Domus Ventilation DX Series Instruction Manual

1.0 Safety Informaon
IMPORTANT: Installaon or replacement of units or spare parts must be carried out by a qualified or Domus
approved service engineer/ electrician and in accordance with IEE or local naonal wiring regulaons.
2.0 Introducon
The Domus DX Roof Fan Kit is available in 6, 9 and 12 inch impeller sizes
suitable for supply or extract and can form the heart of an automac
venlaon system.
Ensure adequate air replacement for the fan and any fuel burning
appliance in the room.
Two types of roof fan kits are available, one for a flat roof and the other
to cover a pitched roof installaon.
The applicaons are ideally suitable for direct venlaon of a top storey
area.
The fan is IP24 splash proof approved with the motor rated at IP44.
Roof Terminal components are made in so grey colours from ultra
violet stable Styrosun so they will blend with most decors and will not
fade in sunlight.
2.1 Sensors
Operated via a separately wired fused spur (byothers) or operated
via the oponal DX-CON remote controller allowing supply or extract,
variable speed and automac or manual switching of several fans if
desired (see wiring details).
2.2 Switching
Sensors are available as remote units or integral ‘plug in’ units. They
are able to control mulple fans, depending on sensor and fan types.
Integral sensors arequick and easy to install and are aesthecally
pleasing, whilst remote sensors give the benefit of locaon close to the
pollutant source.
Remote Sensors should be posioned at least 1.5m abovethe floor and
away from direct sources of heat such as radiators etc.
Opons include: Humidity, Air Quality, Passive Infra Red, Temperature
and Timer versions.
Further informaon is available in the relevant secon .
Roof Installaon Accessories
A range of roof installaon accessories is available. Further informaon
on page 8.
2.1.1 Coding For Flat Roof Fan Kits
Roof Fan Kits are supplied as a complete package with all
installaon parts included.
Figure 1. Typical installaon on flat roof upstand, direct venlaon.
Descripon
Code
6" Flat Roof Fan Kit Complete DX6FR
9" Flat Roof Fan Kit Complete DX9FR
12" Flat Roof Fan Kit Complete DX12FR
1.0 Safety Informaon
IMPORTANT: Installaon or replacement of units or spare parts must be carried out by a qualified or Domus
approved service engineer/ electrician and in accordance with IEE or local naonal wiring regulaons.
2.0 Introducon
The Domus
flat roof Fan
Kit is available in 6, 9 and 12 inch impeller sizes
suitable for supply or extract and can form the heart of an automac
venlaon system.
Ensure adequate air replacement for the fan and any fuel burning
appliance in the room.
Two types of roof fan kits are available, one for a flat roof and the other
to cover a pitched roof installaon.
The applicaons are ideally suitable for direct venlaon of a top storey
area.
The fan is IP24 splash proof approved with the motor rated at IP44.
Roof Terminal components are made in so grey colours from ultra
violet stable Styrosun so they will blend with most decors and will not
fade in sunlight.
2.1 Sensors
Operated via a separately wired fused spur (by others) or operated
via the oponal DX-CON remote controller allowing supply or extract,
variable speed and automac or manual switching of several fans if
desired (see wiring details).
2.2 Switching
Sensors are available as remote units or integral ‘plug in’ units. They
are able to control mulple fans, depending on sensor and fan types.
Integral sensors are quick and easy to install and are aesthecally
pleasing, whilst remote sensors give the benefit of locaon close to the
pollutant source.
Remote Sensors should be posioned at least 1.5m above the floor and
away from direct sources of heat such as radiators etc.
Further informaon is available in the relevant secon .
Roof Installaon Accessories
A range of roof installaon accessories is available. Further informaon
on page 8.
2.1.1 Coding For Flat Roof Fan Kits
Roof Fan Kits are supplied as a complete package with all
installaon parts included.
Figure 1. Typical installaon on flat roof upstand, direct venlaon.
Descripon Code (50 Hz)
6" Flat Roof Fan Kit Complete DX6FR
9" Flat Roof Fan Kit Complete DX9FR
12" Flat Roof Fan Kit Complete DX12FR
approved service engineer/ electrician and in accordance with IEE or local national wiring regulations.
2.0 Introduction
The Domus DX Roof Fan Kit is available in 6, 9 and 12 inch impeller sizes
suitable for supply or extract and can form the heart of an automatic
ventilation system.
Ensure adequate air replacement for the fan and any fuel burning
appliance in the room.
Two types of roof fan kits are available, one for a flat roof and the other
to cover a pitched roof installation.
The applications are ideally suitable for direct ventilation of a top storey
area.
The fan is IP24 splash proof approved with the motor rated at IP44.
Roof Terminal components are made in soft grey colours from ultra
violet stable Styrosun so they will blend with most decors and will not
fade in sunlight.
2.1 Sensors
Operated via a separately wired fused spur (by others) or operated
via the optional DX-CON remote controller allowing supply or extract,
variable speed and automatic or manual switching of several fans if
desired (see wiring details).
2.2 Switching
Sensors are available as remote units or integral ‘plug in’ units. They
are able to control multiple fans, depending on sensor and fan types.
Integral sensors are quick and easy to install and are aesthetically
pleasing, whilst remote sensors give the benefit of location close to the
pollutant source.
Remote Sensors should be positioned at least 1.5m above the floor and
away from direct sources of heat such as radiators etc.
Options include: Humidity, Air Quality, Passive Infra Red, Temperature
and Timer versions.
Further information is available in the relevant section .
Roof Installation Accessories
A range of roof installation accessories is available. Further information
on page 8.
2.1.1Coding For Flat Roof Fan Kits
2.2.1 Coding For Pitched Roof Fan Kits
Roof Fan Kits are supplied as a complete package with all
installation parts included.
Figure 1.Typical installation on flat roof upstand, direct ventilation.
Figure 2. Typical installation on pitched roof, direct ventilation.
Description Code (50 Hz)
6" Flat Roof Fan Kit Complete DX6FR
9" Flat Roof Fan Kit Complete DX9FR
12" Flat Roof Fan Kit Complete DX12FR
Description Code (50 Hz)
6" Pitched Roof Fan Kit Complete DX6PR
9" Pitched Roof Fan Kit Complete DX9PR
12" Pitched Roof Fan Kit Complete DX12PR
AA
O/A height
above roof D
Depth of roof
construction C
Depth of
Fan B
3.0 Dimensions
Figure 3. Typical installation on pitched roof, direct ventilation.
V E N T I L A T I O N
DX Flat Roof Fan Kit 50Hz/60Hz
Ducted to Ceiling & Direct Venlaon) for at roofs
Installaon and Maintenance
1.0 Safety Information
IMPORTANT: Installation or replacement of units or spare parts must be carried out by a qualified or Domus
LAB1347R May 2018 Page 1
Remote options include DX-CON and DX-RH (Relative Humidity).
Integral options include DX-PIR, DX-T (run-on timer) and DX-H (humidity).

