DIVERSITECH 675-TS32 User manual

www.diversitech.com
Technical Support 1-800-995-2222
TOUCH SCREEN THERMOSTAT
INSTRUCTION MANUAL
675-TS32 3 Heating and 2 Cooling

3
•7 Day programmable with 4 events
per day – including fan
•Large, easy to read dot matrix display
•True touch screen technology
•Automatic selection of cool
or heat mode
•Programmable fan mode
•Programmable filter monitor
•Programmable installer message
•Configurable humidification relay
•Customizable full and partial
lock security
•Adjustable differential settings
for multistage installations
•Energy watch calculates kWh
and HVAC costs
•Simple mode for
non-programmable usage
•Programmable Vacation Mode
675-TS32
3 Heating and 2 Cooling with Extra Programmable Output
Standard in all DiversiTech Touch Screen Thermostats: Complete and quick set-up with
gas, oil, electric, heat pump, air conditioning and multi-stage HVAC systems.
2

5
TABLE OF CONTENTS
TABLE OF CONTENTS.........................................................................................................5
GLOSSARY OF TERMS........................................................................................................6
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
SELECT A LOCATION..........................................................................................................7
MOUNTING THE THERMOSTAT TO THE WALL .....................................................................8
WIRING LEGEND ................................................................................................................9
WIRING DIAGRAMS..........................................................................................................10
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
HOME PAGE.....................................................................................................................16
CONTROL PAGE ...............................................................................................................17
THERMOSTAT OPERATION MODES....................................................................................18
TEMPERATURE SETPOINTS ..............................................................................................19
FAN OPERATION MODES ..................................................................................................20
MENU PAGE.....................................................................................................................21
MENU PAGE - DATE AND TIME SETTINGS .........................................................................22
MENU PAGE - PROGRAM SETTINGS..................................................................................23
MENU PAGE - ENERGY WATCH.........................................................................................24
MENU PAGE - SCREEN OPTIONS.......................................................................................25
MENU PAGE - VACATION MODE........................................................................................26
MENU PAGE - ADVANCED SETTINGS.................................................................................27
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – WELCOME...................................................................................28
ADVANCED SETTINGS – CONFIGURING YOUR EQUIPMENT .................................................30
ADVANCED SETTINGS – SETTING THE DIFFERENTIAL .......................................................31
ADVANCED SETTINGS – TIMER FEATURE..........................................................................32
ADVANCED SETTINGS – HEAT PUMP ...............................................................................33
ADVANCED SETTINGS – CALIBRATION..............................................................................35
SIMPLE THERMOSTAT MODE ...........................................................................................36
TROUBLESHOOTING .........................................................................................................37
IMPORTANT NOTICE .......................................................................................................38
WARRANTY .....................................................................................................................39
4
Your Kit Includes: Outdoor Wireless Temperature Transmitter
+ Antenna + Receiver Module + 2 Batteries
This convenient feature provides you the outdoor temperature right
on your DiversiTech thermostat.
Outdoor Wireless Temperature Transmitter and Receiver Kit

7
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
SELECTING A LOCATION
Install your DiversiTech thermostat approximately 5 feet (1.5 meters) above the floor in an
area with good air circulation.
Avoid the following locations:
• Hot or cold air from ducts
• Radiant heat for appliances or sun such as a skylight
• Unheated areas or uncooled areas:
for example an outside wall behind the thermostat.
6
Anticipator control – Anticipator control
is used to turn off the heating equipment
before the room temperature actually
reaches the cut-out point.
Cut-in Point – The air temperature at the
thermostat at which it initiates action of
heating/cooling equipment.
Cut-out Point – The air temperature at the
thermostat at which it terminates action of
heating/cooling equipment.
Cycle rate – Cycle rate is the frequency that
heating or cooling equipment is turned on
during a certain period of time. Cycle rate
is often given in units of cycles per hour
(CPH).
Differential – Differential is defined as
the difference between the cut-in and
cut-out points as measured at the
thermostat under specified operating
conditions. For example, if the thermostat
turns the heating equipment on at 70
degrees F and turns the heating equipment
off at 74 degrees F, then the differential is
4 degrees F.
Programmable thermostat – A thermo-
stat with the capability of automatically
adjusting temperature set point to pre-
selected settings at pre-selected times.
Setback – The automatic alteration of the
thermostat control point(s) by means other
than manually changing the temperature set
point.
Set point – The desired temperature
setting on an electromechanical or
electronic thermostat.
GLOSSARY OF TERMS

