DINDAN 14ACU/005 User manual

Enclosure cooling unit
Model
14ACU/005
User's guide

Authorized Service Center
THAILAND : Dindan Technical Co.,Ltd.
27 Soi LuanJerAnuSorn 2 Sukhumvit Rd.
Bangna Subdist., Bangna Dist., Bangkok 10260 Thailand
Tel : +662 753 4212
Fax : +662 753 4211
E-mail: [email protected]
Website: www.dindan-tech.com
VIETNAM : Space Cooling Co.,Ltd.
Room 0311-C1, Mandarin Garden Complex , Hoang Minh Giam Street ,
Cau Giay District , Hanoi , Vietnam
Tel : +84 46 664 3395
Fax : +84 46 664 3398
Website: www.spacecooling.com.vn
INDONESIA : PT.YAKIN MAJU SENTOSA
COMPLEX PERTOKOAN GLODOK JAYA NO.74
JAKARTA 11180 , INDONESIA
Tel : +6221 626 3851; 626 3852; 649 7777
Fax : +6221 626 3855; 629 0036
E-mail: [email protected]
Website: www.yakinmaju.com

1
Content Page
1. Over view 3-5
2. Specifications 6-7
3. Notification 8
4. Technical information 9-10
5. Installation 11-19
6. Maintenance 20
7. Fault Indication 21
8. Assembly and part number 22

Introduction
Cooling unit for control cabinet is used for diminishing internal heat by
providing cool air to the control cabinet that can protect sensitive equipment It is
specially designed to resist surrounding temperature as high as 40-50 oC and can
function well in any factories including those with intensive dust, particles and oil mist
or with high acidity.
2

3
14ACU/005
1. Over view

4
Main Controller box
Compressor
Condensor coil
Condensor fan
Drain pan
Temperature display
Evaporator coil
Evaporator fan
Filter
Temperature setting
LED status display
Switch on-off
Hiprosent control
Main controller
(Hiprosent control)

5
HIPROSENT CONTROL (EGS033-2)
Control and Monitor
A1 = Main Controller
A2 = Temperature Adjustment
A3 = LED compressor's status
A4 = LED operating status
A5 = LED Hi-Lo Voltage
A6 = Socket for Output Alarm (not appropriate with Cooling Unit)
Cable and signal
B1 = Temperature sensor
B2 = Drainage failure sensor
B3 = Ice Sensor
B4 = Over heat sensor
220VAC
C1 =Capacitor
M1 = Compressor
M2 = Condenser Fan
M3 = Evaporator Fan
S1 = On/Off switch
A6
A2
A3 A4
A5
12BC7856
D
ES1
C1
M3
1Ph M2
1Ph
M1
1Ph
220V 50/60Hz
Main connection
from 10A BREAKER
supply by Customer
A1
1
23
45
67
89
10 11
12 13
14
21048691357
B1
B3
B4
B2

2. Specifications
6
Characteristics (under normal operating condition at ambient temp. +35 oC.)
Model 14ACU/005
Capacity
W.
300
Installation type panel
Input single-phase (V.) 220V+20% / -15%
frequency (Hz.) 50/60
current (A.) 1.83
Compressor hermetic type reciprocate
torque start type low
refrigerant type 134a
lock rotor (A.) 8.30
System operate direct expand yes
Hi-prosent ctrl1. thermostat yes
condensor thermal detector yes
anti-freeze detector yes
compressor overheat detector none
water detector none
Protection over drain protect system yes
Display thermometer (red 7 segment 19 mm.) yes
system status (2 colour LED) yes
Electrical equip. safety device 7A slow-blow fuse
Evaporator coil face area x rows 25.5 sq.inch x 2
servo fan (r.p.m.) 2700
number of fan x cfm (0.18 inH2O) 1 x 50
Condenser coil face area x rows 33.75 sq.inch x 3
servo fan (r.p.m.) 2850
number of fan x cfm (0.2 inH2O) 1 x 158
Physical data approx.weight (kgs.)(include Inst.Plt) 26
dimension (mm.) W:384 D:175 H:432
condensate drain OD. 3/8 inch
internal casing electro-galvanize
Air filter width x lenth (mm.) 168 x 250

7
(LEFT VIEW) (FRONT VIEW)
(BOTTOM VIEW)
175
384
432
Ambient Air In
Warm Air
Out
Socket plug
Return Air
Cold Air
Out
In
300
133
(REAR VIEW) Out
Warm Air
Drain
Overdrain hole
40
Installation Plate & Templet for cutting Area
View From Outside of Cabinet
450
12
Cutting Area 379.6 mm.
450 mm.(heigh)
384 mm.(width)
37
Cutting Area 185 mm.
26 97.5 97.5 97.5 112.5
12 140 80 140
14- 3.2 Drill
19.7
for Special holder
Fasten M6x20mm. bolt

3. Notification
•Before, drilling, and cut. should use clean dry cloth, or the inventory doesn’t
lead the electricity, covers the equipment for protects iron dust touches the
electrical equipment while installing. (In case of machine still operate.)
•Cooling unit should be installed in the good circuration area
•Check vertical and horizontal level of which their error shall be allowable
within +/- 2 oin order to facililate efficient drainage
•Should always install gasket between Installation plate and Cooling Unit
before hang the cooling unit on the installation plate
•Installing of drain tube (Page 18)
•In order to minimize water condensation, cabinet doors should be tightly closed
during operation
•Circulation fan should be installed in cabinet if various equipment is densely
installed inside
•In order to obtain highest performance and durablility, repair and alteration of
cooling unit should be under care of distributor
•Should not adjust temperature difference more than 10oC betwee
enviromental temperature and cooling space, to prevent moisture build up on
some part in the cooling area when you open the cabinet panel
•If it is necessary to set temperature lower than 25oC, it is recommended to
use precision cooling unit or contact your Professional Maker.
•The equipments that are locate in the cooling air stream have to be
obstructed by the insulator to prevent water condensation
8