LAB1347R May 2018 Page 2
V E N T I L A T I O N
2
150mm min.
C x D ceiling opening
Ceiling panel
Roof slab
Roof felt/
Lead flashing
3.0 General Dimensions
*minimum height of Flat roof upstand (by others).
DX Unit A B C* D
6" 269 161 150 170
9" 337 158 150 180
12" 413 172 150 185
Fan Code A B C D
DX6FR 610 610 300 300
DX9FR 610 610 450 450
DX12FR 695 695 450 450
4.0 Flat Roof Kit Installation
Prepare a timber or builders work upstand on the roof to the
dimensions below. Carry roof felt or weathering material over the curb
to ensure a good seal. The kit is supplied with the fan, spacer and grille
assembled for transit purposes.
The instructions opposite assume the fan assembly has been separated
to begin the installation.
Figure 2. Flat roof upstand construction details.
A x B overall finished curb size
Spacer
Roof
Terminal
Fan unit
Internal
Grille
Upstand
fixings (4)
Terminal/
fixings (4)
Fan / Terminal
Grille
fixings
(2)
fixings (4)
Upstand
Fan / Spacer
Release the electrical cover
from the fan plate.
For various wiring options
see wiring details page 4.
Spacer
1
2
3
5
4
6
7
Feed the supply cable
through the spacer.
Drill through the
dimples in the Roof
Terminal.
Fit the grille to
the fan, locating
top lip before
fixing.
Offer up the spacer
section to the terminal
underside and fix using
the 4, 5mm screws
provided.
Assemble the fan
to the spacer
section 4 panhead
screws.
Position centrally &
squarely over curb and
fix using 6mm wood
screws and sealing
washers.
Figure 3. Exploded assembly Flat Roof Kit.
2
150mm min.
C x D ceiling opening
Ceiling panel
Roof slab
Roof felt/
Lead flashing
3.0 General Dimensions
*minimum height of Flat roof upstand (by others).
DX Unit A B C* D
6" 269 161 150 170
9" 337 158 150 180
12" 413 172 150 185
Fan Code A B C D
DX6FR 610 610 300 300
DX9FR 610 610 450 450
DX12FR 695 695 450 450
4.0 Flat Roof Kit Installation
Prepare a timber or builders work upstand on the roof to the
dimensions below. Carry roof felt or weathering material over the curb
to ensure a good seal. The kit is supplied with the fan, spacer and grille
assembled for transit purposes.
The instructions opposite assume the fan assembly has been separated
to begin the installation.
Figure 2. Flat roof upstand construction details.
A x B overall finished curb size
Spacer
Roof
Terminal
Fan unit
Internal
Grille
Upstand
fixings (4)
Terminal/
fixings (4)
Fan / Terminal
Grille
fixings
(2)
fixings (4)
Upstand
Fan / Spacer
Release the electrical cover
from the fan plate.
For various wiring options
see wiring details page 4.
Spacer
1
2
3
5
4
6
7
Feed the supply cable
through the spacer.
Drill through the
dimples in the Roof
Terminal.
Fit the grille to
the fan, locating
top lip before
fixing.
Offer up the spacer
section to the terminal
underside and fix using
the 4, 5mm screws
provided.
Assemble the fan
to the spacer
section 4 panhead
screws.
Position centrally &
squarely over curb and
fix using 6mm wood
screws and sealing
washers.
Figure 3. Exploded assembly Flat Roof Kit.
Installation and Maintenance
DX Flat Roof Fan Kit 50Hz/60Hz

