Det-Tronics x2200 User manual

15.1 Rev: 1/16 95-8549
Instructions
UV Flame Detector
X2200

Table of Contents
DESCRIPTION ..............................1
Outputs ................................1
LED ...................................2
oi
(Optical Integrity) ......................2
Communication ..........................3
Data Logging ............................3
Integral Wiring Compartment................3
SIGNAL PROCESSING OPTIONS ..............3
GENERAL APPLICATION INFORMATION ........4
Response Characteristics ..................4
False Alarm Sources ......................4
Factors Inhibiting Detector Response .........4
IMPORTANT SAFETY NOTES .................5
INSTALLATION .............................6
Detector Positioning.......................6
Detector Orientation.......................6
Protection Against Moisture Damage .........7
Wiring Procedure .........................7
Setting Device Network Addresses
(EQ and EQP Models Only) ............13
STARTUP PROCEDURE .....................14
Fire Alarm Test..........................14
TROUBLESHOOTING .......................14
MAINTENANCE ............................14
Cleaning Procedure ......................15
oi
Plate Removal and Replacement .........15
Periodic Checkout Procedure ..............15
Clock Battery ...........................15
FEATURES ................................16
SPECIFICATIONS ..........................16
REPLACEMENT PARTS .....................18
Replacement Parts List ...................18
DEVICE REPAIR AND RETURN ...............18
ORDERING INFORMATION ..................18
Accessories ............................18
X2200 Model Matrix......................19
APPENDIX A – FM APPROVAL AND
PERFORMANCE REPORT ...................20
APPENDIX B – CSA APPROVAL...............24
APPENDIX C – ATEX APPROVAL..............25
APPENDIX D – IECEx APPROVAL .............27
APPENDIX E – EN54 APPROVALS.............28
APPENDIX F – ADDITIONAL APPROVALS ......29

195-854915.1
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X2200 includes the Automatic
oi
®(Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
DESCRIPTION
The X2200 UV Flame Detector meets the most stringent
requirements worldwide with advanced detection
capabilities and immunity to extraneous sources,
combined with a superior mechanical design. The
detector is equipped with both automatic and manual
oitest capability. The detector has Division and Zone
explosion-proof ratings and is suitable for use in indoor
and outdoor applications.
The standard output configuration includes fire, fault, and
auxiliary relays. Output options include:
– 0 to 20 mA output (in addition to the three relays)
– Pulse output for compatibility with existing Detector
Electronics Corporation (Det-Tronics) controller
based systems (with fire and fault relays)
– Eagle Quantum Premier®(EQP) compatible model
(no analog or relay outputs)
– HART communication
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm or
fault conditions.
The X2200 housing is available in copper-free aluminum
or stainless steel, with NEMA/Type 4X and IP66/IP67
rating.
OUTPUTS
Relays
The standard detector is furnished with fire, fault, and
auxiliary relays. All three relays are rated 5 amperes at
30 Vdc.
The Fire Alarm relay has redundant terminals and normally
open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.
INSTRUCTIONS
UV Flame Detector
X2200
©Detector Electronics Corporation 2016 Rev: 1/16

95-8549215.1
The Auxiliary relay has normally open / normally
closed contacts, and is configurable for energized or
de-energized operation, and latching or non-latching
operation.
0 to 20 mA Output
A 0 to 20 mA output is available as an option (in addition
to the three relays). This option provides a 0 to 20 mA dc
current output for transmitting detector status information
to other devices. The circuit can be wired in either an
isolated or non-isolated configuration and can drive
a maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc. Table1
indicates the detector status conditions represented by
the various current levels. The output is calibrated at the
factory, with no need for field calibration. A model with
relays and 0-20 mA with HART is also available. Refer to
Addendum number 95-8638 for complete details.
NOTE
The output of the 0 to 20 mA current loop is not
monitored by the fault detection circuitry of the
X2200. Therefore, an open circuit on the loop will
not cause the fault relay to change state or the
detector status LED to indicate a fault. The status
of the LED always follows the status of the relays.
An alarm condition will normally over-ride a fault condition,
unless the nature of the fault condition impairs the ability
of the detector to generate or maintain an alarm output,
i.e., loss of operating power.
LON/SLC Output
The EQP model is designed for use exclusively with
the Det-Tronics Eagle Quantum Premier system. The
detector communicates with the system controller over
a digital communication network or LON/SLC (Local
Operating Network / Signaling Line Circuit). The LON/
SLC is a fault tolerant, two wire digital communication
network arranged in a loop configuration. Analog and
relay outputs are not available on this model.
LED
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions.
Table2 indicates the condition of the
LED for each status.
ATTENTION
The X2200 contains a source tube that is filled
with a gas mixture containing Krypton 85 (Kr85) ,
a radioactive material. Radioactive materials are
subject to regulation under U.S. and international
law.
oi(OPTICAL INTEGRITY)
Automatic
oi
The X2200 includes the Automatic
oi
feature — a
calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform — once every minute, 60 times per
hour. However, a successful Automatic
oi
test does not
produce an alarm condition.
The detector signals a fault condition when less than half
of the detection range remains. This is indicated by the
Fault output and is evident by the yellow color of the LED
on the face of the detector. See the "Troubleshooting"
section for further information.
Table1—Detector Status Conditions Indicated by Current Level
Current Level (±0.3 mA) Detector Status
0 mA Power Fault
1 mA General Fault
2 mA
oi
Fault
4 mA Normal Operation
16 mA Pre-Alarm
20 mA Fire Alarm
Table2—Detector Status Indicator
Detector Status LED Indicator
Power On/Normal Auto
oi
(no fault or fire alarm) Green
Power On/Normal Man
oi
Green, flashing off for 0.5 sec.
every 5 sec.
Fault Yellow
Pre-Alarm/Background UV Red, flashing on for 1 sec. and
off for 1 sec.
Fire (Alarm) Steady Red
On Power-Up, The LED Flashes in Sequence as Follows,
Indicating Sensitivity and Signal Processing Status
Low UV Sensitivity
Medium UV Sensitivity
High UV Sensitivity
Very High UV Sensitivity
One Red Flash
Two Red Flashes
Three Red Flashes
Four Red Flashes
Stand. UV Signal Process.
Arc Rej. UV Signal Process.
One Yellow Flash
Two Yellow Flashes

