Domus HRX-aQ AQH200-B User manual

HRX-aQ Range
Installation Instructions
Mechanical Ventilation with Heat Recovery
Product Code: AQH200-B
1.0 SAFETY INFORMATION
• DO NOT SWITCH OFF THE UNIT – it is designed to run continuously. If the unit is switched
off, indoor pollutants and moisture levels may increase which could endanger your health or
damage your home. It is important to follow the advice in this manual and correctly maintain the
system to ensure a healthy indoor environment.
• All wiring must be in accordance with prevailing national regulations, for example the current
IEE Wiring Regulations BS7671. The electrical installation should be inspected and tested by a
suitably qualified person after completion.
• The installer is responsible for the installation and electrical connection of this system on site.
It is the responsibility of the installer to ensure that the equipment is safely and securely installed
and left only when electrically and mechanically safe.
• When installing the appliance, care should be taken not to damage any hidden utilities.
• Ensure that the mains supply (Voltage and Frequency) complies with the rating label.
• Isolate from power supply before removing any covers. During installation / maintenance
ensure all covers are fitted before switching on the mains supply.
• The appliance should be provided with a local double pole fused spur fitted with a 3 Amp fuse
and a minimum contact separation of at least 3mm.
• This unit must be earthed.
• Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct
runs terminating close to the fan must be adequately protected by suitable guards.
• All regulations and requirements must be strictly followed to prevent hazards to life and
property, both during and after installation and any subsequent servicing or maintenance.
• This appliance should not be used by children or persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning the safe use of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried
out by children.
LAB1199R | OCTOBER 2023 PAGE 1

• In dwellings where it is intended to install open-flue appliances and extract ventilation, the
combustion appliance should be able to operate safely, whether or not the fans are running. A
way of showing compliance with The Building Regulations in these circumstances would be to
follow the installation guidance shown below, and to show by tests that combustion appliances
operate safely, whether or not the fans are running.
A. For gas appliances: where a room contains an open-flue appliance, the
extract rate should not exceed 20l/s (72m³/h).
B. For oil appliances: where a room contains an open-flue appliance, the extract
rate should be limited to 40l/s (144m³/h) for an appliance with a pressure jet burner and
20l/s (72m³/h) for an appliance with a vaporising burner.
C. For solid fuel appliances: avoid installing extract ventilation in the same room. Further
reference should be made to Approved Document J of The Building Regulations.
• Do not install this appliance in areas where the following may be present or occur:
Excessive oil or a grease laden atmosphere.
Corrosive or flammable gases, liquids or vapours.
Be subject to direct water spray.
Ambient temperatures higher than 50ºC and lower than -25ºC.
Possible obstructions that may hinder access or removal of the unit.
• This appliance should not be directly connected to a tumble dryer or cooker hood.
• A supply of fresh replacement air must be drawn from the exterior of the property.
• The extracted air must be expelled to the exterior of the property.
• It is recommended that the two external terminals or grilles are set at least 2m apart.
• The supply and exhaust ceiling valves should be positioned at least 300mm from internal walls
to allow airflow measuring equipment to fit correctly over the valves.
• Ducting should be insulated with Thermal duct insulation where it passes through unheated
spaces and voids (e.g. loft spaces) to reduce the possibility of condensation forming and heat
loss.
• A condensate drain should be installed from the appliance to an appropriate drain location.
DOMUS Ventilation recommends the 297 condensate drain kit.
• The condensate drain and associated pipe work must be cleared of debris prior to
commissioning and insulated where it passes through unheated spaces and voids.
1.1 Hazard Symbols
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before
installing, operating or maintaining this product.
LAB1199R | OCTOBER 2023 PAGE 2

1.2 Important Information
This manual contains important information on the safe and appropriate
assembly, transport, commissioning, operation, maintenance,
disassembly and simple troubleshooting of the product.
While the product has been manufactured according to the accepted
rules of current technology, there is still a danger of personal injury or
damage to equipment if the following general safety instructions and
the warnings contained in these instructions are not complied with.
• Read these instructions completely and thoroughly before
working with the product.
• Keep these instructions in a location where they are accessible
to all users at all times.
• Always include the operating instructions when you pass the
product on to third parties.