LAB1347R May 2018 Page 3
V E N T I L A T I O N
Installation and Maintenance
DX Flat Roof Fan Kit 50Hz/60Hz
5.0 Electrical Installaon
Electrical work should be undertaken by a qualified electrician in
accordance with the wiring regulaons.
1
2
3
4
Clamp the cable and complete the connecons.
Release the electrical panel from the fan plate.
Remove the terminal cover.
Refit terminal cover before replacing the electrical panel.
5.1 Wiring
6.1.1Fan Operated By On / Off Switch
5.1.2 Fan Operated By Integral Sensor
5.1.3 Basic Fan Operated By Remote Sensor
L5
L4
L3
L2
L1
N
or
L
N
Double pole
DX Fan unit
isolator
Fuse
max. 3 amp
Double pole
isolator
Fuse
max. 3 amp
L5
L4
L3
L2
L1
N
or
L
N
DX Fan unit with
integral sensor
SL
(Swit ched Live)
Double
pole
isolator
Fuse
max.
3 amp
Remote Sensor
L1 L2 N
DX Fan unit
or
L5
L4
L3
L2
L1
N
Connect link wire between L2 & L4 for extract OR
connect link wire between L2 & L3 for supply.
Connect link wire between L2 & L4 for extract OR
connect link wire between L2 & L3 for supply.
Connect link wire between L2 & L4 for extract OR
connect link wire between L2 & L3 for supply.
Connect switched live signal to L5 for integral mer module.
IMPORTANT
Isolaon - Before commencing work, make sure that the unit is
electrically isolated from the mains supply.
IMPORTANT
(Shuer Operaon DX fans)
There will be a short delay on startup and shutdown of approximately
40 seconds. This is normal.
5.0 Electrical Installaon
Electrical work should be undertaken by a qualified electrician in
accordance with the wiring regulaons.
1
2
3
4
Clamp the cable and complete the connecons.
Release the electrical panel from the fan plate.
Remove the terminal cover.
Refit terminal cover before replacing the electrical panel.
5.1 Wiring
6.1.1Fan Operated By On / Off Switch
5.1.2 Fan Operated By Integral Sensor
5.1.3 Basic Fan Operated By Remote Sensor
L5
L4
L3
L2
L1
N
or
L
N
Double pole
DX Fan unit
isolator
Fuse
max. 3 amp
Double pole
isolator
Fuse
max. 3 amp
L5
L4
L3
L2
L1
N
or
L
N
DX Fan unit with
integral sensor
SL
(Swit ched Live)
Double
pole
isolator
Fuse
max.
3 amp
Remote Sensor
L1 L2 N
DX Fan unit
or
L5
L4
L3
L2
L1
N
Connect link wire between L2 & L4 for extract OR
connect link wire between L2 & L3 for supply.
Connect link wire between L2 & L4 for extract OR
connect link wire between L2 & L3 for supply.
Connect link wire between L2 & L4 for extract OR
connect link wire between L2 & L3 for supply.
Connect switched live signal to L5 for integral mer module.
IMPORTANT
Isolaon - Before commencing work, make sure that the unit is
electrically isolated from the mains supply.
IMPORTANT
(Shuer Operaon DX fans)
There will be a short delay on startup and shutdown of approximately
40 seconds. This is normal.

