ddtop TRG804X User manual

1/ 22
WWW.DDTOP.COM
TRG804X
RADAR LEVEL MITTER-6.3GHz
Operating Manual
TRG804X-DT-JS-1006-2018(A)

2/ 22
WWW.DDTOP.COM
PREFACE
Thank you for choosing the products of Dandong Top Electronics Instrument (Group)-Co.,Ltd.
This operation manual provides you with important information on installation, connection and
commissioning as well as on maintenance, troubleshooting and storage.
Please read it carefully before installation and commissioning and keep it as part of the product
near the meter for easy reading.
This manual can be downloaded by entering the version number at www.ddtop.com.
If the instructions are not followed, the protection provided by the meter may be destroyed.
Trademark, Copyright and Restriction Instructions
Dandong Top Electronics Instrument (Group) Co.,Ltd.®, Dandong Top Pump Co.,Ltd.®,
DDTOP® are registered trademarks of the company.
The performance specifications of the meter are effective as of the date of publication and are
subject to change without notice. Dandong Top Electronics Instrument (Group)Co.,Ltd. reserves the
right to modify the products described in this manual at any time without prior notice.
Quality Assurance
Dandong Top Electronics Instrument (Group) Co.,Ltd. guarantees that all variable area flow meters
have no defects in materials and manufacturing processes within one year from the date of delivery.
During the warranty period, if the product returns with quality problems and the claim is
determined by the manufacturer to be within the scope of warranty, Dandong Top Electronics
Instrument (Group) Co.,Ltd. is responsible for repair or replacement of the buyer (or owner) free of
charge. Dandong Top Electronics Instrument (Group) Co.,Ltd. is not responsible for the costs caused
by improper use of equipment, labor claims, direct or subsequent damage and installation and use
of equipment. In addition to the special written warranty certificate for certain products of Dandong
Top Electronics Instrument (Group) Co.,Ltd., Dandong Top Electronics
Instrument (Group) Co.,Ltd. does not provide any express or implied warranty.

3/ 22
WWW.DDTOP.COM
Quality
Dandong Top Electronics Instrument (Group) Co.,Ltd. has passed the ISO9001 quality system
certification. The whole process of product production is strictly in accordance with the scope of
the quality system, providing the strongest guarantee for product and service quality.

4/ 22
WWW.DDTOP.COM
Content
1. Safety Tips..................................................................................................................................................................5
2. Product Descriptions ..............................................................................................................................................5
3. Technical Parameters .............................................................................................................................................6
4. Outline Dimension Diagram-Figure 3..............................................................................................................8
5. Unpacking and Inspection....................................................................................................................................9
6. Installation..................................................................................................................................................................9
7. Instrument Configuration................................................................................................................................... 11
8. Precautions ............................................................................................................................................................. 20
9. Fault Analysis and Troubleshooting ............................................................................................................... 21
10. Disassemble........................................................................................................................................................ 22
11. Product Certification........................................................................................................................................ 22

5/ 22
WWW.DDTOP.COM
1. Safety Tips
For safety reasons, it is expressly prohibited to modify or change the product without authorization.
Repair or replacement is only allowed to use the accessories specified by the manufacturer.
1.1 The explosion may cause death or serious injury.
When installing the device in an explosive environment, be sure to comply with applicable local,
national and international standards, codes and regulations. Ensure that the equipment is installed
in accordance with intrinsically safe or non-flammable site operating procedures.
1.2 Process leakage may cause serious injury or death.
If the process seal is damaged, the medium may leak at the connection.
1.3 Failure to follow the safety installation guidelines may result in death or serious injury.
All operations described in this manual must be carried out by trained and qualified or
end-user-appointed personnel.
2. Product Descriptions
2.1 Main structure-Figure 1
Figure 1 Product Main Structure

