
INSTALLATION INSTRUCTIONS Air Handler : AHB
X40158 Rev.D Specifications subject to change without notice. 5
LOW VOLTAGE CONTROL CONNECTIONS
The 24 volt power supply is provided by an internally wired 115/24V
low voltage transformer which is standard on all models.
Field supplied low voltage wiring can enter the unit on the top left
hand corner.
Install the strain relief bushing (supplied with unit) in the selected
hole.
Connect low voltage field wiring to the Brown (24V Common) and
Red (24V Hot), and Grey (24V Fan) pigtails.
* THE MAXIMUM EXTERNAL STATIC PRESSURE IS 0.8’’ W.C.,
WITHOUT COOLING COIL. DEDUCT STATIC PRESSURE OF
COIL FOR MAXIMUM STATIC PRESSURE.
AIR FLOW CHECK
For proper system operation, the air flow through the indoor coil
should be between 350 and 450 cfm (165 and 212 L/s) per ton of
cooling capacity. The air flow through the unit can be determined by
measuring the external static pressure to the unit and selecting the
motor speed tap that will most closely provide the required air flow.
1. Set up to measure external static pressure at the supply and
return duct connections.
2. Drill holes in the ducts for pressure taps, pitot tubes, or other
accurate pressure sensing devices.
3. Connect these taps to a level inclined manometer or draft gauge.
4. Ensure thecoil and filter are clean, and all the registers are open.
5. Determine the external static pressure with the blower operating.
6. Refer to the Air Flow Data tables, to find the speed tap that will
most closely provide the required air flow for the system.
7. Refer to Motor Speeds and Airflow in these instructions if the
speed tap is to be changed.
8. Recheck the external static pressure with the new speed tap, and
confirm speed tap selection.
CARE AND MAINTENANCE
The system should be regularly inspected by a qualified service
technician. Consult the servicing dealer for recommended frequency.
Between visits, the only consumer servicerecommended or required
is air filter maintenance and condensate drain operation.
Keep the low voltage wiring as short as possible inside the control
box.
Complete connections between indoor blower, outdoor section,
indoor thermostat according to instruction provided with the
Condenser Installation Instructions and refer to Wiring Diagram.
MOTOR SPEEDS AND AIRFLOW
The motor speed can be set to one of three speeds. To change the
blower speed unplugs the black wire connection at the blower motor
and move to desired speed tap.
AIR FILTER
Inspect air filters at least monthly and replace or clean as required.
Disposable type filters should be replaced. Reusable type filters may
be cleaned by soaking in mild detergent and rinsing with cold water.
The frequency of cleaning depends upon the hours of operation and
the local atmospheric conditions. Install filters with the arrows on the
side pointing in the direction of air flow. Clean filters keep unit
efficiency high.
LUBRICATION
The bearings of the blower motor are permanently lubricated.
CONDENSATE DRAINS
During the cooling season check the condensate drain lines to be
sure that condensate is flowing from the primary drain but not from
the secondary drain. If condensate ever flows from the secondary
drain, the unit should be promptly shut off and the condensate pan
and drains cleaned to insure a free flowing primary drain.
AHB WIRING DIAGRAM