LAB1347R May 2018 Page 4
V E N T I L A T I O N
Installation and Maintenance
DX Flat Roof Fan Kit 50Hz/60Hz
5.1.4 Supply / Extract Fan Operated via remote DX-CON Control
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
5.1.5 Supply / Extract Fan Operated via remote DX-CON
Control and Remote Sensor(s)
Remote switch may be set: On/Off, Supply/ Extract, Economy/Std.
(variable speed), Auto/Manual.
One or more Remote Sensors may be wired in parallel to one DX-CON
Control.
Humidity Sensor: DX-RH
5.1.6 Supply / Extract Fan Operated via remote DX-CON
Control and an Integral Sensor
DX-CON controller
L5
L4
L3
L2
L1
N
L4
L3
L2
L1
N
L1
N
Double
pole
isolator
Fuse
max.
3 a mp
L
N
DX Fan unit
mains
supply
DX-CON controller
L5
L4
L3
L2
L1
N
L4
L3
L2
L1
N
L1
N
Double
pole
isolator max.
Fuse
3 a mp
L
N
DX Fan unit
Remote sensor
mains
L2 L1 N
supply
DX-CON controller
L5
L4
L3
L2
L1
N
L4
L3
L2
L1
N
L1
N
Double
pole
isolator
Fuse
max.
3 a mp
L
N
DX Fan unit with
integral sensor
Required if using
integral Timer
mains
supply
Model
Input Power
(W) Weight
(kg)
Max. Economy
DX6FR supply & extract 38 20 6.3
DX9FR supply & extract 50 37 8.7
DX12FR supply & extract 100 70 11.0
A single sensor will switch all fans if more than one fan is being
operated by a single DX-CON controller.
NOTE: Multi-fan options:
Up to 5 fans (size 6"/9") can be controlled by one DX-CON.
Up to 2 fans (size 12") can be controlled by one DX-CON.
Do not mix different fan sizes on the same controller.
5.2 Unit Consumption & Weight
Note figures are for extract only at 50hz.
5.3 Electrical Specification
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm max. or min. Fuse: 3 amp (if fan is supplied
from a 5A lighting circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 5 x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled from
the same CON speed control. This avoids the possibility of one fan (if
speed controlled at a lower flow rate) being stalled by the other fan(s).
Adequate make-up air provision sufficient to provide ventilation in
accordance with building regulations is required in all rooms. This
should be checked during commissioning with all fans in the same room
running together in all possible configurations.
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
Remote switch may be set: On/Off, Forward/Reverse, Economy/Std.
(variable speed), Auto/Manual.
Maximum one Integral Sensor per fan, 6/9/12 denotes unit size identity.
Humidity Sensor: DX-H6/9/12
Passive Infra Red Sensor: DX-PIR6/9/12
Run on Timer: DX-T6/9/12.
A single sensor will switch all fans if more than one fan is being
operated by a single DX-CON controller.
NOTE: Multi-fan options:
Up to 5 fans (size 6"/9") can be controlled by one DX-CON.
Up to 2 fans (size 12") can be controlled by one DX-CON.
Do not mix different fan sizes on the same controller.