395-854915.1
Magnetic
oi
/ Manual
oi
The detector also incorporates both Magnetic
oi
(Mag
oi
) and Manual
oi
(Man
oi
) features that
provide the same calibrated test as the Automatic
oi
, and in addition actuates the Alarm output to verify
operation for preventive maintenance requirements.
These features can be performed at any time and
eliminate the need for testing with a non-calibrated
external test lamp.
CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
The Mag
oi
test is performed by placing a magnet
at the location marked "MAG OI" on the outside
of the detector (see Figure 2). The Man
oi
test is
accomplished by connecting the
oi
lead (terminal
22) to power supply minus via an external switch. The
magnet or switch must be held in place for a minimum
of 6 seconds to complete the test. Either of these test
methods activates the calibrated UV emitter.
If the
resulting signal meets the test criteria, indicating that
greater than half of the detection range remains, the fire
alarm output of the detector is activated. This condition
remains until the magnet is removed or the switch is
released, regardless of whether the detector has been
configured for latching or non-latching operation.
If less than half of the detection range remains, no alarm
is produced and a fault is generated. The fault indication
can be reset by momentarily applying the Mag
oi
or Man
oi
switch. In this case, the detector's optics should be
cleaned and the
oi
tests should be repeated. See the
"Cleaning Procedure" section of this manual for details.
NOTE
Refer to Appendix A for FM verification of
the
oi
function.
COMMUNICATION
The X2200 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 supports MODBUS protocol, with
the detector configured as a slave device.
For HART communication, connect a HART communicator
across a 250 ohm resistor in the 0-20 mA loop.
NOTE
The EQP model uses LON/SLC communication.
RS-485 and HART communication are not
available on the EQP model.
DATA LOGGING
Data logging capability is also provided. Status conditions
such as normal, power down, general and oifaults, pre-
alarm, fire alarm, time, and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Inspector Connector accessory, RS-485, or the
EQP Controller.
INTEGRAL WIRING COMPARTMENT
All external wiring to the device is connected within
the integral junction box. The detector is furnished with
four conduit entries, with either 3/4 inch NPT or M25
threads.
SIGNAL PROCESSING OPTIONS
The UV detector output (measured in counts per second)
is compared to the fire threshold (the "sensitivity" setting).
If the radiant energy level from the fire exceeds the
selected alarm threshold level, the fire alarm output is
activated. In every application, it is crucial to ensure that
the radiant ultraviolet energy level from the expected fire
at the required distance from the detector will exceed the
selected sensitivity level.
The UV detector in the X2200 can be programmed for:
– Arc Rejection
– Standard Signal Processing
Arc Rejection
The Arc Rejection mode enables the detector to
prevent nuisance fire alarms caused by UV from short-
duration electrical arcs or electrostatic discharge,
while maintaining the ability to reliably detect the UV
radiation given off by a flame. Typical applications that
benefit from arc rejection logic include electrostatic
coating processes and uncontrolled environments where
transient UV sources can be present, such as many
typical outdoor applications. Most false alarm sources
have short transient UV signatures, while fire creates
a long UV signature over many seconds. Most fires
are detected in a few seconds (see response times in
Appendix A).
Standard Signal Processing
Standard signal processing is recommended for high-
speed suppression systems only. To allow for high-speed
operation, the standard processing mode does not
incorporate the arc rejection programming. This mode
should only be used in a controlled, indoor environment.

