Detcon C1D2 User manual

C1D2 Dual Alarm Bar
2 Strobe with Horn Alarm Station
Operator’s Installation and Instruction Manual
DETCON, Inc.
4055 Technology Forest, Suite 100
The Woodlands, Texas 77387
Ph.281.367.4100 / Fax 281.298.2868
www.detcon.com
Aug. 04, 2015 • Document #4530 • Revision 0.1

Dual Alarm Bar
Dual Alarm Instruction Manual ii
This page left intentionally blank

Dual Alarm Bar
Dual Alarm Instruction Manual iii
Table of Contents
1.0 Description................................................................................................................................................ 1
1.1 Strobe ................................................................................................................................................... 2
1.2 Horn...................................................................................................................................................... 2
2.0 Installation................................................................................................................................................ 3
3.0 Operation.................................................................................................................................................. 5
4.0 Specifications............................................................................................................................................ 6
5.0 Spare Parts List........................................................................................................................................ 6
6.0 Warranty.................................................................................................................................................. 7
7.0 Revision Log............................................................................................................................................. 8
Table of Figures
Figure 1 Unit ........................................................................................................................................................ 1
Figure 2 Strobe..................................................................................................................................................... 2
Figure 3 Horn ....................................................................................................................................................... 2
Figure 2 Alarm Station Dimensions..................................................................................................................... 3
Figure 3 Wiring Diagram..................................................................................................................................... 4

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 1 of 8
1.0 Description
The Detcon Dual Alarm Bar audiovisual alarm stations are designed for installation and use in industrial
environments. The alarm station consists of a strobe and siren. The strobe can consist of any dome color such
as amber, blue, clear, green, Purple and Red. The siren is capable of producing coded blasts or sustained
tones. The Dual Alarm Bar alarm assemblies are specifically designed for locations or environments where a
very bright visual and high decibel alarm signal is required. The high-intensity strobe light provides 60-80
flashes per minute. The siren produces a noise level of 105db(A) @ 10 feet. The Horn and Strobes are UL
listed and CSA Certified and meet NEMA 4X watertight, dust-tight requirements. Alarm components are pre-
assembled on a NEMA 4 enclosure that is designed for C1D2 Groups B, C, and D locations.
Figure 1 Unit
The alarm station is pre-wired to control circuit alarm devices for the purpose of warning personnel of
hazardous conditions. When used in conjunction with Detcon Sentinel or other Detcon Controllers, the alarm
station is typically used to provide an alarm 1 (strobe1), alarm2 (strobe2), and alarm 3 (horn) for
predetermined hazardous environmental gas levels (toxic or flammable) as indicated by remote mount gas
sensors.

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 2 of 8
1.1 Strobe
The alarm station strobe is configured with choice of dome colors such as amber, blue, clear, green, magenta,
or red. The strobes are rated NEMA4x for C1D2 Groups A, B, C, and D locations, and utilize a Strobe Guard,
and gasket to complete the NEMA4 rating. The strobes produce 1.9 joules per flash while drawing relatively
low current and have a flash rate of 60~80 per second.
Figure 2 Strobe
1.2 Horn
This range of light weight all GRP, flameproof sounders is intended for use in potentially explosive gas and
dust atmospheres and has been designed with high ingress protection to cope with the harsh environmental
conditions found offshore and onshore in the oil, gas and petrochemical industries. The Horn is rated for Class
I, Zone 1. The Horn has the ability to produce up to 125db(A) output dependent upon the tone settings (refer
to the Sound Signals Table).
Figure 3 Horn

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 3 of 8
2.0 Installation
NOTE:
DO NOT
handle the unit by the cable.
The cable is not meant to be used as a
handle, and damage may occur to the unit if the cable is used to carry the unit.
The unit comes with U-Bolt hardware provided for mounting on 2~3 inch poles. Mount on pole at appropriate
height, and ensure hardware is tightened down so that the unit is not capable of moving.
There are two possible cables that may be connected to the unit. Connect the cable provided to the Control
Unit and to the Alarm Bar. This cable can only be connected one way. No other customer wiring is necessary.
Figure 4 Alarm Station Dimensions

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 4 of 8
Strobe 3
Alarm 3
Strobe 4
Alarm 4
Strobe 1
Alarm 1 Strobe 2
Alarm 2
Red
Red
Black
Blue
Red
Black
Black
Black
Orange
Green
White
Black
Black
Red
Red
Blue
Red
White
Orange
Green
Black
Black
Red
Red
Green/Yellow
Blue
White
Gray
Brown
Black
Black
Blue
Brown
White
Gray
Use Ty-Wraps to keep wiring neat.
Cable to Horn.
DB3 Horn
Alarm 5
Figure 5 Wiring Diagram