LAB1347R May 2018 Page 5
V E N T I L A T I O N
Installation and Maintenance
DX Flat Roof Fan Kit 50Hz/60Hz
Plug the connector into the required sensor module. Screw the sensor module into position.
1
2
4
3
5
6 7
Push the repacement cover into the grille front.
Lift out the sensor module wiring connector.
Push out the sensor area cover from the grille.
Remove the module plate.
Unscrew the module plate from motor plate assembly.
6.4 Fitting Integral Sensors (Optional)
Note: Before following the pictorial sequence shown, first remove the
fans front cover grille (2 screws). Release the four main corner screws
and lift out the motor/fan plate assembly. Remove the electrical cover
plate opposite the sensor plate. Follow the pictorial sequence on this
page.
Plug the connector into the required sensor module. Screw the sensor module into position.
1
2
4
3
5
6 7
Push the repacement cover into the grille front.
Lift out the sensor module wiring connector.
Push out the sensor area cover from the grille.
Remove the module plate.
Unscrew the module plate from motor plate assembly.
5.4 Fitting Integral Sensors (Optional)
Note: Before following the pictorial sequence shown, first remove the
fans front cover grille (2 screws). Release the four main corner screws
and lift out the motor/fan plate assembly. Remove the electrical cover
plate opposite the sensor plate. Follow the pictorial sequence on this
page.

LAB1347R May 2018 Page 6
V E N T I L A T I O N
Installation and Maintenance
DX Flat Roof Fan Kit 50Hz/60Hz
Fix backplate box to the prepared wall.
Feed approx. 200mm of supply cable into the box.
1
2
4
3
5
6
7
Fit the control into the backplate box and secure.
Test the installation.
Lift up panel and remove two screws to dismantle unit.
Spot through backplate box and drill and plug the wall.
Connect the end of the cable into the control block.
200mm
1.5m
Push out backplate box cable entry using a screwdriver.
6.5 Fitting Remote Controller DX-CON or
Remote sensors (optional)
The DX-CON Multi Fan Control provides supply or extract, variable
speed and automatic or manual switching of several fans if desired, (see
note below). The control is best mounted approx 1.5m above the floor.
Remote Sensors are available for Humidity, Air Quality and Passive Infra
Red control. Remote Sensors should be positioned at least 1.5m above
the floor and away from direct heat sources e.g. radiators.
Note:
Up to 5 fans (size 6 / 9 inch) can be controlled by one DX-CON.
Up to 2 fans (size 12 inch) can be controlled by one DX-CON.
Do not mix different fan sizes on the same controller.
Fix backplate box to the prepared wall.
Feed approx. 200mm of supply cable into the box.
1
2
4
3
5
6
7
Fit the control into the backplate box and secure.
Test the installation.
Lift up panel and remove two screws to dismantle unit.
Spot through backplate box and drill and plug the wall.
Connect the end of the cable into the control block.
200mm
1.5m
Push out backplate box cable entry using a screwdriver.
itting Remote Controller DX-CON or
5.5 F
ote sensors (optional)
Rem
The DX-CON Multi Fan Control provides supply or extract, variable
speed and automatic or manual switching of several fans if desired, (see
note below). The control is best mounted approx 1.5m above the floor.
Remote Sensors are available for Humidity only. Remote Sensors should be
positioned at least 1.5m above the floor and away from direct heat sources
e.g. radiators.
Note:
Up to 5 fans (size 6 / 9 inch) can be controlled by one DX-CON.
Up to 2 fans (size 12 inch) can be controlled by one DX-CON.
Do not mix different fan sizes on the same controller.