95-8549415.1
GENERAL APPLICATION
INFORMATION
RESPONSE CHARACTERISTICS
Response is dependent on the detector's sensitivity
setting, arc rejection, and time delay settings. Other
factors include distance, type of fuel, temperature of the
fuel, and time required for the fire to come to equilibrium.
As with all fire tests, results must be interpreted according
to an individual application.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.
Welding
Electric arc welding is a source of intense ultraviolet
radiation. UV radiation from arc welding readily scatters
and can deflect across significant distances, even when
direct obstructions exist. Any open door or window can
allow nuisance UV radiation from arc welding to enter an
enclosed area.
It is recommended that the system be bypassed during
welding operations in situations where the possibility of a
false alarm cannot be tolerated. Gas welding mandates
system bypass, since the gas torch is an actual fire.
Articial Lighting
The X2200 should not be located within 3 feet (0.9 m)
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
EMI/RFI Interference
The X2200 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE Marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot (0.3 m).
FALSE ALARM SOURCES
The UV sensor is solar blind to the ultraviolet component
of solar radiation. However, it may respond to sources of
UV besides fire, such as arc flash, electric arc welding,
grinding metal, lightning, high voltage corona, x-rays,
and gamma radiation.
FACTORS INHIBITING DETECTOR RESPONSE
Windows
Glass and Plexiglas windows significantly attenuate UV
radiation and must not be located between the detector
and a potential flame source. If the window cannot be
eliminated or the detector location changed, contact
Det-Tronics
for recommendations regarding window
materials that will not attenuate UV radiation.
Obstructions
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical
obstructions out of the line of view of the detector.
In addition, UV absorbing gases or vapors must not
be allowed to accumulate between the detector and
the protected hazard. See Table 3 for a list of these
substances.
Smoke
Smoke will absorb UV radiation. If accumulations
of dense smoke can be expected to precede the
presence of a flame, then detectors that are used
in enclosed areas should be mounted on the wall
approximately 3 feet (0.9 m) from the ceiling where
the accumulation of smoke is reduced.
Detector Viewing Windows
It is important to keep the detector viewing windows as
free of contaminants as possible in order to maintain
maximum sensitivity. Commonly encountered substances
that can significantly attenuate UV radiation include, but
are certainly not limited to, the following:
– Silicones
– Oils and greases
– Dust and dirt buildup
– Paint overspray

595-854915.1
IMPORTANT SAFETY NOTES
WARNING
Do not open the detector assembly in a hazardous
area when power is applied.The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage.
CAUTION
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If in
doubt, consult the authority having jurisdiction
before wiring the system. Installation must be done
by a properly trained person.
CAUTION
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing detection system tests or maintenance.
CAUTION
The UV ame detectors are to be installed in places
where the risk of mechanical damage is low.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
ATTENTION
The source tube is a flame-sealed gas tube
containing Neon, Hydrogen, and a trace amount
of Krypton 85 (Kr85), a radioactive material. The
total volume of gas within the tube is 0.6 ml per
tube, making the gas mixture inside the tube
nonflammable. If the gas envelope is broken, it
will not produce a ammable mixture, and the gas
immediately disperses into the air and is unlikely
to present any type of hazard. Krypton gas and its
radioactive isotope are inert and are not absorbed
by the body. No special handling measure or
personal protection equipment is needed for the
UV detectors.
The following is a partial list of compounds that exhibit
signicant UV absorption characteristics. These are
also usually hazardous vapors. While generally of little
consequence in small amounts, these gases can restrict
UV detection if they are in the atmosphere in heavy
concentrations. It should also be determined whether or
not large amounts of these gases may be released as a
result of a re-causing occurrence.
Acetaldehyde Methyl Methacrylate
Acetone Alpha-Methylstyrene
Acrylonitrile Naphthalene
Ethyl Acrylate Nitroethane
Methyl Acrylate Nitrobenzene
Ethanol Nitromethane
Ammonia 1-Nitropropane
Aniline 2-Nitropropane
Benzene 2-Pentanone
1,3 Butadiene Phenol
2—Butanone Pyridine
Butylamine Hydrogen Sulde
Chlorobenzene Styrene
1-Chloro-1-Nitropropane Tetrachloroethylene
Chloroprene Toluene
Cumene Trichloroethylene
Cyclopentadiene Vinyl Toluene
O-Dichlorobenzene Xylene
P-Dichlorobenzene
If UV-absorbing gases may be a factor in a given
application, precautionary measures should be taken.
Detectors can be placed closer to the potential hazard
area, and/or the sensitivity of the detection system can be
increased. Contact the factory for further details.
Substances such as methane, propane, butane, hexane,
camphor, and octane are not UV absorbing.
Table3—UV Absorbing Gases and Vapors

95-8549615.1
INSTALLATION
NOTE
The recommended lubricant for threads and
O-rings is a silicone-free grease (p/n 005003-
001) available from Det-Tronics. Under no
circumstances should a lubricant containing
silicone be used.
DETECTOR POSITIONING
Detectors should be positioned to provide the best
unobstructed view of the area to be protected.
The following factors should also be taken into
consideration:
• Identify all high risk fire ignition sources.
• Be sure that enough detectors are used to adequately
cover the hazardous area.
• Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
• Verify that all detectors in the system are properly
located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. The Q1201C Laser Aimer
is recommended for establishing the detector's
FOV. Refer to Appendix A for specific information
regarding detector range and FOV.
• The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.
• The detector must be mounted on a rigid surface in
a low vibration area.
• Dense fog, rain as well as certain gases and vapors
(see Table 3) can absorb UV radiation and reduce
the sensitivity of the detector.
• If possible, fire tests can be conducted to verify
correct detector positioning and coverage.
• For ATEX/IECEx installations, the X2200 Flame
Detector housing must be electrically connected to
earth ground.
DETECTOR ORIENTATION
Refer to Figure 2 and ensure that the
oi
plate will be
oriented as shown when the X2200 is mounted and
sighted. This will ensure proper operation of the
oi
system and will also minimize the accumulation of
moisture and contaminants between the
oi
plate and
the viewing windows.
IMPORTANT
If removed, the
oi
plate must be securely
tightened to ensure proper operation of the
oi
system (40 oz./inches [28.2 N .cm] recommended).
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
CENTER AXIS
OF DETECTOR
FIELD OF VIEW
INCORRECT
CORRECT
NOTE: DETECTOR MUST ALWAYS BE AIMED
DOWNWARD AT LEAST 10 TO 20 DEGREES.
D1974
Figure1—Detector Orientation Relative to Horizon
Figure2—Front View of the X2200
UV VIEWING WINDOW
oiPLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
oiMAGNET
DETECTOR
STATUS INDICATOR
B2171