9
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING LEGEND
TERMINAL EQUIPMENT STANDARD COLOR
Y1 First Heat Pump & AC Yellow
G Fan Green
W2 First Stage Furnace White
OBW Reverse Valve - Second Stage Furnace Orange
RH 24V AC Heat Red
Y2 Second Heat Pump & AC Unknown
C Common Blue
H No Connectionl Unknown
DH Np Connection Unknown
RC 24V AC Cool Unknown
11 & 12 Not Used
NOTE: The above colors are standard in HVAC industry. The wiring should be
confirmed before installation
8
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
MOUNTING THE THERMOSTAT TO THE WALL
1. Make sure to turn off the power supply located at the electrical service panel.
All heating and cooling units should be OFF.
2. Remove the cover plate by pulling up the cover from the left or right side only.
3. Align the thermostat unit to the wall.
4. Mark the two locations for drilling the 3/16” holes required for the plastic screw anchors.
5. Remove the thermostat and drill the two 3/16” holes in these locations.
6. Insert the plastic gyproc screw anchors and tighten them securely.
7. Make the appropriate wire connections based on the specifications of the
household HVAC unit(s). Please refer to Wiring Table to determine the appropriate
wire connections.
8. Securely mount the thermostat unit to the wall with the two supplied screws.
9. Fit the cover plate back by clipping one side first (left or right) and than push down
on the opposite side.
10. Turn on the electricity at the electrical service panel.

11
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING DIAGRAMS
AC2
I2
2 AIR CONDITIONERS
24V
FAN
AC1
I1 RC DH H C Y2 RH OBW W2 G Y1
COMMON
HEAT 2
HEAT 1
I2
1 AIR CONDITIONER AND 2 HEAT
24V
FAN
AC
I1 RC DH H C Y2 RH OBW W2 G Y1
COMMON
10
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING DIAGRAMS
I2
1 AIR CONDITIONER
24V
FAN
AC
I1 RC DH H C Y2 RH OBW W2 G Y1
COMMON
HEAT
I2
1 AIR CONDITIONER AND 1 HEAT
24V
FAN
AC
I1 RC DH H C Y2 RH OBW W2 G Y1
COMMON

13
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING DIAGRAMS
I2
COMMON
2 HEAT PUMPS
HP2
24V
REVERSE VALVES
FAN
HP1
I1 RC DH H C Y2 RH OBW W2 G Y1
I2
COMMON
1 HEAT PUMP AND 2 HEAT
HEAT 2
24V
REVERSE VALVES
HEAT 1
FAN
HP
I1 RC DH H C Y2 RH OBW W2 G Y1
12
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING DIAGRAMS
HEAT
REVERSE VALVES
I2
1 HEAT PUMP AND 1 HEAT
24V
FAN
HP
I1 RC DH H C Y2 RH OBW W2 G Y1
COMMON
REVERSE VALVES
I2
1 HEAT PUMP
24V
FAN
HP
I1 RC DH H C Y2 RH OBW W2 G Y1
COMMON

15
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING DIAGRAMS
14
DIVERSITECH TOUCH SCREEN THERMOSTAT INSTALLATION
WIRING DIAGRAMS
HEAT
TRANSFORMER
COOL
TRANSFORMER
I2
2 TRANSFORMERS
I1 RC DH H C Y2
CUT
RH OBW W2 G Y1
I2
1 TRANSFORMER
I1 RC DH H C Y2 RH OBW W2 G Y1
HEAT
TRANSFORMER