General Condition
Storage: Cooling unit should be stored at temp not exceeding 70 oC
Transportation: This type of cooling unit can't be laid down horizontally.
Installation: It shall be installed in vertical direction only
(please see figure below)
Disposal of damaged Cooling Unit
As its refrigeration system contain Refrigerant and lubricating oil for
compressor, in order to protect environment, these substances should be
disposed of properly or other under direction given by distributor.
4. Technical information
Protective equipment
Refrigeration system has been tested with high pressure device at 350 PSI.
This series of cooling unit also contains electronic circuit and sensors are
installed at significant points to monitor any defect of refrigeration cycle in order
to reduce burden of the user and to prolong use life of cooling unit at more
costeffective practice.
Note
- LED light will display green colour (continuously) to indicate condition.
- Under any abnormal condition, please see pages 21.
9
CORRECT INCORRECT

10
Correct installation Incorrect installation
Refrigeration Cycle
Drainage
Drainage of condensed water from cooling system shall be done by inserting
drain tube under drainpan (see page 18) and trying not to left it twisted. Make
sure, the other end of drain tube is not lower than water level in the container,
in order to avoid water reflux
Condenser
Evaporator
Compressor
Cap.tube
Filter
dryer
External
Internal
Drain tube
Drain tube Drain tube

11
5. Installation
Accessories for 14ACU/005
Items Quantity
Cooling unit 1
User's guide & Warranty card 1
Socket plug 1
Socket plug base plate 1
Special holder 2
Foam gasket 1
Air filte 1
Socket plug cover (circle) 1
Installing plate 1
3/8'' Drain Tube (200 cm.) 1
3 x 1 Sq.mm VCT power cord. (200 cm.) 1
Self tapping screw 1/8'' x 3/8'' (for Installation plate) 17
Fiber washer (for Installation Socket plug cover)1
M6 x 20 mm. bolt 2
Plain washer (for M6 x 20 mm. bolt) 2
Spring washer (for M6 x 20 mm. bolt) 2
1/2” Cable clamp 2
6” Cable tie 3

Installation procedure
1. Remove Installation plate B (front plate) from Installation plate A (back plate)
2. Align installation plate(rear plate) in the position to be installed.
12
Installation plate B
(front plate)
Installation plate A
(rear plate)
Screw M4x10 mm.

3. Layout 1-14 positions for drilling and cutout along the dot line with Jigsaw
4. Cover eqipments inside cabinet with clean and dry cloth,and cover with paper
boxes at position will be drilled and cutted in order to prevent metal scrapt
falling in cabinet.
13
Paper box
185 mm.
6 7
12
11
10
9
8
14 13
15
Cutting line / เส้นแสดงการตัด
1
2
3
4
5

14
5. Drill and cut the holes and area as be pointed out from installation plate.
6. Chamfer the cutted edge and paint rust proff colour.

15
7. Socket plug Installation
7.1 Put the cable in the socket plug and screw.
7.2 Put the socket plug and Socket plug base plate in the position and screw it
8. Installation plate attachment
8.1 Install the Installation plate A (rear plate) with 14 self tapping screws
8.2 Connect main power line with 220VAC which be connected to 10 Amp.
breaker (Main power is 1 Sq.mm.)
Beware Breaker shouldn't be shared its load with any other components.
Installation plate A (rear plate)
socket plug
3 x 1 Sq.mm.
VCT power cord
Socket plug base plate

9. Install the Installation plate B (front plate) to Installation plate A (rear plate)
10. Install the socket plug cover.
16
socket plug cover
Fiber washer
Self tapping screw
1/8'' x 3/8''
Installation plate A
(rear plate)
Installation plate B
(front plate)

11. Attach the foam gasket to the installation plate and fasten the special holders
on it and then hang the cooling unit on this holders, fasten another 2 screws
M6 x 20 mm. at the bottom of the cooling unit.
12. Uncover the frontal case of cooling unit then plug-in the plug.
17
foam gasket
Special holders
Installation plate and it foam
M6 x 20 mm.
bolt (2 unit)

18
13. Install the draining tube by the illustrature below
Beware:
Avoid dipping draing tube below than water level
which be clogged its drainage
14. Turn on breaker for operation
Tire with 6” CABLE TIE
Fixed with 1/2” CABLE CLAMP
Fixed with 1/2” CABLE CLAMP
3/8” Draining tube
Tank
Water level
Illustrate of drainage wiring
Table of contents
Popular Accessories manuals by other brands

INNOBIZ
INNOBIZ Kaolia Instructions for use

Decagon Devices
Decagon Devices Dielectric Leaf Wetness Sensor Owner's/operator's manual

ECO Sensors
ECO Sensors A-21ZX Instructions for use

LEGRAND
LEGRAND WattStopper DW-100 installation instructions

Waterpik
Waterpik 200 Series instruction manual

Defy
Defy DFD 211 instruction manual

Graef
Graef CC80 operating instructions

greenteQ
greenteQ senso manual

AGT
AGT PSG BCR01 Installation Manual, Operating Manual, Maintenance Manual, Spare Part List

Heat Controller
Heat Controller Comfort-Aire manual

Sutron
Sutron Accubar SDI-12 Operation & maintenance manual

Hytronik
Hytronik HEC7028 instruction manual