Page 7
V E N T I L A T I O N
Installation and Maintenance
DX Flat Roof Fan Kit 50Hz/60Hz
6.0 Ancillaries
Single Spigot Adaptor
Used in conjuncon with flexible ducng systems.
Mounted onto the front of the Spacer secon using the 4 off 5mm x
40mm brass screws supplied with the Single Spigot Adaptor. Replaces
the internal grille.
Can also be used connected directly to a Roof Terminal using the 4 off
5mm x 40mm brass screws supplied with the Single Spigot Adaptor.
Manufactured from HIPS material.
Flexible Ducng and Installaon Accessories
Afull range of ducng and installaon accessories is available from
Domus. Call Domus on 02920 885231 to request literature.
7.0 Maintenance
Periodically, at least once a year or more frequently in case of heavy
use, remove the dirt and encrustaon from the grille(s) fan impeller
and motor casing. Ensure the impeller is not cracked or deformed and is
able to rotate freely and without oscillaon.
Do not use any solvents to clean this product.
10.0 Aer Sales Enquiries
For technical assistance or further product informaon, including spare
parts and replacement components, please contact the Aer Sales
Department.
8.0 Replacement Of Parts
As a manufacturer Domus is aware that me is important. In the event
of a breakdown of this equipment, it should be adequately packaged
and returned to Domus.
Please telephone Domus before posng your unit.A returns number will
be issued to idenfy your package.
We will endeavour to repair or replace it within fiveworking days of
receipt.See our warranty terms.
9.0 Warranty
The 3 year warranty starts from the day of delivery and includes parts
and labour for the first year.The remaining period covers replacement
parts only.
This warranty is void if the equipment is modified without
authorisaon, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good pracce.
Installaon or replacement of units or spare parts must be carried out
by a qualified or Domus approved service engineer/ electrician and in
accordance with IEE or local naonal wiring regulaons.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Condions of Sale.
Customers purchasing from outside of the UK should contact Domus
Internaonal Sales office for further details.
A unit returned to Domus should be suitably protecvely packaged and
clearly marked with the ‘returns number’ obtained from Domus prior to
posng.
Technical or commercial consideraons may, from me to me, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior noce.
6.0 Ancillaries
Single Spigot Adaptor
Used in conjuncon with flexible ducng systems.
Mounted onto the front of the Spacer secon using the 4 off 5mm x
40mm brass screws supplied with the Single Spigot Adaptor. Replaces
the internal grille.
Can also be used connected directly to a Roof Terminal using the 4 off
5mm x 40mm brass screws supplied with the Single Spigot Adaptor.
Manufactured from HIPS material.
Flexible Ducng and Installaon Accessories
Afull range of ducng and installaon accessories is available from
Domus. Call Domus on 02920 885231 to request literature.
7.0 Maintenance
Periodically, at least once a year or more frequently in case of heavy
use, remove the dirt and encrustaon from the grille(s) fan impeller
and motor casing. Ensure the impeller is not cracked or
deformed and is
able to rotate freely and without oscillaon.
Do not use any solvents to clean this product.
10.0 Aer Sales Enquiries
For technical assistance or further product informaon, including spare
parts and replacement components, please contact the Aer Sales
Department.
8.0 Replacement Of Parts
As a manufacturer Domus is aware that me is important. In the event
of a breakdown of this equipment, it should be adequately packaged
and returned to Domus.
Please telephone Domus before posng your unit.A returns number
will
be issued to idenfy your package.
9.0 Warranty
The 2year warranty starts from the day of delivery and includes parts
and labour for the first year.The remaining period covers replacement
parts only.
This warranty is void if the equipment is modified without
authorisaon, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good pracce.
Installaon or replacement of units or spare parts must be carried out
by a qualified or Domus approved service engineer/ electrician and in
accordance with IEE or local naonal wiring regulaons.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Condions of Sale.