17
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
CONTROL PAGE
®The DiversiTech thermostat Control Page provides you with an easy and
intuitive screen to set your thermostat – all functions are available at the
touch of a finger! To access the Control Page, simply touch the Home
Page Screen… anywhere!
1 Current Room Temperature
2 Thermostat Control Mode: Run Program or Hold Temperature
3 Temperature Control Mode: Auto, Heat, Cool and Off
4 Fan Operation Mode; Fan Automatic, Fan Intermittent, Fan Off
5 Menu Page – Access all program features with this button
6 Temperature Control Mode: Heat and Cool temperature set points allows you to
change, raise or lower set point as desired. In “Auto” mode touch the Heat/Cool
button (Heat or Cool will flash once selected), then raise or lower set points as desired.
7 Displays Installer Message: review important information
8 Returns to the Home Page
16
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
HOME PAGE
®To return to the Home Page, simply touch icon at any time!
Home Page displays the following information:
1 Current Room Temperature
2 ºF/ºC Indicator
3 Thermostat Control Mode: Run Program or Hold Temperature
4 Temperature Control Mode: Auto, Heat and Cool
5 Fan Operation Mode: Fan Automatic, Fan Intermittent, Fan Off
6 Fan Operation Indicator
7 Heat Setpoint and Cool Setpoint
8 Date Stamp (Month/Day/Year)
9 Time: Choose between 12 hour or 24 hour clock
10 Outdoor Temperature
®Now that you know the basics let’s review the Control Page - and begin
to learn about all the unique features!

19
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
TEMPERATURE SETPOINTS
•AUTO, HEAT, COOL AND OFF
Based on your HVAC equipment you can quickly and easily select the mode
of operation - Automatic • Heat • Cool • Off
• AUTO – choose your heat and cool temperature setpoints – the temperature
will automatically adjust according to the requirement
• HEAT – choose your Heat setpoint
• COOL – choose your Cool setpoint
• OFF – no heating or cooling
•PROGRAM TEMPERATURE SETPOINTS:
• Choose HEAT: Heat will appear with a temperature range, select your temperature
• Choose COOL: Cool will appear with a temperature range, select your temperature
• Choose AUTO: A combined heat/cool button will appear – when heat flashes
– choose your temperature setpoint, touch the button to toggle to cool, then
set your temperature setpoint.
18
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
THERMOSTAT OPERATION MODES
• Your DiversiTech thermostat can run in Program Mode or can hold a fixed
temperature.
•RUN PROGRAM: Your custom program settings will be initiated - 4 events
per day including the fan mode
•HOLD TEMPERATURE: Allows you to raise or lower the temperature setpoint
by touching the heat/cool - to lower + to raise

21
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE
®To access the Menu Page, simply touch Menu from the Control Page.
Remember it is as easy as a touch of the button.
• Set-up of your DiversiTech thermostat is effortless with intuitive menu driven
programming - on our patented touchscreen.
• Enter Date and Time Settings: Program 7 days with 4 events per day to
improve efficiency and reduce energy costs
•Energy Watch: display kWh consumption as well as the dollar cost of the
HVAC System - configure this feature in Advanced Settings
•Clean the Screen without worry
• Access the Set Screen menu
•Advanced Settings for configuration of equipment
•Vacation Mode
• View Filter Monitor
20
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
FAN OPERATION MODES
• There are three modes of fan operation: Fan Auto, Fan On, Fan Off. When
the fan is running, the animated fan icon will appear on the Home Page.
•FAN AUTO: The fan will run on only when there is a demand for heating or cooling.
•FAN ON: The fan runs continuously
•FAN INTERMITTENT: The fan will run 10 minutes per 1/2 hour providing a
convenient way to improve air quality and save energy.