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 5 of 8
3.0 Operation
The Quad Alarm Bar provides four strobes and an alarm horn. The wireless alarm station is set to respond to
alarms from the controlling unit. The controller has independent control over the strobes and the Horns, and
they will be activated when the appropriate alarm is activated.
The horn has up to 32 possible settings, for use in different configurations. The default settings of the horn are
factory set. The default setting for the horn is 3 (11101). To change the setting of the horn, remove the rear
cover of the horn, and set the dip switches (TONE 1) according to the Sound Signals Table. TONE 1 has a 5
position dip switch used to set the horn sound signal.
Table 1 Sound Signals
Switch Setting Tone Tone Description
1 11111 Alt Tones 800/970 Hz at 1/4 sec
2 11110 Sweeping 800/970 Hz at 7Hz Fast Sweep(LF)
3 11101 Sweeping 800/1000 Hz at 1 Hz Med Sweep(LF)
4 11100 Continuous at 2850 Hz
5 11011 Sweeping 2400-2850 Hz at 7 Hz Fast Sweep
6 11010 Sweeping 2400-2850 Hz at 1 Hz
7 11001 Slow Whoop Slow Whoop
8 11000 Sweep 1200-500 Hz at 1 Hz Din Tone
9 10111 Int. Tone of 970 Hz at 1 Hz
10 10110 Swept 500 Hz 770 Hz in 0.5 second. Back-Up Alarm(LF)
11 10101 Alt. Tones 800/970 Hz at 7/8 Hz
12 10100 Int. Tone at 2850 Hz at 1Hz Back Up Alarm(HF)
13 10011 970Hz at 1/4 sec on 1 sec off
14 10010 Continuous at 970 Hz
15 10001 554Hz for 100ms / 440 Hz for 400ms French Fire Sound
16 10000 Int. 660 Hz 150 ms on 150 ms off Swedish Fire Alarm
17 01111 Int. 660 Hz 1.8 sec on 1.8 sec off Swedish Fire Alarm
18 01110 Int. 660 Hz 6.5 sec on 13 sec off Swedish Fire Alarm
19 01101 Continuous 660 Hz Swedish Fire Alarm
20 01100 Alt 554/440 Hz at 1 Hz Swedish Fire Alarm
21 01011 Int. 660 Hz at 7/8 Hz Swedish Fire Alarm
22 01010 Int. 2850 Hz 150 ms on 100 ms off Pelican Crossing
23 01001 Sweep 800-970 Hz at 50 Hz Low Freq Buzz
24 01000 Sweep 2400-2850 Hz at 50 Hz High Freq Buzz
25 00111 3 970Hz pulses 0.5on/0.5off, 1.5 off
26 00110 3 2850Hz pulses 0.5on/0.5off, 1.5 off
27 00101 Int. 3100 Hz 0.32s on / 0.68s off
28 00100 Spare/Customer Tone
29 00011 Spare/Customer Tone
30 00010 Spare/Customer Tone
31 00001 Spare/Customer Tone
32 00000 Spare/Customer Tone

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 6 of 8
4.0 Specifications
Dual Alarm Bar
Voltage: 12VDC
Current : 1.5A Max
Mount: Wall Mount or 2~3” Pipe Mount
Environment Rating: Designed to meet NEMA 4 specifications
Area Classification: Designed for use in C1D2 Groups B, C, D locations
Ambient Temperature Range: -40°C to 65°C
Dimensions: 21”H X 7.67”W X 14.6”D
Weight: 18lbs approx.
Dome Colors: Amber, Blue, Clear, Green, Purple and Red
Light Source/Lamp Style: Xenon Strobe Lamp
Lamp Life: 7,000 Hours
Candle Power: 50 effective candlepower (EFC)
Flash Rate/Minute: 60-80
Joules per Flash: 1.9
Sound Output: Up to 125dB(A) @ 1 meter
(Tone dependent)
5.0 Spare Parts List
354-4900x6-024 12-80VDC Strobe (x represents color of lamp)
Strobe colors: Red (2), Amber (4), Green (5), Blue (6), Magenta (7), and Clear (9)
356-DB3007-024 MEDC DB3 Horn – 12-48VDC
980-RSRK63-xxM Turck 6 conductor cable (for Quad and Dual Alarm Bar)
Where xxM= length: 02M=2meter, 10M=10meter, 15M=15meter
980-RSMRKM-xxM Turck 5 Conductor cable (Specifically for the Dual Alarm Bar)
Where xxM= length: 02M=2meter, 10M=10meter, 15M=15meter

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 7 of 8
6.0 Warranty
Detcon Inc., as manufacturer, warrants under intended normal use each new Quad Alarm Bar NEMA 4X
alarm stations to be free from defects in material and workmanship for a period of one year. The warranty
period begins from the date of shipment to the original purchaser and ends one year thereafter. All warranties
and service policies are FOB the Detcon Inc. facility located in The Woodlands, Texas.

Dual Alarm Bar
Dual Alarm Instruction Manual Rev. 1.0 Page 8 of 8
7.0 Revision Log
Revision Date Changes made Approval
0.0 02/04/15 Initial Release LU
1.0 08/04/15 Redesign for DB3B Horn LU
Shipping Address: 4055 Technology Forest, Suite 100, The Woodlands, Texas 77381
Mailing Address: P.O. Box 8067, The Woodlands Texas 77387-8067
Table of contents