1.3 Personal Protective Equipment
The following minimum Personal Protective Equipment (PPE) is
recommended when interacting with this product:
• Protective Steel Toed Shoes - when handling heavy objects.
• Full Finger Gloves (Marigold PU800 or equivalent) - when
handling sheet metal components.
• Semi Fingerless Gloves (Marigold PU3000 3DO or equivalent) -
when conducting light work on the unit requiring tactile dexterity.
• Safety Glasses - when conducting any cleaning/cutting operation
or exchanging filters.
• Reusable Half Mask Respirators - when replacing filters which
have been in contact with normal room or environmental air.
We would always recommend a site specific risk assessment by a
competent person to determine if any additional PPE is required.
2.0 GENERAL DESCRIPTION
The HRX-aQ appliance is a key part of a whole house ventilation system
specifically designed to improve indoor air quality in dwellings. The
system is designed to provide measured amounts of filtered, fresh air to
living areas while constantly removing polluted, stale air from bathing,
cooking and washing areas at the same gentle rate. Any available heat
in the outgoing stale air is recovered by a built-in heat exchanger and
used to pre-warm the fresh supply air.
A manual boost switch is provided to increase the ventilation rate, e.g.
when cooking or showering thereby maintaining a comfortable indoor
environment.
A programmable user interface is provided to thereby maintaining a
comfortable indoor environment and includes the following features:
• Time and date functions
• Independent fan control adjustable at three levels; Low, Boost, Max
• Programmable filter check reminder
• Programmable 100% Thermal bypass
• Optional 3 minute delay-on boost switching
• Optional 5 to 30 minute delay-off boost switching
• Optional programmable frost protection
• Programmable humidity level boost switching
• Temperature controlled switching available for optional duct heater
(supplied by others)
• Elapsed runtime meter
The boost facility can also be triggered from a lighting circuit; contacts
to accommodate external sensors or switches are also available (Section
5.1).
The G3 filters in the appliance ensure that the fresh supply air is clean as
it enters the home. Additionally, the stale extract air is filtered to protect
the heat exchanger from unwanted contamination. These filters have
to be cleaned regularly, depending on the levels of pollution. The filters
should be replaced when they start to show visible signs of wear.
This product is listed in the NCM PCDB, (was SAP Appendix Q)
therefore, part of the installation process requires that an installation
checklist is completed and submitted to the Building Control Body
(BCB). Blank checklists are available at https://www.ncm-pcdb.org.
uk/sap/filelibrary/pdf/Check_Lists/Domestic_Ventilation_Compliance_
Guide_2010_-_Checklist_(extract).pdf.
Unit Overview
1.
2.1 Pack Includes
• Domus HRX-aQ appliance
• Ventilation user-control centre
• 4m length of 4 core signal cable (to connect AQH wiring centre and
user-control)
• Installation and operating instructions manual
• Householders operating manual
• ErP label and data fiche
LAB1199R | OCTOBER 2023 PAGE 3

2.2 Physical Specification
Unit Dimensions
2.
net weight 7.9kg
Rating: 230V 50Hz 59W (0.54A)
2.3 Main Features
2.3.1 Thermal Bypass
The HRX-aQ is fitted with a fully automatic 100% heat exchanger
bypass mechanism. Time clock control and manual override are also
available.
In automatic mode, the bypass will open when the indoor target
temperature reaches a pre-set value. Using the interface, the trigger
temperature can be set between +15°C and 25°C.
The interface contains an optional frost protection system. During
periods of very cold weather, the fresh air supply fan will automatically
reduce in speed to approximately 20% of its commissioned setting to
reduce the load on your heating system and avoid possible freezing of
the heat exchanger. During these periods, the extract fan will increase in
speed to its commissioned boost speed to maintain an even air pressure.
Using the interface, the trigger temperature can be set between -15°C
and +5°C.
3.0 INSTALLATION
The following instructions are intended to help prevent hazards.
Installation should only be carried out by a qualified electrician and
competent persons in clean, dry conditions where dust and humidity are
at minimum levels.
We advise installers to fix all mains, switch and sensor wiring
(in accordance with the latest edition of the Wiring Regulations)
prior to fixing the HRX-aQ unit in position.
3.1 Preparation
When accepting delivery of the appliance, inspect for transit damage. If
in doubt, call our Customer Services team on 03443 715523.