23
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE - PROGRAM SETTINGS
•PROGRAM SETTINGS: This feature easily and quickly programs your
thermostat to fit your needs and lifestyle. Remember by programming the
thermostat you can increase energy efficiency and reduce energy.
• 7 Day Programmable with 4 events per day including Fan Mode
• Select the Day of the Week
• Select the Event number: for example 1
• Select the Start Time: for example 7:00 AM
• Choose desired temperature setpoint – by raising or lowering the heat/cool button
• Choose the next event: for example 2 and repeat the steps
Once you have set all the events for one day you may
copy the same settings to other days of the week. First
ensure that your program settings are correct. Then
select the next day of the week that you would like to
have the same program setting. DiversiTech thermo-
stat will then prompt you to copy the settings.
Remember that you must choose Run Program from
the Control Page to activate this feature.
22
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE - DATE AND TIME SETTINGS
•Select the 12 or 24 hour clock display.
•Set the time of day by choosing hour and minute buttons.
•Set the Month, Day and Year by choosing the buttons.

25
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE - SCREEN OPTIONS
•CLEAN SCREEN: This function allows you to safely wipe and clean the screen with
a dampened cloth with out accidentally changing any of the settings; it places the
DiversiTech thermostat screen in a sleep mode for 15 seconds.
•SET SCREEN: Your DiversiTech thermostat has a number of options to ensure clear
viewing throughout the day and night, firstly;
• Backlight: choose between Auto or ON
• Reverse: Choose between a dark background (ON) or light background (OFF)
• Night Reverse: Another patented feature – ON: at 9PM the screen automat-
ically reverses the background for comfortable viewing at night – at 6:00AM
it returns to the Normal Mode for clear daytime viewing. OFF: screen back-
ground determined by “Reverse” function setting.
• Contrast: Provides a range from 1 – 10 to lighten or darken the screen best
suit your surroundings – we advise the setting of 7.
24
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE - ENERGY WATCH
•ENERGY WATCH: This unique and patented feature
provides a display of system energy consumption and
the cost of running your HVAC system. This feature
must be activated in the Advanced Settings - page 28.

27
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE - ADVANCED SETTINGS
®IMPORTANT INSTALLER SET-UP
This DiversiTech thermostat works with many different HVAC systems –
Gas, Oil, Electric Heat Pump, 2 Stage Heat Pump, 2 Stage Furnace and
Compressors. You must enter this menu to configure the thermostat with
HVAC operating equipment, and to fully customize the thermostat.
ADVANCED SETTINGS: To begin, hold your finger for 5 seconds on the
Advanced Settings Button – you will hear a beep telling you that you are in the
process of entering this feature.
A warning message will appear:
CAUTION: INCORRECT CONFIGURATION
CAN DAMAGE YOUR SYSTEM, CONTINUE?
YES NO
ACCEPT – YES
26
DIVERSITECH TOUCH SCREEN THERMOSTAT OPERATION
MENU PAGE - VACATION MODE
•VACATION SETTINGS: Allows you to set the temperature to a fixed setpoint dur-
ing the time you are on vacation, providing energy savings and comfort for your return
home. IMPORTANT: Heat or Cool must be selected from the Control Page before
entering the Vacation Settings page. To begin select Vacation Mode ON:
• Select the Start Date
• Select the End Date
• Adjust the Heat or Cool temperature setpoint: the Vacation mode begins at 10
PM on the day of your departure and ends at Midnight on the day of your arrival.
• When the Vacation mode is active the suitcase icon will appear on the Home
Page. Upon your return from vacation, a message Vacation Mode Ended will
be displayed on the screen. Simply touch the
screen to acknowledge the message, and your
DiversiTech thermostat will automatically revert
to the Program Settings if you are in Run
Program Mode or your can choose to Hold
Temperature to raise or lower the setpoint.
•FILTER MONITOR: Displays filter usage in days and
resets filter timer – when activated the Filter Monitor
icon will appear on your Home Page – this feature must
be activated in Advanced Settings.