Customers purchasing from outside of the UK should contact Domus
Internaonal Sales office for further details.
A unit returned to Domus should be suitably protecvely packaged and
clearly marked with the ‘returns number’ obtained from Domus prior to
posng.
Technical or commercial consideraons may, from me to me, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior noce.
6.0 Ancillaries
Single Spigot Adaptor
Used in conjuncon with flexible ducng systems.
Mounted onto the front of the Spacer secon using the 4 off 5mm x
40mm brass screws supplied with the Single Spigot Adaptor. Replaces
the internal grille.
Can also be used connected directly to a Roof Terminal using the 4 off
5mm x 40mm brass screws supplied with the Single Spigot Adaptor.
Manufactured from HIPS material.
Flexible Ducng and Installaon Accessories
Afull range of ducng and installaon accessories is available from
Domus. Call Domus on 02920 885231 to request literature.
7.0 Maintenance
Periodically, at least once a year or more frequently in case of heavy
use, remove the dirt and encrustaon from the grille(s) fan impeller
and motor casing. Ensure the impeller is not cracked or deformed and is
able to rotate freely and without oscillaon.
Do not use any solvents to clean this product.
10.0 Aer Sales Enquiries
For technical assistance or further product informaon, including spare
parts and replacement components, please contact the Aer Sales
Department.
8.0 Replacement Of Parts
As a manufacturer Domus is aware that me is important. In the event
of a breakdown of this equipment, it should be adequately packaged
and returned to Domus.
Please telephone Domus before posng your unit.A returns number will
be issued to idenfy your package.
We will endeavour to repair or replace it within fiveworking days of
receipt.See our warranty terms.
9.0 Warranty
The 3 year warranty starts from the day of delivery and includes parts
and labour for the first year.The remaining period covers replacement
parts only.
This warranty is void if the equipment is modified without
authorisaon, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good pracce.
Installaon or replacement of units or spare parts must be carried out
by a qualified or Domus approved service engineer/ electrician and in
accordance with IEE or local naonal wiring regulaons.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Condions of Sale.
Customers purchasing from outside of the UK should contact Domus
Internaonal Sales office for further details.
A unit returned to Domus should be suitably protecvely packaged and
clearly marked with the ‘returns number’ obtained from Domus prior to
posng.
Technical or commercial consideraons may, from me to me, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior noce.
6.0 Ancillaries
Single Spigot Adaptor
Used in conjuncon with flexible ducng systems.
Mounted onto the front of the Spacer secon using the 4 off 5mm x
40mm brass screws supplied with the Single Spigot Adaptor. Replaces
the internal grille.
Can also be used connected directly to a Roof Terminal using the 4 off
5mm x 40mm brass screws supplied with the Single Spigot Adaptor.
Manufactured from HIPS material.
Flexible Ducng and Installaon Accessories
A full range of ducng and installaon accessories is available from
Domus. Call Domus on 02920 885231 to request literature.
7.0 Maintenance
Periodically, at least once a year or more frequently in case of heavy
use, remove the dirt and encrustaon from the grille(s) fan impeller
and motor casing. Ensure the impeller is not cracked or deformed and is
able to rotate freely and without oscillaon.
Do not use any solvents to clean this product.
10.0 Aer Sales Enquiries
For technical assistance or further product informaon, including spare
parts and replacement components, please contact the Aer Sales
Department.
8.0 Replacement Of Parts
As a manufacturer Domus is aware that me is important. In the event
of a breakdown of this equipment, it should be adequately packaged
and returned to Domus.
Please telephone Domus before posng your unit.A returns number will
be issued to idenfy your package.
We will endeavour to repair or replace it within fiveworking days of
receipt.See our warranty terms.
9.0 Warranty
The 3 year warranty starts from the day of delivery and includes parts
and labour for the first year.The remaining period covers replacement