6/ 22
WWW.DDTOP.COM
1. Transmitter, with circuit board module inside
2. Sealing component, with sealing structure inside
3. Flange, with flange installation on site
4. Antenna, selected according to site conditions
2.2 Working Principle
The radar antenna emits a very short microwave pulse with very low energy. The pulse propagates
in space at the speed of light and meets the surface of the measured medium. Part of its energy is
reflected back and received by the same antenna. The time interval between the transmitted pulse
and the received pulse is proportional to the distance from the antenna to the surface of the
measured medium, so that the distance from the antenna to the surface of the measured medium is
calculated.
2.3 Packaging
Please send packaging waste to a special recycling agency.
2.4 Lifting and Transportation
Please use quality lifting equipment and lifting straps, and pay attention to safety.
2.5 Storage
Storage temperature -20℃~40℃
Storage humidity≤40%
3. Technical Parameters
3.1 Key Performance
Power Supply:(16~36)V DC (two-wire)
Output: 4~20mA
Blind Zone: 400mm
Transmission Frequency: 6.3GHz
Structure: rod antenna, horn antenna

7/ 22
WWW.DDTOP.COM
Figure 2 Two-wire Load Resistance Diagram
3.2 Appearance and Performance Parameters
TRG8041-Apperance TRG8041- Performance parameter
TRG8042- Apperance TRG8042- Performance parameter
Antenna structure: Rod type
Application conditions: suitable for strong corrosive liquids,
simple process conditions
Measuring range: 10m
Measurement accuracy: ±10mm
Process temperature: (-40~120)℃
Process pressure: (-0.1~0.3) MPa
Antenna structure: horn type
Application conditions: temperature-resistant,
pressure-resistant, slightly corrosive liquid
Measuring range: 30m
Measurement accuracy: ±10mm or 0.1%FS
(whichever is greater)
Process temperature: (-40~200)℃
Process pressure: (-0.1~4.0) MPa

8/ 22
WWW.DDTOP.COM
3.3 Explosion-proof Mark
Passed the national explosion-proof certification, certification mark:
Intrinsically safe Ex ia IIC T1~T5/T6 Ga;Ex iaD 20 T85℃
Intrinsically safe and flameproof composite type Ex d ia [ia Ga]IIC T1~T5/T6 Gb;Ex tD A21 T100℃
/T85℃
3.4 Executive Standard
TRG804X Radar Level Transmitter Executive Standard
JB/T 13252-2017 Microwave (radar) level transmitter
4. Outline Dimension Diagram-Figure 3
If special size is required when ordering, the actual size shall prevail.
Figure 3 Outline Dimension

9/ 22
WWW.DDTOP.COM
5. Unpacking and Inspection
5.1 Precautions for Unpacking Inspection
5.1.1 Check whether the product nameplate (Figure 4) is consistent with the supply list information
Figure 4 Product Nameplate
5.1.2 Check the quantity and material of each part against the packing list.
5.2 Content of Inspection
5.2.1 Check whether the appearance of the meter is defective or damaged.
6. Installation
6.1 Installation Tool
Tools suitable for process connections like wrenches, flange gaskets and flange bolts.

10 / 22
WWW.DDTOP.COM
6.2 Installation Technical Requirements
Installation Location
During installation, take care to maintain a distance of at least 600 mm between the instrument and
the vessel wall, as shown in Figure 5.
①-Datum plane;
②-The center of the container or the axis of symmetry.
Figure 5 Schematic Diagram of Installation Position
For a cone-shaped container with a flat tank top, the best installation position of the meter is the
center of the top of the container, so that the bottom of the measuring container can be ensured, as
shown in Figure 6.
Figure 6 Diagram of Installation Position of Cone Bottom Tank

11 / 22
WWW.DDTOP.COM
Moisture proof
For installation in an outdoor or humid room and on a cooling or heating tank, in order to prevent
moisture, the cable gland should be tightened, and the cable should be bent downward at the inlet,
as shown in Figure 7.
Figure 7 Diagram of Moisture-proof Wiring
Container Tube Connection
The length of the container nozzle should be as long as possible to ensure that the end of the
antenna extends into the tank, as shown in Figure 8.
Figure 8 Diagram of Container Connecting Pipe Connection
7. Instrument Configuration
7.1 Electrical Wiring