29
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – WELCOME
•ºF: Choose between display units of Fahrenheit or Celsius for thermostat temperature
•SECURITY: The security settings allow you to protect your DiversiTech ther-
mostat from unauthorized use, and provides 2 levels of security. On your
Home Page once this feature is activated you will see a small lock icon.
• Turn Security On or Off – the Factory Setting PIN is 1111
• As a first time user you will be prompted to enter the Factory Setting PIN 1111
• Enter your new PIN and then Re-enter your new PIN once more.
• There are two modes of password protection: Full Lock Function does not allow
any changes unless the user enters the PIN. Partial Lock Function allows you to
change only the temperature setpoint without entering a PIN.
•INSTALLER MESSAGE: (up to 42 characters) to
appear at programmable intervals . Enter your
message on the screen using the keyboard – for
example service reminders or emergency contact
information. Type your message in using the keyboard,
upon completion choose OK. Set the number of
months after which you with the message to appear.
Touch the home or menu icon to exit.
28
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – WELCOME
•HOME BUTTON: Returns you to the Home Page at anytime- remember you will
have to re-enter through the Advanced Settings button.
•DAYLIGHT TIME : Choose Daylight Time On or Off dependent on your Time Zone.
•FILTER: A Helpful reminder to change or clean your air filter. The Filter Monitor
function indicates how many days of "fan run time" the air filter has been used. Reset
it each time after changing your air filter.
•ENERGY WATCH: By entering the HVAC system con-
sumption parameters rounded off to kW, you will have
a real time total of kilowatts and cost of consumption.
To review touch the Energy Watch button on the Menu
Page. EXAMPLE: Fan 1kW, Heat Pump 1kW/ton,
Furnace 5-30 kW, 7-9¢/kW
• This feature will run consecutively for 255 days. If
you do not enter your information what will appear on
the display is the total time the Compressor and the
Furnace have been operating.

31
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – SETTING THE DIFFERENTIAL
®THE DIVERSITECH 675-TS32 THERMOSTAT ALLOWS YOU TO CON-
TROL UP TO 3 STAGES OF HEATING AND 2 STAGES OF COOLING,
DEPENDENT ON THE TYPE OF SYSTEM YOU HAVE CONFIGURED.
•1ST STAGE DIFFERENTIAL: Set temperature difference between temperature set
point and actual temperature reading before 1st stage heating or cooling is initiated.
•2ND STAGE DIFFERENTIAL: Set temperature difference between 1st stage initiation
and 2nd stage heating or cooling initiation.
•3RD STAGE DIFFERENTIAL: Set temperature difference between 2nd stage initiation
and 3rd stage heating or cooling initiation.
•OB ENERGIZED: Reverses the Heat Pump OB Valve contact to HEAT or COOL
(manufacturer dependent).
30
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – CONFIGURING YOUR EQUIPMENT
®IMPORTANT: BY INADVERTENTLY MODIFYING COMPRESSOR AND
FURNACE SETTINGS, YOU MAY SERIOUSLY DEGRADE SYSTEM
PERFORMANCE.
®CHOOSE SYSTEM HEATING AND/OR COOLING EQUIPMENT –
REMEMBER ALL YOU NEED TO DO IS TOUCH THE BUTTON WITH
YOUR FINGER.
• Choose Heat Pump, 2 Stage Heat Pump, Air Conditioning, No Compressor – please
review the wiring table and diagram for wiring instructions.
• Choose Furnace Off (No Furnace), Electric Furnace, Emergency Electrical Furnace
(additional electric furnace which will come on in emergency mode in conjunction
with electric furnace), Gas Furnace, Oil Furnace, and 2 Stage Gas Furnace; please
review the wiring table and diagram for wiring instructions.
•CYCLE RATE: Set Maximum compressor cycles per hour.
•AUTO CHANGE: Set the minimum difference between Auto Mode, Heat and Cool
temperature set points.

33
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – HEAT PUMP
• HP “ON” when Furnace On: Heat Pump and Furnace can operate together when
2nd stage furnace is required. HP “OFF” when Furnace On: turns off the Heat Pump
when the furnace is On (required on some gas or oil furnaces).
32
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – TIMER FEATURE
• Specify the number of minutes for which Stage 1 will function until Stage 2 is
activated to help raise (or cool) temperature (if the temperature set point is not
reached). This unique function avoids excess compressor wear in the case where
the necessary temperature set point is not met through setting of the Staging
Differentials. Set to “00” to disable.