The HRX-aQ appliance can be fitted directly to a concrete ceiling or
suitable horizontal timber support.
Appropriate screw fixings to suit the support medium will need to be
supplied by the installer. The built-in mounts suit 4 x 4mm (No.8) pan
head screws.
Ensure that there is sufficient space for access to the wiring
centre (cover removal), the condensation fittings and ductwork
Ensure that there is sufficient space below the appliance to access the
filters and for carrying out any future maintenance on the appliance.
The HRX ceiling appliance must be connected to the duct work as
shown below; duct connections can not be substituted.
When viewed from below, the filter access and duct configuration is as
shown on the diagram below:
Filter access
Duct Configurations
3.
3.2 Fitting 297 Condensate Drain Kit
Using a small amount of solvent weld suitable for ABS pipe fittings (not
supplied), attach the threaded socket to the selected condensate outlet
spigot (Figure 4). Important: follow the health and safety and user
instructions supplied with the solvent weld. This is particularly important
when working in confined spaces.
When the threaded socket is secure, fit and hand-tighten the threaded
elbow or alternatively the threaded straight adapter, making sure that
the rubber seal washer is seated correctly. Gently push the waterless
trap onto the elbow stem. Important: check that the arrows printed
on the trap point away from the HRX-aQ appliance (in the direction
of flow) and prior to fitting, ensure that the waterless trap operates
correctly by running a trickle of water from a tap through the trap in the
direction of the arrows.
Using the remainder of the kit items, complete the condensate
drain-system to suit the dwelling layout. Important: the drain must
incorporate a continuous fall to the nearest waste water network.
The condensate drain system should be adequately supported and
suitably insulated if it passes through unheatedspaces and voids (e.g.
loft spaces) to prevent freezing.
Condensate Drain Connection
4.
LAB1199R | OCTOBER 2023 PAGE 4

3.3 Ducting Guidelines
Please refer to the design drawings for the proposed ducting layout.
Four 204x60mm sockets are provided for connecting the ducting.
Ductwork should be securely connected to the sockets using Domus
Ventilation DDSEAL acrylic sealant; failure to do this will cause
unnecessary air leakage and impair performance. Ducting must be
connected to all four sockets in accordance with the configuration
(Figure 5).
Where ducting passes through unheated areas and voids (e.g. loft
spaces) it must be insulated using Domus Ventilation Thermal
duct insulation in order to comply with The Building Regulations.
Additionally, both ducts connecting the HRX-aQ to outside must
be insulated with an additional continuous vapour barrier to avoid
condensation forming on the outside of the ducts.
Alternative proprietary duct insulation may be used provided it complies
with the 2010 Domestic Ventilation Compliance Guide.
When passing through a fire-stopping wall or fire-compartment wall,
Domus Ventilation FireBrake intumescent duct connectors should
be used in order to maintain the integrity of firestopping walls in
accordance with Approved Document B of the Building Regulations.
Alternative proprietary fire-stopping methods may be employed
provided they comply with Approved Document B of The Building
Regulations.
The fresh supply air must be drawn in from the exterior of the property.
If drawn through a wall, a Domus Ventilation 905 airbrick should
be fitted. If drawn in through a pitched roof a Domus Ventilation
4411/4411T universal roof terminal should be fitted or a proprietary
roof terminal designed for mechanical ventilation with a free area of at
least 10,000mm².
The stale extract air must be expelled to the exterior of the property.
If expelled through a wall, a Domus Ventilation 905 airbrick should
be fitted. If expelled through a pitched roof a Domus Ventilation
4411/4411T universal roof terminal should be fitted or a proprietary
roof terminal designed for mechanical ventilation with a free area of at
least 10,000mm².
It is an industry recommendation (TR35) that the fresh supply and stale
exhaust external inlets and outlets should be fitted at least 2m apart to
avoid recirculation of stale exhaust air.
Further details regarding installation can be found in the 2010 Domestic
Ventilation Compliance Guide.
3.3.1 Rigid Ducting
Install using the least number of fittings to minimise resistance to
airflow. All duct runs should be as short and as straight as possible for
maximum performance with adequate support.