795-854915.1
PROTECTION AGAINST MOISTURE DAMAGE
It is important to take proper precautions during
installation to ensure that moisture will not come in
contact with the electrical connections or components
of the system. The integrity of the system regarding
moisture protection must be maintained for proper
operation and is the responsibility of the installer.
If conduit is used, we recommend installing drains,
according to local codes, at water collection points
to automatically drain accumulated moisture. It is
also recommended to install at least one breather,
according to local codes, at upper locations to provide
ventilation and allow water vapor to escape.
Conduit raceways should be inclined so that water will
flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use
an IP66/IP67 washer to prevent water ingress.
WIRING PROCEDURE
Wire Size and Type
The system should be wired according to local
codes. The wire size selected should be based
on the number of detectors connected, the supply
voltage and the cable length. Typically 16 AWG or
2.5
mm2
shielded cable is recommended. Wires
should be stripped 3/8 inch (9 mm). A minimum input
voltage of 18 Vdc must be present at the X2200.
NOTE
Refer to “Power Consumption” in the
“Specications”section of this manual.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures 7
through 12, and Figure 15. Consult the factory if not using
shielded cable.
In applications where the wiring cable is installed in
conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.
WARNING
All entries must contain appropriately rated plugs
or ttings. It is required that each plug or tting be
wrench-tightened to an appropriate installation
torque and meet the minimum thread engagement
requirements per the applicable local standards,
codes, and practices in order to retain the dened
ratings. PTFE sealant or equivalent should be used
on NPT threads.
IMPORTANT
Devices certied for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and
NEC 505.
CAUTION
Installation of the detector and wiring should be
performed only by qualied personnel.
13.1
(33.3)
10.6
(27.0)
4.0
(10.2)
4.0
(10.2)
3.0
(7.6)
3.0
(7.6)
4X ø0.42
(1.1)
F2069
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10° MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTOR’S MOUNTING ANGLE.
Figure3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)

95-8549815.1
Detector Installation
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 or M10 bolts with a length
of at least 1 inch (25 mm). The surface must also have
sufficient capacity to hold the detector and mounting
arm weights (See "Specifications" section). Refer to the
Q9033 Mounting Arm manual (95-8686) for additional
installation information. See Figure3 for dimensions.
Relay and 0-20 mA Output Models
Follow the instructions below to install the X2200.
1. Make field connections following local ordinances
and guidelines in this manual. Refer to Figures 4
through 12.
2. Check all field wiring to be sure that the proper
connections have been made.
IMPORTANT
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
EOL Resistors (Not Used with EQP Model)
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors.
1. Required EOL resistor power rating must be 5 watts
minimum.
NOTE
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies to
ATEX/IECEx installations only.
2. Resistor leads should be cut to a length of
approximately 1 1/2 inches (40 mm).
3. Bend the leads and install the EOL resistor as shown
in Figure 6.
4. Maintain a 3/8 inch (10 mm) minimum gap between
the resistor body and the terminal block or any other
neighboring parts.
NOTE
The EOL resistor can only be used within the
ameproof terminal compartment. Unused conduit
entries shall be closed with suitable blanking
elements.
Figure4—X2200 Terminal Block
3/8 INCH (10 MM) GAP MINIMUM
1112
13
141516171819
B2126
BULKHEAD
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA + mA –
mA + REF mA – REF
COM FIRE COM FIRE
NO FIRE NO FIRE
NC FIRE NC FIRE
COM FAULT COM FAULT
NO FAULT NO FAULT
+Vin
–Vin
+Vin
–Vin –Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
COM AUX
NO AUX
NC AUX
RS485 A
RS485 B
MAN Oi
E2061
Figure6—EOL Resistor Installation
Figure5—Wiring Terminal Identication