3534
®CALIBRATION OF TEMPERATURE
Your DiversiTech thermostat is rated for +/-1° temperature accuracy.
• If you have determined due to drafts, sunlight or other environmental factors that your
thermostat needs calibration, follow this easy guide. Common causes of offset are
lack of air circulation in the vicinity of your DiversiTech thermostat or skylights.
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – CALIBRATION
®TEMPERATURE CALIBRATION TABLE
• Firstly, determine with a calibrated thermometer the temperature difference –
then use the following table to adjust your thermostat.
Thermostat Fahrenheit Celsius
Calibration Number Change Change
+3.0 +6°F +3.0°C
+2.5 +5°F +2.5°C
+2.0 +4°F +2.0°C
+1.5 +3°F +1.5°C
+1.0 +2°F +1.0°C
+0.5 +1°F + .5°C
Factory Setting 00 No Correction Required
-0.5 -1°F -.5°C
-1.0 -2°F -1°C
-1.5 -3°F -1.5°C
-2.0 -4°F -2.0°C
-2.5 -5°F -2.5°C
-3.0 -6°F -3.0°C
DIVERSITECH TOUCH SCREEN THERMOSTAT CONFIGURATION
ADVANCED SETTINGS – CALIBRATION

37
TROUBLESHOOTING
•Touch screen buttons do not function properly. Remove cover, press the reset
button located in the bottom left corner then accurately touch 3 target centers on
the screen when prompted.
•Air conditioning turns on in HEAT mode and heating turns on in COOL mode.
Reverse the OB valve (see “Advanced Settings” Page 31).
•PARTIAL LOCK and FULL LOCK do not function. You must not touch the screen
for 1 minute for DiversiTech thermostat to automatically lock.
•Thermostat appears normal until the screen becomes blank when the com-
pressor or heating system turns on. You need to connect the “C” wire. 4 wire
system will not function unless the heat and compressor contactors can supply enough
current to power the thermostat with only 4 wires, if you cannot hook up the “C”
wire another possible solution is to connect one 250 ohm 10 watt resistor in the
HVAC room, for cooling problems between C and W or in the case of heating prob-
lem between C and Y1.
•I forgot my PIN and cannot unlock the thermostat. Remove the cover plate, press
the reset button located in the bottom right corner, as soon as the message “touch
to reset password” appears touch the screen, your PIN will be erased and the ther-
mostat will unlock.
36
SIMPLE THERMOSTAT MODE
®DIVERSITECH THERMOSTAT CAN ALSO FUNCTION AS A NON-PRO-
GRAMMABLE THERMOSTAT AFTER IT HAS BEEN CONFIGURED.
• To enable “Simple Mode”, press the reset button (take off the thermostat face-
plate and press the reset button located in the bottom right-hand corner). The
message “Touch for simple thermostat” will appear. Touch the screen, and
DiversiTech thermostat becomes a simplified non-programmable thermostat.
• Please note that when changing to Simple Mode, you will not lose any of the
settings you have previously entered in the “Programmable Mode”.
• To revert back to the Programmable DiversiTech thermostat, simply press the
reset button and touch the screen when the message “Touch for Programmable
Thermostat” appears.
Simple Mode has the following basic features:
Temperature Control Modes:
Fan Operation Modes:

39
WARRANTY
Hardware
DiversiTech warrants the original end user (“Customer”) that new DiversiTech branded products will be free from defects
in workmanship and materials, under normal use, for two (2) years from the original purchase date.
Software
DiversiTech warrants to Customer that the DiversiTech thermostat software will perform in substantial conformance to
its program specifications for a period of two (2) years from the date of the original purchase.
Exclusions
This warranty excludes (1) physical damage to the surface of the product, including cracks or scratches on the touch-
screen or outside casing; (2) damage caused by misuse, neglect, improper installation, unauthorized attempts to open,
repair, or modify the product, or any other cause beyond the range of intended use; (3) damage caused by accident, fire,
power changes, other hazard, or Acts of God; or (4) use of the product with any device if such device causes the problem.
Exclusive Remedies
Should a covered defect occur during the warranty period and Customer notifies DiversiTech, Customer’s sole and exclu-
sive remedy will be, at DiversiTech’s sole option and expense, to repair or replace the product. Replacement products or
parts may be new or reconditioned or a comparable version of the defective item. DiversiTech warrants any replaced
product or part for a period of ninety (90) days from shipment, or through the end of the original warranty, whichever is
longer.
Obtaining Warranty Service
Customer must contact and return product to a local DiversiTech product dealer or installer within the applicable war-
ranty period to obtain warranty service. Dated proof of original purchase will be required. DiversiTech will not be respon-
sible for Customer’s memory data contained in, stored on, or integrated with any products returned to DiversiTech for
repair, whether under warranty or not.
Warranty Exclusive
THE FORGOING WARRANTIES AND REMEDIES ARE EXCLUSIVE AND IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR
IMPLIED, INCLUDING WARRANTIES OF MERCHANTABILITY, FITNESS FOR A PARTICULAR PURPOSE, CORRESPONDENCE WITH
DESCRIPTION, AND NON-INFRINGEMENT, ALL OF WHICH ARE EXPRESSLY DISCLAIMED BY DIVERSITECH AND ITS SUPPLI-
ERS.
Disclaimer
NEITHER DIVERSITECH NOR ITS SUPPLIERS SHALL BE LIABLE FOR INCIDENTAL, CONSEQUENTIAL, INDIRECT, SPECIAL,
OR PUNITIVE DAMAGES OF ANY KIND, OR FINANCIAL LOSS ARISING OUT OF OR IN CONNECTION WITH THE SALE OR
USE OF THIS PRODUCT, WHETHER BASED IN CONTRACT, TORT (INCLUDING NEGLIGENCE) OR ANY OTHER THEORY,
EVEN IF DIVERSITECH HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES. DIVERSITECH’S ENTIRE LIABILITY
SHALL BE LIMITED TO REPLACEMENT OR REPAIR OF THE PRODUCT.
38
IMPORTANT NOTICE
®WHEN USING THIS THERMOSTAT WITH A GAS FURNACE
A COMMON WIRE (C) MUST BE CONNECTED.
•When working without a common wire:
Aconfirm in heat mode the cooling does not switch on or Bconfirm in cooling mode
the heat does not switch on.
• If test Aor Bfail or the thermostat shuts down in either heat or cool mode then it is
necessary to connect a common wire, (C), alternatively it may be possible to solve
this issue by simply connecting the 250 ohm 10 watt resistor between C and W (in
the case of a cooling problem – see B) or between C and Y1 (in the case of a heat-
ing problem - see A) at the HVAC equipment.
• When working without a common wire, Aconfirm that when there is a call for heat,
cooling does not also activate, and when there is a call for cool, heating does not
also activate.
• If using the configuration of Heat Pump and Furnace with no Common Wire con-
firm that when Heat Pump and Furnace are working together (both stages are oper-
ating at the same time) that the display does not go blank, if so you must use a
Common Wire.
• This thermostat is equipped to run with two separated power transformers if required
RC and RH. Terminals RC and RH are internally connected together however you
should wish to use two transformers simply cut with a blade the copper trace on
the printed circuit board located between the C and Y2 screw terminals.
Table of contents
Other DIVERSITECH Thermostat manuals
Popular Thermostat manuals by other brands

Heatmiser
Heatmiser neoStat-hw V2 instruction manual

White Rogers
White Rogers 1F80ST-0471 Installation and operating instructions

Lennox
Lennox ComfortSense L3021H installation instructions

Hunter
Hunter 42227 owner's manual

Watts
Watts FloorStat 500650-120CS user manual

Honeywell
Honeywell T8621A user manual

Honeywell Home
Honeywell Home The Digital Round T8775A installation instructions

Venstar
Venstar ColorTouch T6900 Owner's manual and installation instructions

Goodman
Goodman TSTAT G2200C Brochure & specs

Honeywell
Honeywell T810D installation instructions

Elko
Elko iNels RFTC-10/G manual

Jung
Jung 1790RTR operating instructions