12 / 22
WWW.DDTOP.COM
According to the wiring shown in Figure 9 below, terminal 2 is connected to 24VDC positive, and
terminal 1 is connected to 24VDC negative.
Figure 9 Electrical Wiring
7.2 Configuration Operation Process
7.2.1 Diagram of Parameter Setting-Figure 10
The reference surface of the measurement is the sealing surface of the thread or flange
①-Blind area;
②-Range setting;
③-High level adjustment;
④-Low level adjustment
Figure 10 Diagram of Parameter Setting
7.2.2 Introduction to Operation Interface
There are 4 buttons on the instrument panel (Figure 11), and the instrument can be configured

13 / 22
WWW.DDTOP.COM
through the 4 buttons. The language of the configuration menu is optional. After configuration, the
LCD screen displays the measured value, and the measured value can be read out very clearly
through the glass window.
Figure 11 Instrument Panel
Basic Settings
The basic settings include the basic parameters of the instrument: low level adjustment, high level
adjustment, material properties, damping time, output mapping, calibration unit, calibration, blind
zone range, sensor label.
Display
Display and set the display mode, display content and LCD contrast of the instrument.
Diagnose
Diagnosis completes the inspection and testing functions of the instrument. Mainly include:
measuring peak value, measuring state, selection curve, echo curve and simulation.
Service
Including false echo, current output, reset, measurement unit, language, HART working mode, copy
sensor data and password.
【BK】key
-Exit the programming state
-Back to the previous menu
-Display echo curve
【↑】key
-Modify parameter
value
【 】key
-Select programming items
-Select to edit parameter
bits
-Parameter item content
display
【OK】key
-Enter programming
state
-Confirm programming
-Confirm parameter
modification

14 / 22
WWW.DDTOP.COM
Information
Basic instrument information such as product model, serial number, production date, and software
version.
Programming method
When the instrument is running, press the OK key to enter the programming state and display the
programming main menu. After editing each parameter, press OK to confirm, otherwise the editing
is invalid. After finishing editing, press BK key to exit programming state and return to running state.
At any time during programming, you can press BK key to abandon programming and exit the
parameter item programming state.
7.2.3 Configuration steps
Basic settings
Basic settings include the settings of main instrument parameters, such as range, material properties,
damping time, etc. In the running state, press the OK key to enter the programming state, the LCD
displays the main menu, as shown in Figure 11-1 Basic Settings
11-1 Basic Setting
Low Level adjustment
Low level adjustment is used for range setting. Together with the high level adjustment, it
determines the ratio of the current output linear corresponding relationship. In the main menu,
when the menu number is 1, press the OK key to enter the basic setting sub-menu, LCD display, as
shown in Figure 11-2 low adjustment.

15 / 22
WWW.DDTOP.COM
11-2 Low Level Adjustment
Press OK to enter the programming low percentage, refer to the character/number parameter
programming method in the parameter editing method to edit the percentage value and distance
value. After editing, press OK key to confirm, press BK key to abandon programming.
High Level Adjustment
High level adjustment is used for range setting. Together with the low level adjustment, it
determines the ratio of the current output linear corresponding relationship. When the menu
number of the LCD display is 1.1, press the key to enter the high position adjustment, and the
LCD display is shown in Figure 11-3.
Figure 11-3 High Level Adjustment
At this point, press the OK key to edit the high adjustment.
Material Property
When the LCD display menu number is 1.2, press the key to enter the material property
programming, and the LCD will display, as shown in Figure 11-4. The material properties menu is
used to select solid, liquid or micro DK, so as to further determine other properties of the material

16 / 22
WWW.DDTOP.COM
that affect the measurement.
Figure 11-4 Material Property
Damping time
When the LCD display menu number is 1.3, press the key to enter the damping time setting
menu, the LCD displays, as shown in Figure 11-5 damping time.
11-5 Damping Time
Press the OK key to enter the parameter editing state, use the ↑ key to set the number, use the key
to select the edit digit, and press the OK key to confirm after editing.
Range setting
In order to get the correct measurement results, you need to set the range of the meter. When the
menu number is displayed as 1.7, press the key to enter the range setting menu, and the LCD
will display, as shown in Figure 11-6.
11-6 Measuring Range Setting

