360 deg ceiling PIR with Audio detection
INSTALLATION AND OPERATING INSTRUCTIONS
FORWARD
The GX360 is a 12 volt DC ceiling passive detectors with the addition of Audio detection. Up to four (4) GX360 detectors may be
connected to one (1) DX360 control unit. Four core alarm or telephone cable is used to wire the detectors to the control unit.
The DX360 produces 12 volts DC for the GX360 detectors and switches mains voltage up to 3KW of incandescent lighting or
2KW of fluorescent lighting.
A light sensor which is built in to the GX360 detectors inhibits the DX360 from turning the lights ON if the room is too bright.
The DX360 can only be initiated by PIR detection but once activated, sound detection will keep the lights ON. This is especially
useful in offices where people sit very still or are obscured by furniture. The sound of speech or typing on a key board will be
sufficient to maintain detection.
FIXING
The GX360 can be fitted to a wall or ceiling where it will view 360
degrees to cover the appropriate area. The range is variable up to
12 metres. As the GX360 detector also detects sound, it is
important to fit the detector on a solid surface with limited vibration.
Any vibration will be picked up by the detector and cause it to keep
the lighting ON. An audio sensitivity control is provided to reduce
this detection or disable it altogether.
3 4 5 6 7 8 9 10 11 12
- + LS T - + LS T
DX360
TECHNICAL HELPLINE 0181 3615255
LUMINITE Electronics LTD
2a Bellevue Road, Friern Barnet
LONDON N11 3ER
Tel: 0181 3687887 Fax: 0181 3683952
www.luminite.co.uk
SPECIFICATION
•Input voltage 12 volts DC
•Power consumption 15 m/a
•Detector output voltage 3-12 volts DC
•Audio sensitivity Adjustable
•PIR sensitivity Adjustable
GX360 GX360 etc.
Fig 1
DETECTOR WIRING
The detectors may be wired in a chain or alternatively wired back
separately to the control unit using 4 core alarm cable (7/2/4) or
telephone cable. The wiring example in Fig 1 shows two detectors
wired to one DX360. Up to four (4) detectors may be connected to
one DX360 control unit.
All GX360 detectors have built in light sensors but only one is required
for each DX360 control unit as shown.
COMMISSIONING.
Set the DX360 for walk test. Allow about two minutes for the
detectors to settle before beginning the tests. Turn both audio and
PIR sensitivity controls to maximum. Each time movement or sound
is detected by the GX360’s the red trigger indicator will light. In
addition the room lights will come on for about 20 seconds. Walk about
within the detection area to make sure you are satisfied with the
coverage. Try to keep quiet when walk testing or turn the audio
detection control on the GX360 down to minimum. When satisfied
with the set up, set the DX360 up for normal use. See separate
DX360 instructions.
TROUBLE SHOOTING
PROBLEM Lights remain ON
SOLUTION Look at the detector and observe the red
detection indicator. In a quiet room
without movement this indicator should
not light. If it does, turn the AUDIO
sensitivity control down as it may be
picking up vibration from the ceiling.
Turning this control down fully stops the
audio detection altogether.
If the problem persists, turn down the PIR
sensitivity as well.
If both the above methods fail, try
removing the trigger wire from terminal 5.
The lights must turn off after the
set time period. If they do not, check the
wiring for Live In and Live Out to make
sure they are the correct way round.
Optional over-ride switch
Lens Information
Mounting height Sensing
Above floor diameter
6.0m 15.2m
5.4m 14.0m
4.8m 12.6m
4.2m 11.6m
3.6m 10.4m
3.0m 9.2m
2.7m 8.6m
2.4m 8.0m
At 2.4m
Ceiling height
4.0m 4.0m
7.6m
At 2.4m
Ceiling height
At 2.4m ceiling height
the detectors cover a
radius of 4 metres.
(Diameter 8 metres)
To cover a large area it will be
necessary to use more than one
detector as shown. Detector
coverage should overlap for best
results.
DX360
Lighting
Control Unit
Mains IN
220-240V
50Hz
To
Lighting
Max 2KW
Resistive
4 core cable

Popular Security Sensor manuals by other brands

Visonic NEXT K9-85 installation instructions

Visonic

Visonic NEXT K9-85 installation instructions

Refco AQUASWITCH Installation, operation and maintenance guide

Refco

Refco AQUASWITCH Installation, operation and maintenance guide

Energy Saving Sensors HC-7B installation manual

Energy Saving Sensors

Energy Saving Sensors HC-7B installation manual

Digiscan Labs Protect 1207i user manual

Digiscan Labs

Digiscan Labs Protect 1207i user manual

Velleman ham1011 manual

Velleman

Velleman ham1011 manual

Ness Quantum Pet aware Dual Installation notes

Ness

Ness Quantum Pet aware Dual Installation notes

Wiseup WBD100 user guide

Wiseup

Wiseup WBD100 user guide

RKI Instruments 35-3010RK-03 manual

RKI Instruments

RKI Instruments 35-3010RK-03 manual

Visonic SRN-2000 installation instructions

Visonic

Visonic SRN-2000 installation instructions

Pilz PSEN 2.1p-41 operating manual

Pilz

Pilz PSEN 2.1p-41 operating manual

C-LOGIC 645-MD instruction manual

C-LOGIC

C-LOGIC 645-MD instruction manual

careium i10 Technical guide

careium

careium i10 Technical guide

Riken Keiki GD-10X Series operating manual

Riken Keiki

Riken Keiki GD-10X Series operating manual

Mier Drive Alert DA-600 installation manual

Mier

Mier Drive Alert DA-600 installation manual

jablotron GS-133 quick start guide

jablotron

jablotron GS-133 quick start guide

Autonics LSE-4A5R2 manual

Autonics

Autonics LSE-4A5R2 manual

Thermocable ProReact EN Analogue installation instructions

Thermocable

Thermocable ProReact EN Analogue installation instructions

Code 3 Sprinter Installation & operation manual

Code 3

Code 3 Sprinter Installation & operation manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.