 Value of rack temperature sensor #1* R Rack_T1 A 30048
48 Value of rack temperature sensor #2* R Rack_T2 A 30049
49 Value of rack temperature sensor #3* R Rack_T3 A 30050
50 Temperature setpoint of the Zone Master* R Master_Temp_Setpoint A 30051
1 Lower limit alarm of discharge air temp* R/W Disch_Air_Lo_SP I 45002
2 Relative humidity displayed as xx% R Humidity_dis I 35003
3 Cooling Stages On = Cooling stages are currently on – This point applies to
DX unit only R Stages_On I 35004
4 Number of heat stages running R Heaters_On I 35005
5 Maximum humidity in last 24hrs R Maximum I 35006
6 Minimum humidity in last 24hrs R Minumum I 35007
7 Cooling Utilization Over Last Hour -Percentage of cooling is used in the last
hour of operation; this point applies to DX unit. R Comp_duty I 35008
8 Heating Utilization Over Last Hour -Percentage of heating is used in the
last hour of operation R Heat_duty I 35009
9 Humidifier Utilization Over Last Hour -Percentage of humidifier is used in
the last hour of operation R Hum_duty I 35010
10 Compressor 1 Runtime -This point applies to DX unit with one compressor
-high R C1_Hours_H I 35011
11 Compressor 1 Runtime -This point applies to DX unit with one compressor
-low R C1_Hours_L I 35012
12 Compressor 2 Runtime -This point applies to DX unit with dual compressor
- high R C2_Hours_H I 35013
13 Compressor 2 Runtime -This point applies to DX unit with dual compressor
- low R C2_Hours_L I 35014
14 Heater 1 Runtime - high R Ht1_Hours_H I 35015
15 Heater 1 Runtime - low R Ht1_Hours_L I 35016
16 Current second R CURRENT_SECOND I 35017

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.08
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
17 Current minute R CURRENT_MINUTE I 35018
18 Current hour R CURRENT_HOUR I 35019
19 Current day R CURRENT_DAY I 35020
20 Current month R CURRENT_MONTH I 35021
21 Current year R CURRENT_YEAR I 35022
22 Firestat setpoint R/W Firestat_SP I 45023
23 Humidity High limit alarm R/W Hum_Hi_SP I 45024
24 Return air temp High alarm limit R/W Ret_Air_Hi_SP I 45025
25 Humidity low limit alarm R/W Hum_Lo_SP I 45026
26 Return air temp Low alarm limit R/W Ret_Air_Lo_SP I 45027
27 Humidity deadband R/W Hum_deadband I 45028
28 humidity setpoint R/W Hum_setpoint I 45029
29 Time before the system starts up R/W Start_dly I 45030
30 Optional Alarm 1 Delay R Del I 35031
31 Optional Alarm 2 Delay R Del I 35032
32 Optional Alarm 3 Delay R Del I 35033
33 Message on optional alarm screen, some also add function R Alarm1_txt I 35034
34 Message on optional alarm screen, some also add function R Alarm2_txt I 35035
35 Message on optional alarm screen, some also add function R Alarm3_txt I 35036
36 Message on optional alarm screen, some also add function R Alarm4_txt I 35037
37 Comps 0=none, 1=one, 2=one+UL, 3=two, 4=two+UL, 5=Four/two circuit R Comp_sel I 35038
38 0=none, 1= comp limited, 2=twocomp limited, 3= comp unlimited,
4=twocomp unlimited R Dehum_mode I 35039
39 0=None, 1=one, 2=one elect, 3=two, 4=three, 5=three elect R Reheat_sel I 35040
40 0=none, 1=comp mod, 2=comp non, 3= comf mod, 4= conf non mod R Hum_sel I 35041
41 Custom message on alarm R Alm_Contact_msg I 35042
42 0= start wo/alarm, 1= start w/alarm, 2= requires reset of alarm R PowerUp_sel I 35043
43 0=None, 1=short beeps, 2=long beep, 3=Constant R Buzzer_Select I 35044
44 Chilled water valve open percentage R CW_disp I 35045
45 Chilled Water Utilization Over Last Hour - This applies to Chilled water or
Energy saver units. R WtrVlv_duty I 35046
46 Humidifier Runtime - high R Hum_Hours_H I 35047
47 Humidifier Runtime - low R Hum_Hours_L I 35048
48 Blower Runtime - high R Blower_Hours_H I 35049
49 Blower Runtime - low R Blower_Hours_L I 35050
50 Optional Alarm 4 Delay R Del I 35051
51 0= no comp assist, 1=one comp assist, 2= two comp assist, 3... 4... R Assist_sel I 35052
52 Water valve type 0=none, 1=chill, 2=Engy, 3=Aux chill, 4=Disc Reg R WtrVlv_sel I 35053
53 Water valve voltage 0= 0-10, 1=2-10, 2=7-10, 3=6-9, 4=4-7 R WtrVlv_Volts_sel I 35054
54 Modulating humidifier percentage* R Hum_Volts I 35055