17 / 22
WWW.DDTOP.COM
Press the OK key, the corresponding parameter ± or reverse black, use the ↑ or key to set the
parameter, and press the OK key to confirm.
Blind Zone
When there is a fixed obstacle close to the sensor surface that interferes with the measurement, and
the maximum material height will not reach the obstacle, the blind zone range setting function can
be used to avoid measurement errors. When the LCD displays menu number 1.8, press the key
to enter the blind zone range setting menu, and the LCD displays, as shown in Figure 11-7 Blind
Zone Range.
11-7 Blind Zone
Press OK to enter the parameter editing state, and press OK to confirm after editing.
Display
This function is used for display mode programming. When the LCD displays the main menu, press
the key to move the arrow to the display item, and the LCD will display as shown in Figure
11-8.
11-8 Display

18 / 22
WWW.DDTOP.COM
Press the OK key to enter the display mode programming.
Display content
Enter display mode programming, LCD display, as shown in Figure 11-9.
11-9 Display Content
The parameter indicating the current display content is the empty height, that is, the meter displays
the measured empty height value. Press the OK key to enter the editing state, and the LCD will
display, as shown in figure 11-10.
11-10 Display Empty Height
Use the key to move the arrow to the desired parameter item and press OK to confirm.
When editing is complete, press the BK key to exit display programming and return to the previous
menu.
Service
The service menu includes more specialized functions. Mainly include false echo learning,
time-varying gain control, reset and instrument parameter storage. When the LCD displays the
main menu, press the key to move the arrow to the service item, and the LCD displays, as

19 / 22
WWW.DDTOP.COM
shown in Figure 11-11 Service.
11-11 Service
False Echo
When there is a fixed obstacle in the measurement range that interferes with the measurement, the
false echo learning function can be used to overcome its influence. When the main menu is
displayed on the LCD and the menu number is 4, press the OK key to enter the service submenu,
and the LCD will display as shown in Figure 11-12 false echo.
11-12 False Echo
Press the OK key, the LCD will display, as shown in Figure 11-13, the false echo sub-menu.

20 / 22
WWW.DDTOP.COM
11-13 False Echo Submenu
If you it is needed to update/create a new false echo curve, press the key, move the arrow to
the current new entry, press OK to confirm, and the LCD will display, as shown in Figure 11-14.
11-14 False Echo Update
Prompt to enter the true echo distance value. After entering the distance value, press the OK key to
confirm. Please wait for the LCD display.
8. Precautions
8.1 Make sure that the power supply is safe and reliable. The power supply must be connected in
accordance with the correct positive and negative poles, and the ground terminal of the
transmitter must be reliably grounded;
8.2 When installing the radar level transmitter, be careful not to install it above the material flow. If it
is unavoidable, it is recommended to install a still-wave tube or bypass tube for easy
measurement;
Table of contents
Popular Radar manuals by other brands

Dahua Technology
Dahua Technology DH-PFR4K-B240 user manual

K40 ELECTRONICS
K40 ELECTRONICS UNDETECTABLE K40-1000 owner's guide

Endress+Hauser
Endress+Hauser Micropilot FMR60B PROFIBUS PA operating instructions

Endress+Hauser
Endress+Hauser Levelflex M FMP45 operating instructions

MALA
MALA MIRA operating manual

Carmanah
Carmanah SPEEDCHECK 15 user manual

Hella Gutmann
Hella Gutmann CSC-Kit Radar III operating instructions

Endress+Hauser
Endress+Hauser Micropilot FMR56 technical information

Endress+Hauser
Endress+Hauser Levelflex FMP56 Brief operating instructions

Radenso
Radenso Pro M installation guide

Image Sensing Systems
Image Sensing Systems RTMS Echo user guide

Honeywell
Honeywell PRIMUS 660 Pilot's manual