3.3.2 Flexible Ducting
Ensure flexible ducting lengths are kept to a maximum of 300mm and
ducting is pulled taut so that it is smooth and straight. Mechanically
fix flexible ducts using Domus Ventilation 125-5 hose clips and tape
seal using Domus Ventilation 50TP45 duct tape or any good quality
proprietary duct tape for added air-tightness.
5.
Unit Connections
4.0 ELECTRICAL
WARNING: This appliance must be earthed.
All wiring must be carried out by a qualified electrician and
conform to the prevailing national regulations, for example the
latest edition of BS7671: IEE Wiring Regulations.
This appliance is suitable for 230V 50Hz single phase supply only, fused
at 3 Amps. A double-pole switch having a minimum contact separation
of 3mm must be used to provide isolation for the appliance.
External wiring (1.5mm² max.) and isolators to be supplied by others.
A 4m length of 4-core signal cable is supplied with the unit to connect
the wiring centre to the user interface.
LAB1199R | OCTOBER 2023 PAGE 5

5.0 WIRING
5.1 Wiring Centre PCB Layout and Connections
4m SIGNAL CABLE (SUPPLIED)
8m VERSION AVAILABLE SEPARATELY
RED
GREEN
YELLOW
BLUE
EXAMPLE
6.
Unit Wiring
LAB1199R | OCTOBER 2023 PAGE 6

6.0 COMMISSIONING
IMPORTANT: Ensure that the protective covers have been
removed from the filters.
When the wiring connections have been checked, switch on the mains
supply and check that the system is operating correctly (Section 7.0).
Airflow rates will need to be set at each room’s air-valve in accordance
with the 2010 Domestic Ventilation Compliance Guide to balance the
system. Airflow measurements should be performed using a calibrated
airflow measuring device. The most common method uses a vane
anemometer, placed in a hood which completely covers the air-valve to
measure the extract or supply airflow rate. The instrument should be
calibrated annually by returning the instrument to a UKAS accredited
calibration centre and be capable of achieving an accuracy of ±5%.
Each room airflow rate will need to be recorded on the Inspection
Checklist and Airflow Measurement Test Sheet. A completed copy must
accompany these instructions and be handed over to the dwelling’s
owner upon completion of the installation.
6.1 System Balancing
• Ensure that the pre-commissioning checks have been carried out and
that frost protection is not engaged.
• Fully open all of the air-valves.
• Switch the system to boost using the user interface.
• Close all internal and external doors and windows.
• Measure the total air volume of the extract valves (wet rooms).
• Using the user interface control, adjust the ‘boost’ speed to achieve
the total design extract boost rate.
• .Adjust individual wet room air-valves to achieve the individual room
design extract rates.
• Switch the system to low using the user interface.
• Measure the total air volume of the supply valves (habitable rooms).
• Using the user interface control, adjust the ‘low’ speed to achieve
the total design supply rate.
• Adjust individual habitable room air-valves to achieve the individual
room design supply rates.
• Double check all of the valve flow rates and record the readings.
• Using the lock nuts fitted to the air-valves, lock in position.
7.0 USER INTERFACE
7.
User Interface Front View
8.
User Interface Rear View
Half hour time switch segments
Thermal bypass active
Date
Speed
Frost protection active
Programme number
Intake temperature
Exhaust temperature
Humidity level
Time
Filter check
reminder
Frost
Bypass
12:00
1 2 43 5 76
60%
Filter
Low
Frost Bypass
Boos
t
Max
00
p9 28-01-2016
06 12 18 24
°C
2
1.0
°C
8
.0
9.
User Interface Screen
7.1 Time and Date (Mandatory Action When Power First
Applied To System)
• From the home screen, Press “DAY”, the hour text will flash.
• Use the “+” and “-“ buttons to set the hour.
• Press “DAY”, the minute text will flash.
• Use the “+” and “-“ buttons to set the minute.
• Press “DAY”, the day will flash.
• Use the “+” and “-“ buttons to set the day.
• Press “DAY”, the month will flash.
• Use the “+” and “-“ buttons to set the month.
• Press “DAY”, the year will flash.
• Use the “+” and “-“ buttons to set the year.
• Press “DAY”, 12/24 will flash.
• Use the “+” and “-“ buttons to set 12 or 24 hour clock format.
• Press “DAY” to confirm and return to home screen.
