QLM500 INSTALLATION MANUAL 
7
 
PWR-IN 
 
PWR-IN is a 5-pin Male A-Coded M12 connector. Input power must only be supplied to the 
QLM500 at the PWR-IN connector; from there it is internally distributed to the connected 
reading device, the ID-NET™ network and all the I/O devices. 
 
You can use the CBL-1487 connector and follow the pinout above to build your own Power 
Supply connector cable. 
 
You can also use one of the CS-A2-02-G-xx cables which terminate in four single stranded 
wires. The brown wire corresponds to pin 1 Vdc, the blue wire to pin 3 GND. The white 
and black wires are not used. 
 
The LED placed below the PWR-IN connector, signals the presence of input Power. If the 
polarity is correct, the LED is blue; if the polarity is reversed, the LED is red; if no power is 
supplied, the LED is off. 
 
 
CAUTION 
The QLM500 and the connected reader are protected from polarity inversion 
through the PWR-IN connector, but this is not true for the other devices 
connected to the ID-NET™ Network, TRG and I/O connectors (i.e. external 
trigger, encoder, etc.). Check the correct Power Supply polarity looking at 
the PWR-IN LED before connecting other devices to the QLM500. 
 
The power supply must be between 10 and 30 Vdc only. 
 
 
Voltage Drop and Max Distributed Current Calculations 
 
For correct ID-NET™ network management, the maximum number of readers which can 
propagate power through the QLs must be calculated so that max distributed current is not 
exceeded (4.0 A), and so voltage drop doesn't affect reader functioning. This is done 
according to the following formula: 
 
Voltage Drop = (Max Reader Current x Number of readers) x 
(Resistance per Meter per wire* x Cable length in Meters) 
 
* the resistance calculation must include both wires (Vdc and GND). 
 
Example: 
An ID-NET™ network is composed of 4 DS2100N readers. Three 2-meter ID-NET™ cables 
are used to connect the readers, which have Cable Resistance = 0.058 Ohms per meter per 
wire. The network power is 24 Vdc. 
(0.125 A x 4 readers) x [(0.058 x 2) x 6 meters] = 0.348 Vdc voltage drop 
24 Vdc - 0.348 = 23.65 Vdc at reader number 4 (worst case) 
 
Integrate a sufficient number of QL200s to resupply network power. 
 
 
ID-NET 
 
ID-NET is a 5-pin Female A-Coded M12 connector. It is used to connect the network signals 
and the power supply for the ID-NET™ Network towards ID-NET™ Slaves.