parts only.
This warranty is void if the equipment is modified without
authorisaon, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good pracce.
Installaon or replacement of units or spare parts must be carried out
by a qualified or Domus approved service engineer/ electrician and in
accordance with IEE or local naonal wiring regulaons.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Condions of Sale.
Customers purchasing from outside of the UK should contact Domus
Internaonal Sales office for further details.
A unit returned to Domus should be suitably protecvely packaged and
clearly marked with the ‘returns number’ obtained from Domus prior to
posng.
Technical or commercial consideraons may, from me to me, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior noce.
6.0 Ancillaries
Single Spigot Adaptor
Used in conjuncon with flexible ducng systems.
Mounted onto the front of the Spacer secon using the 4 off 5mm x
40mm brass screws supplied with the Single Spigot Adaptor. Replaces
the internal grille.
Can also be used connected directly to a Roof Terminal using the 4 off
5mm x 40mm brass screws supplied with the Single Spigot Adaptor.
Manufactured from HIPS material.
Flexible Ducng and Installaon Accessories
Afull range of ducng and installaon accessories is available from
Domus. Call Domus on 02920 885231 to request literature.
7.0 Maintenance
Periodically, at least once a year or more frequently in case of heavy
use, remove the dirt and encrustaon from the grille(s) fan impeller
and motor casing. Ensure the impeller is not cracked or deformed and is
able to rotate freely and without oscillaon.
Do not use any solvents to clean this product.
10.0 Aer Sales Enquiries
For technical assistance or further product informaon, including spare
parts and replacement components, please contact the Aer Sales
Department.
8.0 Replacement Of Parts
As a manufacturer Domus is aware that me is important. In the event
of a breakdown of this equipment, it should be adequately packaged
and returned to Domus.
Please telephone Domus before posng your unit.A returns number will
be issued to idenfy your package.
We will endeavour to repair or replace it within fiveworking days of
receipt.See our warranty terms.
9.0 Warranty
The 3 year warranty starts from the day of delivery and includes parts
and labour for the first year.The remaining period covers replacement
parts only.
This warranty is void if the equipment is modified without
authorisaon, is incorrectly applied, misused, disassembled, or not
installed, commissioned and maintained in accordance with the details
contained in this manual and general good pracce.
Installaon or replacement of units or spare parts must be carried out
by a qualified or Domus approved service engineer/ electrician and in
accordance with IEE or local naonal wiring regulaons.
The product warranty applies to the UK mainland and in accordance
with Clause 14 of our Condions of Sale.
Customers purchasing from outside of the UK should contact Domus
Internaonal Sales office for further details.
A unit returned to Domus should be suitably protecvely packaged and
clearly marked with the ‘returns number’ obtained from Domus prior to
posng.
Technical or commercial consideraons may, from me to me, make it necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior noce.
LAB1349R, Issue 1, Apr 2018 Page 8
V E N T I L A T I O N
Domus Ventilation
Block C
Caerphilly Business Park
V an Road
Caerphilly
CF83 3ED
T el: +44 (0)3443 715523
Fax: +44 (0)3443 715524
www.domusventilation.co.uk
LAB1347R May 2018
The EMC Directive
2014/30/EU
The Low Voltage
Directive
2014/35/EU
This manual suits for next models
6
Table of contents
Other Domus Ventilation Fan manuals

Domus Ventilation
Domus Ventilation Sapphire DME100C Centrifugal dMEV User manual

Domus Ventilation
Domus Ventilation HRXE User manual

Domus Ventilation
Domus Ventilation SVC100B User manual

Domus Ventilation
Domus Ventilation Sapphire GTF100 User manual

Domus Ventilation
Domus Ventilation CMX-S User manual

Domus Ventilation
Domus Ventilation DX Series Instruction Manual

Domus Ventilation
Domus Ventilation DX Series Instruction Manual

Domus Ventilation
Domus Ventilation HRXE-AURA User manual

Domus Ventilation
Domus Ventilation CMX-MULTI User manual

Domus Ventilation
Domus Ventilation HRXE-HERA User manual