7.2 Pre-Commissioning
The following steps inhibit automatic functions that could affect
the commissioning process and need to be carried out prior to
commissioning:
• Set the time and date (Section 7.1).
• From the home screen, press “PROG”.
• Use the “+” and “-“ buttons to set the programme number to ‘P9’
(Factory default is P9).
• Press “SET”.
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds.
This action allows access to the ‘Installer’ programming level (opens at
menu 1).
• Press “COPY” twice to move to ‘Menu 3’, ‘Bypass tEnp’.
• Use the “+” or “-“ button to set to ‘off’ (OF).
This action inhibits the automatic bypass operation.
• Press “COPY” four times to move to ‘Menu 7’, ‘IhuN’.
• Use the “+” or “-“ button to set to ‘off’ (OF).
This action inhibits the automatic humidity controlled boost operation.
• Press “SET” to return to the home menu.
LAB1199R | OCTOBER 2023 PAGE 7

7.3 Commissioning (See Also Section 6.0)
• Use the “+” or “-“ button to set speed function to ‘Boost’.
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds to open the installer level.
• Press “COPY” once to move to ‘Menu 2’ ‘Fan 1 Low’.
• Press “PROG” once to ‘Fan 1 Boost’ (Extract/Exhaust fan).
• Use the “+” or “-“ button to set the desired speed (Factory default
speed is 50%).
Note: The installer level access will time out after 1 minute of inactivity
but will record any changes made to the settings.
• Press “SET” to record the settings and return to the home screen.
• Press “ESC” to discard the settings and return to the home screen.
10.
Fan 1 Commissioning Screen
Repeat the above steps for:
• Fan 2 Boost (Supply/Intake fan) (Factory default speed is 50%).
• Fan 1 Low (Extract/Exhaust fan) (Factory default speed is 20%).
• Fan 2 Low (Supply/Intake fan) (Factory default speed is 20%).
‘Max’ speed can be set to a maximum of 99% (Factory default 80%).
Note: Low speed cannot be set higher than Boost speed and Boost
speed cannot be set higher than Max speed.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
7.4 Automatic Heat Exchanger Bypass
7.4.1 Activation / Inactivation
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds.
• Press “COPY” as required to move to ‘Menu 3’, ‘Bypass tEnp’.
• Use the “+” or “-“ button to set to ‘on’ or ‘off’ (OF) as required.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
11.
HX Bypass Activation Screen
7.4.2 Setting Bypass Operating Temperature
• From the home screen, press “TEMP” as required to move to menu
‘T3’.
• T3 is the target indoor temperature setting at which the heat
exchanger bypass mechanism operates to allow the extract air to bypass
the heat exchanger and is adjustable between +15°C and +25°C
(Factory default 20°C).
• Use the “+” or “-“ buttons to set the operating temperature in steps
of 1°C.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
12.
HX Bypass Temperature Screen
7.5 Automatic Humidity Controlled Boost
7.5.1 Activation / Inactivation
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds.
• Press “COPY” as required to move to ‘Menu 7’, ‘IhuN’.
• Use the “+” or “-“ button to set to ‘on’ or ‘off’ (OF) as required.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
13.
Humidity Boost Activation Screen
7.5.2 Setting Humidity Activated Boost Switching Level (%RH)
• From the home screen, press “HUM” to move to the humidity (%
RH) activated boost setting (Factory default 60% RH – recommended).
• Use the “+” or “-“ buttons to set the humidity switching level in
steps of 1% RH (range 30- 85%RH).
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
14.
Humidity Boost Switching Level Screen
LAB1199R | OCTOBER 2023 PAGE 8

7.6 Filter Reminder
The word ‘Filter’ will appear on the home screen after the set time has
elapsed. When this occurs, clean the filters (Section 8.0)
Note: The figure at the bottom of the screen indicates elapsed
operating time in hours. When the numbers are not flashing, they
indicate the elapsed time since the last filter reset. If “DAY” is pressed,
the numbers will flash and indicate the total elapsed operating time in
hours.
• To reset the filter elapsed time reminder following cleaning, press
and hold “SET” for 5 seconds.
7.6.1 Adjustment and Inactivation
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds
• Press “COPY” as required to move to ‘Menu 1’ ‘Filter’
• Use the “+” or “-“ buttons to change the time delay in steps of 50
hours as required or ‘off’.