995-854915.1
C2151
FIRE ALARM PANEL
X2200 DETECTOR
ALARM
24 VDC
+
–
EOL
DEVICE4
oiTEST 3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
NO FIRE2
NO FIRE
NC FIRE2
NC FIRE
COM FAULT1
COM FAULT
NO FAULT1
NO FAULT
+Vin
–Vin
+Vin
–Vin –Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS485 A
RS485 B
MAN Oi
mA + mA –
mA + REF mA – REF
COM AUX
NO AUX
NC AUX
SHIELD
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
Figure7—Ex d Wiring Option
C2152
FIRE ALARM PANEL
X2200 DETECTOR
ALARM
ALARM
24 VDC
+
–
EOL
DEVICE 4
oi TEST 3
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
COM FIRE2
COM FIRE
NO FIRE2
NO FIRE
NC FIRE2
NC FIRE
COM FAULT1
COM FAULT
NO FAULT1NO FAULT
+Vin
–Vin
+Vin
–Vin –Vin
29
28
27
26
25
24
23
22
21
SPARE
SPARE
RS485 A
RS485 B
MAN Oi
mA + mA –
mA + REF
mA – REF
COM AUX
NO AUX
NC AUX
WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE NORMALLY OPEN (NO) AND COMMON (COM) CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
5 PROPERLY CERTIFIED HAZARDOUS LOCATION METALLIC CABLE GLANDS OR STOP PLUGS ARE
REQUIRED TO FILL ALL CONDUIT ENTRIES.
6 SHIELD MUST BE CONNECTED TO THE METALLIC CABLE GLAND. MAKE CERTAIN THAT THE INSULATION
IS REMOVED TO ENSURE ELECTRICAL CONNECTION BETWEEN THE SHIELD AND THE HOUSING.
SHIELD
Figure8—Ex e Wiring Option

95-85491015.1
24 VDC
mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
D2153
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA +
mA + REF
mA –
29
28
27
26
25
24
23
22
21
MAN Oi
X2200 DETECTOR
–Vin –Vin
+Vin
Figure9—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sourcing)
24 VDC
mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
D2154
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA + mA –
mA – REF
29
28
27
26
25
24
23
22
21
MAN Oi
X2200 DETECTOR
–Vin –Vin
+Vin
Figure10—X2200 Detector Wired for Non-Isolated 0 to 20 mA Current
Output (Sinking)
24 VDC
mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
D2155
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA + mA – 29
28
27
26
25
24
23
22
21
MAN Oi
X2200 DETECTOR
–+
24 VDC
–Vin –Vin
+Vin
Figure11—X2200 Detector Wired for Isolated 0 to 20 mA
Current Output (Sourcing)
24 VDC
mA
PLC
–
+
600 Ω MAX
AT 24 VDC
–
+
D2156
OiTEST1
9
8
7
6
5
4
3
2
1
19
18
17
16
15
14
13
12
11
mA + mA – 29
28
27
26
25
24
23
22
21
MAN Oi
X2200 DETECTOR
–
+
24 VDC
–Vin –Vin
+Vin
Figure12—X2200 Detector Wired for Isolated 0 to 20 mA
Current Output (Sinking)
NOTES: 1. INDIVIDUAL MANUAL oiTEST SWITCHES CAN BE
INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE
PANEL. TEST SWITCHES ARE NOT SUPPLIED.

11 95-854915.1
EQP Model
1. Connect external wires to the appropriate terminals
inside the device junction box, shown in Figure 13.
See Figure 14 for terminal identification.
2. Connect the shield of the power cable to earth
ground at the power source.
3. Connect shields for the LON cable as indicated. See
Figure 15.
NOTE
DO NOT ground any shields at the detector housing.
4. With input power disconnnected, set the device
network address. (See “Setting Device Network
Addresses” section of this manual for switch
setting procedure.)
5. Check all field wiring to be sure that the proper
connections have been made.
6. Replace the device cover and apply input power.
7. Make the final sighting adjustments and use a 14 mm
hex wrench to ensure that the mounting arm assembly
is tight.
NOTE
Refer to the Eagle Quantum Premier system
manual (95-8533) for information regarding power
requirements, network communication cable
requirements, and conguration.
6
5
4
3
2
1
16
15
14
13
12
11
SHIELD SHIELD
COM 1 A COM 2 A
COM 1 B COM 2 B
PWR SHIELD PWR SHIELD
+Vin +Vin
–Vin –Vin
C2089
Figure13—X2200 Terminal Block (EQP Model)
Figure14—Wiring Terminal Identication for X2200 EQP Model