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.09
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
55 Dehumidifier Runtime - High R Dehum_Hours_H I 35056
56 Dehumidifier Runtime - Low R Dehum_Hours_L I 35057
57 Fan pressure setpoint inches of water R/W Fan_Pr_sp_hi I 45058
58 Time between drain cycles 0=12hr, 1=24hr, 2=48hr, 3=96hr, 4=None R AutoFlush_dly I 35059
59 Value sent to optional analog output#1* R Y4_Out I 35060
60 Value sent to optional analog output#2* R Y5_Out I 35061
61 1/10th Current Fan Airflow - Based on calculated Pressure Diff formula* R Air_Flow I 35062
62 Name of the sensor 1* R Opt_Snsr1_name I 35063
63 Analog Sensor 1 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}* R Ain_type I 35064
64 Name of the sensor 2* R Opt_Snsr2_name I 35065
65 Analog Sensor 2 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}* R Ain_type I 35066
66 Name of the sensor #3* R Opt_Snsr3_name I 35067
67 Analog Sensor 3 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}* R Ain_type I 35068
68 Name of the sensor 4* R Opt_Snsr4_name I 35069
69 Analog Sensor 4 Type {0=NTC 1=PT1000 2=0-1VDC 3=0-10VDC 4=4-
20mA 5=ON/OFF 6=0-5VDC 7=NTC HT 8=-50T90 9=10T170}* R Ain_type I 35070
70 CW Fan speed (%) controlled by BMS R/W CW_Fan_Speed_bms I 45071
71 DX Fan speed (%) controlled by BMS R/W DX_Fan_Speed_bms I 45072
72 Maximum Fan speed (% of output) modulation. R/W Fan_Speed_max I 45073
73 Minimum Fan speed (% of output) modulation. R/W Fan_Speed_min I 45074
74 Fan pressure setpoint (0.001 inches of water)* R/W Fan_Pr_sp I 45075
75 Fan pressure band (0.001 inches of water)* R/W Fan_pr_band I 45076
76 Maximum air flow that the unit can deliver* R/W Fan_AF_max I 45077
77 Minimum air flow limit of setpoint from BMS or valve modulation.* R/W Fan_AF_min I 45078
78 Fan K Factor* R/W Fan_Kfactor I 45079
79 Number of fans installed in this unit* R/W Num_Fans I 45080
80 Minimum Damper (% of output) modulation for airside economizer*. R/W Damper_min I 45081
81 Heater 2 Runtime - high R Ht2_Hours_H I 35082
82 Heater 2 Runtime - low R Ht2_Hours_L I 35083
83 Heater 3 Runtime - high R Ht3_Hours_H I 35084
84 Heater 3 Runtime - low R Ht3_Hours_L I 35085
85 Energy Saver Runtime - This optional point applies to energy saver units
only -high* R Engy_Hours_H I 35086
86 Energy Saver Runtime - This optional point applies to energy saver units
only - low* R Engy_Hours_L I 35087
87 Chilled Water Runtime - This applies to chilled water units only - high R CW_Hours_H I 35088
88 Chilled Water Runtime - This applies to chilled water units only - low R CW_Hours_L I 35089
89 Compressor 3 Runtime - This applies when unit has four stages tandem
compressors - high R C3_Hours_H I 35090