Note: The filter check reminder is factory set at the maximum of 3000
hours (approx. 4months - recommended). During adjustment, when this
maximum has been reached, the ‘off’ option can be accessed.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
15.
Filter Reminder Adjustment Screen
7.7 Frost Protection Trigger Temperature Adjustment
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds.
• Press “COPY” as required to move to ‘Menu 4’, ‘T5’.
Menu T5 sets the frost protection trigger temperature between -15°C
and +5°C (Factory default +1°C).
• Use the “+” or “-“ buttons to set the trigger temperature in steps of
1°C.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
16.
Frost Protection Trigger Temperature Adjustment Screen
7.8 Delay-On Timer Activation / Deactivation
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds.
• Press “COPY” once to move to ‘Menu 5’ ‘Delay-on setting’.
The Delay-on setting provides a 3 minute delay before Boost speed is
engaged.
• Use the “+” or “-“ button to set to ‘on’ or ‘off’.
Note: The Delay-on function will always be overridden by automatic
humidity sensing.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
17.
Delay-On Activation Screen
7.9 Delay-Off Timer Activation / Deactivation
• From the home screen, press and hold “SET” and “COPY”
simultaneously for 3 seconds.
• Press “COPY” once to move to ‘Menu 6’ ‘Delay-off setting’.
The Delay-off setting provides an adjustable run-on timer when Boost
speed is engaged – adjustable between 5 and 30 minutes or ‘off’.
• Use the “+” or “-“ button to set the desired run-on time in 1 minute
steps (Factory default is off).
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
18.
Delay-Off Activation Screen
7.10 Optional Duct-Heater Operating Temperature (°C)
• From the home screen, press “TEMP” as required to move to menu
‘T4’.
T4 is the outdoor temperature setting at which an optional intake air
duct-heater switch can be activated and is adjustable between +5°C
and +12°C (Factory default 10°C).
• Use the “+” or “-“ buttons to set the activation temperature in steps
of 1°C.
• Press “SET” to record or “ESC” to discard the settings and return to
the home screen.
LAB1199R | OCTOBER 2023 PAGE 9

19.
Optional Duct Heater Operating Temperature Screen
7.11 Programming
• From the home screen, press “PROG” (The programme number will
flash in the bottom left hand corner; P1 to P9).
• Use the “+” and “-“ buttons to view the selected programme
number (Factory default is P9).
The pre-programmed Thermal bypass programmes are shown in the
diagram (See Section XX).
Note: Each square has a time value of 30 minutes. Black squares
indicate a time period where the unit is in automatic bypass mode i.e.
the unit will monitor the temperatures and open or close the bypass
accordingly. White squares (blank spaces) indicate a time block where
the heat exchanger bypass will be permanently set to operate and
divert air around the heat exchanger regardless of the measured and set
temperatures.
Each of the programmes can be edited to create bespoke programmes
as follows:
• From the home screen, press “PROG”.
• Use the “+” and “-“ buttons to select the programme number
(Factory default is P9).
• Press “PROG”. The programme number will stop flashing and the
first block on the timeline at the bottom of the screen will begin to
flash.
• Select the day to be edited by pressing “DAY” until the correct day is
displayed along the top of the screen (1 – Monday, 2 – Tuesday etc.).
• To add a 30 minute temperature controlled bypass block (a black
square) to the timeline, ensure that the word “BYPASS” is displayed on
the screen by pressing “BYPASS”.
• Press the “+” and “-“ buttons to move along the timeline at the
bottom of the screen; a block will be added to each position.
• To remove a block, remove the word “BYPASS” from the screen by
pressing “BYPASS” and press the “+” and “-“ buttons to move along
the timeline at the bottom of the screen; a block will be removed from
each position.
• Daily ‘timeline patterns’ can be copied to another day or multiple
days to avoid programming each day individually.
• From the home screen, press “COPY”.
• Select the day to copy by pressing “PROG” (the day number will
be displayed) and then the day to copy-to by pressing the “+” and “-“
buttons (the day number will flash). When the two correct days have
been selected, press “COPY” and the timeline pattern will copy across.
• Press “SET” to record.