95-85491215.1
Figure15—A Typical EQP System
EQP2100PSM
SHIELD
4 9
24 VDC –
6 7
24 VDC +
5 8
B
11 3
A
10 2
B 2
3
4
C 1
SHIELD
12 1
COM2 COM1
BUS BAR P3
AC LINE
N
H
EQPX2200
SHIELD
13 3
24 VDC –
11 1
24 VDC +
12 2
B
14 4
A
15 5
SHIELD
16 6
COM2 COM1
EQPX2200
SHIELD
13 3
24 VDC –
11 1
24 VDC +
12 2
B
14 4
A
15 5
SHIELD
16 6
COM2 COM1
EQPX2200
SHIELD
13 3
24 VDC –
11 1
24 VDC +
12 2
B
14 4
A
15 5
SHIELD
16 6
COM2 COM1
EQPX2200
SHIELD
13 3
24 VDC –
11 1
24 VDC +
12 2
B
14 4
A
15 5
SHIELD
16 6
COM2 COM1
EQP3700DCIO
SHIELD
6 3
24 VDC –
5 2
24 VDC +
4 1
B
5 2
A
4 1
SHIELD
6 3
COM2 COM1
P1
P2
P3P4
IN–/OUT+
B B
COMMON
C C
+ SUPPLY
A A
CH 1
CH 5
IN–/OUT+
B B
COMMON
C C
+ SUPPLY
A A
CH 2
CH 6
IN–/OUT+
B B
COMMON
C C
+ SUPPLY
A A
CH 3
CH 7
IN–/OUT+
B B
COMMON
C C
+ SUPPLY
A A
CH 4
CH 8
CONTROLLER
24 VDC –
4 2
24 VDC +
3 1
B
52 49
A
53 50
TxD A
59 56
RxD B
58 55
GND GND
57 54
SHIELD
51 48
COM2 COM1
P1
P7
P9 P8
P4 P5
1+ 5+
513
1– 5–
614
2+ 6+
715
2– 6–
816
3+ 7+
917
3– 7–
10 18
4+ 8+
11 19
4– 8–
12 20
P2 P3
C45
NO 46
NC 47
P6
FAULT
GND 5
RXD 2
TXD 3
DB-9
CONNECTION
TO COM PORT
OF PC
DIGITAL INPUTS
C C
21 33
NO NO
22 34
NC NC
23 35
RELAY 1
RELAY 5
C C
24 36
NO NO
25 37
NC NC
26 38
RELAY 2
RELAY 6
C C
27 39
NO NO
28 40
NC NC
29 41
RELAY 3
RELAY 7
C C
30 42
NO NO
31 43
NC NC
32 44
RELAY 4
RELAY 8
24 VDC
SUPPLY
+ –
24 VDC
BATTERY
+ –
H N
AC LINE
POWER
DISTRIBUTION
+
+
++
+
++
–
–––
–
–
–
A2209

13 95-854915.1
SETTING DEVICE NETWORK ADDRESSES
(EQ and EQP Models Only)
Overview of Network Addresses
Each device on the LON must be assigned a unique
address. Addresses 1 to 4 are reserved for the controller.
Valid addresses for field devices are from 5 to 250.
IMPORTANT
If the address is set to zero or an address above
250, the switch setting will be ignored.
Duplicated addresses are not automatically detected.
Modules given the same address will use the number
given and report to the controller using that address. The
status word will show the latest update, which could be
from any of the reporting modules using that address.
Setting Field Device Addresses
Selection of the node address is done by setting rocker
switches on an 8 switch “DIP Switch Assembly” within the
detector’s housing. Refer to Figure 16 for switch location.
WARNING
The network address switches are located within
the detector housing. Disassembly of the detector
head that contains powered electrical circuits is
required to gain access to the network address
switches. For hazardous areas, the area must
be de-classified before attempting disassembly
of the device. Always observe precautions for
handling electrostatic sensitive devices.
The address number is binary encoded with each switch
having a specific binary value with switch 1 being the
LSB (Least Significant Bit), see Figure 17. The device’s
LON address is equal to the added value of all closed
rocker switches. All “Open” switches are ignored.
Example: for node No. 5, close rocker switches 1 and
3 (binary values 1 + 4); for node No. 25, close rocker
switches 1, 4, and 5 (binary values 1 + 8 + 16).
NOTE
The eld device sets the LON address only when
power is applied to the device. Therefore, it is
important to set the switches before applying
power. If an address is ever changed, system
power must be cycled before the new address will
take effect.
After setting address switches, record the address
number and device type.
ADDRESS SWITCHES SENSOR MODULE
REMOVED FROM HOUSING
A2191
Figure16—Location of Address Switches
1 2 3 4 5 6 7 8
1 2 4 8 16 32 64 128
ON
NODE ADDRESS EQUALS THE ADDED VALUE
OF ALL CLOSED ROCKER SWITCHES
A2190
BINARY
VALUE
CLOSED = ON
OPEN = OFF
Figure17—Address Switches for X2200

95-85491415.1
STARTUP PROCEDURE
When installation of the equipment is complete, perform
the “Fire Alarm Test” below.
FIRE ALARM TEST
1. Disable any extinguishing equipment that is
connected to the system.
2. Apply input power to the system.
3. Initiate an oitest. (See “Magnetic oi/ Manual oi”
under Optical Integrity in the "Description" section of
this manual.)
4. Repeat this test for all detectors in the system. If
a unit fails the test, refer to the “Troubleshooting”
section.
5. Verify that all detectors in the system are properly
aimed at the area to be protected. (The Q1201C
Laser Aimer is recommended for this purpose.)
6. Enable extinguishing equipment when the test is
complete.
TROUBLESHOOTING
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
1. Disable any extinguishing equipment that is
connected to the unit.
2. Inspect the viewing windows for contamination and
clean as necessary. (Refer to the “Maintenance”
section for complete information regarding cleaning
of the detector viewing windows.)
3. Check input power to the unit.
4. If the fire system has a logging function, check
the fire panel log for output status information.
See Table 4 for information regarding 0 to 20 mA
output.
5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.
6. If all wiring checks out and cleaning of the oiplate/
window did not correct the fault condition, check for
high levels of background UV radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears, extreme
background UV radiation is present. Re-adjust the
view of the detector away from the UV source or
relocate the detector.
If none of these actions corrects the problem, return the
detector to the factory for repair.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
MAINTENANCE
IMPORTANT
Periodic flamepath inspections are not
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
amepaths.
WARNING
To avoid a potential electrostatic discharge (ESD),
the painted surface of the detector should only be
cleaned with a damp cloth.
WARNING
The sensor module (“front” half of the detector)
contains no user serviceable components and
should never be tampered with.
NOTE
Refer to the X2200 Safety manual (95-8672) for
specific requirements and recommendations
applicable to the proper installation, operation,
and maintenance of all SIL-Certified X2200 Flame
Detectors.
To maintain maximum sensitivity and false alarm
resistance, the viewing windows of the X2200 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.
1If fault continues, return device to factory for repair.
2See “Maintenance” section for cleaning procedure.
Table4—Current Level Output Troubleshooting Guide
Current Level
(±0.3 mA) Status Action
0 mA Power Fault Check system wiring.
1 mA General Fault Cycle power.1
2 mA
oi
Fault Clean windows.2
4 mA Normal Operation
16 mA Hi Background UV
Fault
Remove UV source
or aim detector away
from UV source.
20 mA Fire Alarm