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.010
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
90 Compressor 3 Runtime - This applies when unit has four stages tandem
compressors - low R C3_Hours_L I 35091
91 Compressor 4 Runtime - This applies when unit has four stages tandem
compressors. - high R C4_Hours_L I 35092
92 Compressor 4 Runtime - This applies when unit has four stages tandem
compressors. - low R C4_Hours_H I 35093
93 Condenser Runtime - high R Cond_Hours_H I 35094
94 Condenser Runtime - low R Cond_Hours_L I 35095
95 Constant Fan speed % of output in DX mode. R DX_Fan_Speed I 35096
96 Constant Fan speed % of output in chilled water cooling. R CW_Fan_Speed I 35097
97 Fan air flow setpoint (cfm) 1/10th scale* R Fan_AF_sp I 35098
98 Maximum damper (% of output) modulation in airside economizer*. R/W Damper_max I 45099
99 Zone Airflow Setpoint (1/100th of actual)* R/W ZM_Airflow_SP I 45100
100 Zone Airflow Setpoint from the server (LSB) 000-999* R/W Unity_Airflow_SP_lsb I 45101
101 Zone Airflow Setpoint from the server (1/100th actual cfm)* R/W Unity_Airflow_SP I 45102
102 1/10th of the total zone airflow* R ZM_Airflow I 35103
103 Economizer Runtime - high* R Econ_Hours_H I 35104
104 Economizer Runtime - low* R Econ_Hours_L I 35105
105 Relative humidity of the outside air in %* R Outside_Hum_dsp I 35106
106 Oustide air enthalpy in KJ or BTU* R Outside_Enthalpy I 35107
107 Return air enthalpy in KJ or BTU* R Return_Enthalpy I 35108
108 Analog value of damper in %* R Damper_Mod_disp I 35109
109 Fan speed modulation percentage (bases on output singal) R Fan_Out I 35110
110 Setting of HP alarms/hr before comp is locked out, 1=disabled* R/W HP_Lockout_Cnt I 45111
111 Number of HP alarms C1 had within an hour* R C1_HP_Count I 35112
112 Number of HP alarms C2 had within an hour* R C2_HP_Count I 35113
113 Number of units selected by ZM for standby based on current schedule* R Num_Stdby I 35114
114 Number of units currently running in the zone* R Num_Units_On I 35115
115 State of unit (at address 1). 1,12&13 = On, 2 thru 9 = Off* R Unit Status I 35116
116 State of U2 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit2_status I 35117
117 State of U3 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit3_status I 35118
118 State of U4 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit4_status I 35119
119 State of U5 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit5_status I 35120
120 State of U6 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit6_status I 35121
121 State of U7 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit7_status I 35122
122 State of U8 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit8_status I 35123
123 State of U9 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit9_status I 35124
124 State of U10 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit10_status I 35125
125 State of U11 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit11_status I 35126
126 State of U12 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit12_status I 35127
127 State of U13 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit13_status I 35128

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.011
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
128 State of U14 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit14_status I 35129
129 State of U15 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit15_status I 35130
130 State of U16 when zone master is enabled. (1,12&13 is running, 2-9 is Off)* R Unit16_status I 35131
1 Dehumidify mode is running R Dehum_On D 10002
2 Humidifier is running R Hum_On D 10003
3 Energy saver is running R Engy_On D 10004
4 Cooling inhibit from Zone Master* R Cool_Inhibit D 10005
5 Heat inhibited due to alarm condition R Heat_Held D 10006
6 Humidifier stopped due to alarm R Humidifier_inhibit D 10007
7 Dehum is inhibited R Dehum_Inhibit D 10008
8 reheat during dehum R Rht_during_dehum D 10009
9 Water under floor alarm R Floor_Wtr_alm D 10010
10 No air flow alarm R Air_Flow_alm D 10011
11 Dirty filter from digital input R Filter_alm D 10012
12 Alarm from humidifier digital input* R Humidifier_alm D 10013
13 Temperature of return air above firestat alarm set point R Firestat_alm D 10014
14 One or more comps has short cycled R Shortcycle_alm D 10015
15 Sensor is out of range R Humidity_fail D 10016
16 Sensor is out of range R Ret_Air_fail D 10017
17 Maintenance Schedule Due alarm R Maint_alm D 10018
18 High pressure compressor 1 alarm R C1_HP_alm D 10019
19 Low pressure compressor 1 alarm R C1_LP_alm D 10020
20 High pressure compressor 2 alarm R C2_HP_alm D 10021
21 Low pressure compressor 2 alarm R C2_LP_alm D 10022
22 Smoke detected from digital input* R Smoke_alm D 10023
23 No water flow alarm (stays high 5min longer if set to lockout)* R Wtr_Flow_alm D 10024
24 Sensor is out of range R Disch_Air_fail D 10025
25 Temperature of return air above alarm set point R RA_Tmp_hi_alm D 10026
26 Temperature of return air below alarm set point R RA_Tmp_lo_alm D 10027
27 Humidity above alarm set point R Hum_hi_alm D 10028
28 Humidity below alarm set point R Hum_lo_alm D 10029
29 Fan motor overload* R Fan_Overload D 10030
30 Standby pump on: Check primary pump -Optional alarm. Pump failure input
signal required* R Stdby_Pump_On D 10031
31 Custom alarm #1 -Optional alarm. Custom message displayed* R Cust_msg_Sw1 D 10032
32 Custom alarm #2 -Optional alarm. Custom message displayed* R Cust_msg_Sw2 D 10033
33 Custom alarm #3 -Optional alarm. Custom message displayed* R Cust_msg_Sw3 D 10034
34 Custom alarm #4 -Optional alarm. Custom message displayed* R Cust_msg_Sw4 D 10035
35 Humidifier stopped due to custom alarm switch* R HumSw_Inhibit D 10036
36 Heat inhibited due to custom switch alarm condition* R Heat_inhibit D 10037