15 95-854915.1
CLEANING PROCEDURE
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
To clean the windows and oiplate, use the window
cleaner (p/n 001680-001) with a soft cloth, cotton swab,
or tissue and refer to the following procedure:
1. Disable any extinguishing equipment that is
connected to the unit.
NOTE
Remove input power when cleaning the detector
windows. The rubbing motion on the surface of
the windows during cleaning can create static
electricity that could result in unwanted output
activation.
2. Clean the viewing window and reflective surfaces
of the oiplate using a clean cloth, cotton swab,
or tissue with the window cleaning solution. Use
Isopropyl alcohol for contaminations that the Det-
Tronics window cleaning solution can not remove.
If a fault condition is still indicated after cleaning,
remove and clean the oiplate using the
oi
Plate
Removal and Replacement procedure.
IMPORTANT
When used in extreme environments, the reective
surface of the detector
oi
plate may eventually
deteriorate, resulting in reoccurring
oi
faults and
the need for
oi
plate replacement.
oiPLATE REMOVAL AND REPLACEMENT
1. Disable any extinguishing equipment that is
connected to the unit.
2. Loosen the two captive screws, then grasp the oi
plate by the visor and remove it from the detector.
See Figure 18.
3. Install the new (or cleaned) oi
plate.
4. Recalibrate the detector's oisystem. Refer to the
Inspector Monitor manual, number 95-8581, for
instructions regarding oiplate replacement and oi
system recalibration.
CAUTION
Do not replace the
oi
reflector plate without also
recalibrating the
oi
system.
Recalibration of the oisystem requires the use of the
Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the system using
the Mag oior Man oifeature should performed regularly
to ensure that the system is operating properly. Refer to
Table 1 in the X2200 Safety manual, number 95-8672, for
frequency of proof tests. To test the system, perform the
“Fire Alarm Test” as described in the “Startup Procedure”
section of this manual.
CLOCK BATTERY
The real time clock has a backup battery that will
operate the clock with no external power. Return the
device to the factory for battery replacement if needed.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the ame detector, but the time
stamping of the data log may be affected.
LOOSEN TWO CAPTIVE SCREWS
GRASP VISOR AND
REMOVE oiPLATE
B2211
Figure18—
oi
Plate Removal

95-85491615.1
FEATURES
• Responds to a fire in the presence of modulated
blackbody radiation (i.e., heaters, ovens, turbines)
without false alarm
• High speed capability
• Built-in data logging / event monitoring, up to 1500
events (up to 1000 general, 500 alarms)
• Automatic, manual or magnetic oitesting
• Easily replaceable oiplate
• Fire, fault and auxiliary relays standard
• 0 to 20 mA isolated output (optional)
• Eagle Quantum Premier LON/SLC output (optional)
• HART communication (optional)
• A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
• Operates under adverse weather conditions
• Mounting arm allows easy sighting
• Integral wiring compartment for ease of installation
• Explosion-proof/flame-proof detector housing.
Meets FM, CSA, ATEX, and IECEx certification
requirements.
• Class A wiring per NFPA-72
• Meets NFPA-33 response requirement for under
0.5 second (available when model selected)
• 3 year warranty
• Advanced signal processing (ARC)
• RFI and EMC Directive compliant
Associated Manuals
List of X2200 related manuals:
SPECIFICATIONS
OPERATING VOLTAGE—
24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
POWER CONSUMPTION—
2.5 watts at 24 Vdc nominal;
4.5 watts at 24 Vdc in alarm.
2.8 watts at 30 Vdc nominal;
5.1 watts at 30 Vdc in alarm.
Total power: 7.6 watts at 30 Vdc with EOL resistor installed.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.
For HART model, refer to Addendum number 95-8638.
POWER UP TIME—
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.
OUTPUT RELAYS—
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals
and normally open / normally closed contacts,
normally de-energized operation, and latching or
non-latching operation.
Fault relay, Form A, 5 amperes at 30 Vdc:
The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.
Auxiliary relay, Form C, 5 amperes at 30 Vdc:
The auxiliary relay has normally open / normally
closed contacts, normally energized or de-energized
operation, and latching or non-latching operation.
CURRENT OUTPUT (Optional)—
0 to 20 milliampere (±0.3 mA) dc current, with a
maximum loop resistance of 500 ohms from 18 to
19.9 Vdc and 600 ohms from 20 to 30 Vdc.
LON OUTPUT—
Digital communication, transformer isolated (78.5 kbps).
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from –55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
TITLE FORM NUMBER
Pulse 95-8552
EQP 95-8533
SIL 2 (Safety) 95-8672
HART Addendum
95-8638
Q9033 Mounting Arm
and Collar Attachment 95-8686
Inspector Monitor Software for
X-Series Flame Detectors 95-8581