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.012
Point
IndexDescriptionRead/
WriteVariableNameData
Type
Modbus
TCP/IP
37 Reheat and humidification inhibited from operation* R Rht_Hum_inhibit D 10038
38 Temperature of discharge air below alarm set point* R Disch_Tmp_lo_alm D 10039
39 Manual override: Check bypass switches - Standard alarm. Manual
override switch is on R Override_Alm D 10040
40 High condensation from digital input* R Condensation_alm D 10041
41 Unit in standby, all functions held off - Optional alarm. Control input signal
required Factory setting required* R Unit_In_Standby D 10042
42 Sensor is out of range R CW_sns_fail D 10043
43 Humidifier stopped due to custom alarm switch* R HumSw_Chk_Cyl D 10044
44 Cooling operation inhibited by BMS R/W BMS_Cooling_inhibit D 00045
45 Heat inhibited due to bms* R/W BMS_Heat_inhibit D 00046
46 Humidifier operation inhibited by BMS* R/W BMS_Humidifier_inhibit D 00047
47 Dehumidify mode inhibited by bms* R/W BMS_Dehum_inhibit D 00048
48 Inhibit fan by bms* R/W Fan_Inhibit_bms D 00049
49 Reduces control humidity cycling* R Hum_Expect D 10050
51 Units of temperature 0=F, 1=C R/W USAshr_f_c D 00052
52 Lead compressor select 0= C1, 1= C2 R Lead_Comp D 10053
53 Water valve direct or reverse acting R WtrVlv_dir D 10054
54 Alarm: UPS power on: Check main power -Optional alarm. External alarm
input required* R Ups_On_alm D 10055
55 Loss of power requires manual reset of alarm R PwrUp_alm D 10056
56 Local alarm #1: See tag inside door R SeeTag_cust_alm1 D 10057
57 Local alarm #2: See tag inside door R SeeTag_cust_alm2 D 10058
58 Local alarm #3: See tag inside door R SeeTag_cust_alm3 D 10059
59 Local alarm #4: See tag inside door R SeeTag_cust_alm4 D 10060
60 Enable short cycle alarm of the compressors R ShortCycle_alm_en D 10061
61 Supervisor (BMS) On-Off. Show the state OFFbyBMS in main mask (1: Off;
0: On) R/W Superv_Off D 00062
62 This variable must change at least once a minute or unit will turn on R/W BMS_Heartbeat D 00063
63 HP count lockout reset (seperate from normal alarm resets)* R/W Lockout_Reset D 00064
64 C1 disabled due to excessive HP alarms* R C1_Lockout D 10065
65 C2 disabled due to excessive HP alarms* R C2_Lockout D 10066
66 On-Off unit state (0: Off; 1: On) R Sys_On D 10067
67 Fan running R Blower_On D 10068
*:Thesepointsareoptional–Optionalsensorsorcomponentsrequired

Data Aire’s dap4 Modbus TCP/IP
Document:600‐000‐961version4.013
Unit On code
1-On
12- RUNtoSTBy- On by ZoneMaster until unit setpoint is satisfied
13-ONbyZM- On by Zone Master
Unit Off code:
2-OFFbyALR -off by alarm that controlled by ZM
3-OFFbyZM- manually configured to off by ZM
4-OFFby BMS
5-OFFbySCH- off by scheduler
6-STBbyZM- send to standby mode by ZM
7-OFFbyKey
8-Override- OFF by manual override mode
9-STBY- OFF by optional standby input
0- unit off during starting delay countdown
Other manuals for dap4 touch
7
Other Data Aire Controllers manuals
Popular Controllers manuals by other brands

Tyco
Tyco iSTAR Ultra G2 SE quick start guide

Beam Labs
Beam Labs Pixelator Plus product manual

Yamaha
Yamaha RCX240 Supporting supplement manual

Thermal Dynamics
Thermal Dynamics IHC XT operating manual

Siemens
Siemens OpenAir G B181.1E/KN Series manual

Kutai electronics
Kutai electronics EA448B Operation manual

Carmanah
Carmanah SPEEDCHECK-12 Replacement guide

SanRex
SanRex CALPOTE UG Series instruction manual

oventrop
oventrop REGTRONIC PX Assembly and operating manual

EFI
EFI E-36A Installation and service guide

Ruckus Wireless
Ruckus Wireless ZoneDirector 1100 Configuration guide

DX Engineering
DX Engineering DXE-NCC-2 quick start guide