17 95-854915.1
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 18.
RESPONSE TIME—
Less than 6 seconds. (See Appendix A for details.)
SOURCE TUBE—
Contains radioactive isotope Krypton 85 (Kr85)
Calculated Activity: 14,800 Becquerels (0.4μCi).
ENCLOSURE MATERIAL—
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 20.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5
mm2
wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
Important:
18 Vdc minimum must be available at the
detector. For
ambient temperatures
below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
THREAD SIZE—
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.
SHIPPING WEIGHT (Approximate)—
Aluminum: 7 pounds (3.2 kilograms)
Stainless Steel: 14.6 pounds (6.7 kilograms)
Mounting Arm (AL): 6 pounds (2.75 kilograms)
Mounting Arm (SS): 14 pounds (6.4 kilograms)
WARRANTY PERIOD—
3 years
CERTIFICATION—
®
VdS
For complete approval details, refer to the appropriate
Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX
Appendix D - IECEx
Appendix E - EN54
Appendix F - Additional Approvals
0°
15°
30°
45°
15°
30°
45°
VIEWING ANGLE
C1288
100
90
80
70
60
50
40
30
20
10
DETECTION
DISTANCE
(PERCENT)
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
INCIDENCE DECREASES.
Figure19—Detector Cone of Vision
10.2
(25.9)
4.8
(12.2)
4.7
(11.9)
B2223
Figure20—Dimensions in Inches (cm)

95-85491815.1
REPLACEMENT PARTS
The detector is not designed to be repaired in the field. If
a problem should develop, refer to the "Troubleshooting"
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.
REPLACEMENT PARTS LIST
Part Number Description
009208-002
oiReplacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor
007307-002
Replacement oi Reflector Plate for X52/X22/X98
(requires Inspector Connector to calibrate)
DEVICE REPAIR AND RETURN
Prior to returning devices, contact the nearest local
Detector Electronics office so that a Return Material
Identification (RMI) number can be assigned. A
written statement describing the malfunction must
accompany the returned device or component to
assist and expedite nding the root cause of the
failure. When items are being returned, please note:
NOTE
Shipping personnel must be hazmat trained to
pack, mark, and label the return package. Please
consult your country-specic regulations.
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.
NOTE
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.
Return all equipment transportation prepaid to the factory
in Minneapolis.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
NOTE
Radioactive material is subject to regulation.
All products containing a source tube meet
the definition of an “excepted package” for
radioactive material under the US Department of
Transportation (DOT), the International Air Transport
Association (IATA), the International Civil Aviation
Organization (ICAO), the International Maritime
Dangerous Goods Code (IMDG), and any other
specic hazardous material regulations from the
country of source of return (TDG, RID, ADR, etc.).
These units are classied as “UN2911, Radioactive
Material, Excepted Package – Article.”
ORDERING INFORMATION
When ordering, please specify:
X2200 UV Flame Detector
Refer to the X2200 Model Matrix for details.
Q9033 Mounting Arm is required:
– Q9033A for aluminum detectors only
– Q9033B for aluminum and stainless steel detectors
ACCESSORIES
Part Number Description
000511-029 Converter RS485 to RS232
103881-001 Converter RS485 to USB
007819-001
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
007819-002
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
009207-001
Flame Inspector Monitor CD
103922-001
Model 475 HART Communicator
102740-002
Magnet
008082-001
Magnet and Adapter for Extension Pole
007739-001
Magnet and Extension Pole
007240-001 Q1116A1001, Air Shield (AL)
007818-001
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
007818-002
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
009177-001
Q1120A1001 Paint Shield mounting ring (AL)
006097-001 Q1201 Laser
102871-001
Laser Battery, 3V Lithium (laser)
007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
007338-001
Q2000A1001 X-Series Weather Shield (AL)
007290-001
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
007290-002
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
011385-001
Q9033 Collar Attachment
101197-001
Stop Plug, 3/4” NPT, AL
101197-004
Stop Plug, 3/4” NPT, SS
101197-005
Stop Plug, M25, AL, IP66
101197-003
Stop Plug, M25, SS, IP66
010816-001
Stop Plug, 20 Pack, 3/4”NPT, AL
010817-001
Stop Plug, 20 Pack, 3/4”NPT, SS
010818-001
Stop Plug, 20 Pack, M25, AL, IP66
010819-001
Stop Plug, 20 Pack, M25, SS, IP66
103363-001
14 mm Hex Wrench (Steel)
103406-001
Screwdriver
001680-001
Window cleaner (6 pack)
107427-040
O-ring - Rear Cover (Viton) - black or brown
005003-001
1 oz grease for detectors (silicone-free)
104346-154
O-ring - Rear Cover (Fluorosilicone) - blue
012549-001 1 oz PTFE silicone-free lubricant
Other manuals for x2200
2
This manual suits for next models
1
Table of contents