7.12 Default Interface Factory Settings
• P1
• t3 - 20°C
• t4 - 10°C
• Humidity – 60%
• Filter – 3000 hours
• Fan 1 – Low 20%
• Fan 1 – Boost 50%
• Fan 1 – Max 80%
• Fan 2 – Low 20%
• Fan 2 – Boost 50%
• Fan 2 – Max 80%
• Bypass temp – off
• T5
• Delay-on – off
• Delay-off – off
• Hum - on
8.0 MAINTENANCE
The appliance G3/EU3 filters should be cleaned on a regular basis,
the exact frequency will be determined by individual living conditions,
but we recommend inspection every 3,000 hours (4 months) with
replacement every 27,000 hours (three years).
Before cleaning the filters, turn off the appliance at the isolator switch.
To remove the two filters, pull out the two caps from the front of the
appliance and gently slide out the filters in their carrier frames.
Lightly vacuum the filters to remove surface debris and then gently wash
through in warm soapy water. Ensure that the filters are completely dry
before refitting. Important: do not dry on a radiator or use excessive
heat as this will distort the carrier frames.
LAB1199R | OCTOBER 2023 PAGE 10

9.0 THERMAL BYPASS PROGRAMMES
Thermal Bypass Programmes
20.
LAB1199R | OCTOBER 2023 PAGE 11

10.0 FAULT FINDING
Caution - the electrical supply to the unit and from any external
triggers into the unit must be isolated before removing covers to
electrical connections.
Fault Checks & Possible Solutions
Nothing
displayed on
the controller
LCD screen.
• Check there is power connected to the unit.
Presence of an orange light visible from outside the
white wiring centre box will indicate this.
• Check the electrical connections between VCC
(on controller) and 5V (on PCB).
• Check the electrical connections between GND
(on controller) and GND (on PCB).
‘Unconnect’
displayed on
the controller
LCD screen.
• Check the electrical connections between TD (on
controller) and RXD (on PCB.
• Check the electrical connections between RX (on
controller) and TXD (on PCB).
‘Fail’
displayed on
the controller
LCD screen.
• If relevant, check with the building management
services team if the external inhibit function has
been activated.
• If connected, check the smoke detector isn’t
activating the external inhibit function.
• If no external inhibit control is connected,
check there is a link wire present between the two
terminals of the external inhibit connection on the
main PCB.
• Check the electrical connections of the
aforementioned link wire between the two
terminals of the external inhibit on the main PCB.
‘Fail (fan 1)’
displayed on
the controller
LCD screen.
• Check the electrical connections for fan 1 on the
main PCB. There are four connections at the top
of the board for control and three at the bottom of
the board for power.
• By removing the exhaust duct connection, check
there is nothing obstructing fan 1.
‘Fail (fan 2)’
displayed on
the controller
LCD screen.
• Check the electrical connections for fan 2 on the
main PCB. There are four connections at the top
of the board for control and three at the bottom of
the board for power.
• By removing the supply duct connection, check
there is nothing obstructing fan 2.
Little or
no air is
extracting
or supplying
through the
room valves.
• Check that the filters have been removed from
the pre-commissioning protective covers.
• Check that the filters are not blocked.
• Check that the system has been commissioned
correctly.
• By removing the exhaust and supply duct
connections check there is nothing obstructing the
fans.
The unit is
excessively
noisy.
• Check that the system has been commissioned
correctly.
• By removing the exhaust and supply duct
connections check there is nothing obstructing the
fans
If the fault/faults cannot be resolved using the table above,
contact the Domus Ventilation Customer Service Team.
11.0 WARRANTY
The 2 year warranty starts from the day of delivery and includes first
year parts and labour, remaining year parts only. This warranty is void if
the equipment is modified without authorisation, is incorrectly applied,
misused, disassembled, or not installed, commissioned and maintained
in accordance with the details contained in this manual and general
good practice.
11.1 Extended Warranty
In addition to this two year warranty Domus also offers extended
warranty protection for this product for consumers based in the UK
subject to additional terms and conditions. You can find out more
about this extended warranty cover and purchase by contacting Domus
using one of the above methods.
12.0 END-OF-LIFE AND RECYCLING
Where possible components which can be largely recycled when the
product reaches its end-of-life have been used:
• Fans, motors, controls, actuators, cabling and other electrical
components can be segregated into WEEE recycling streams.
• Sheet metal parts, aluminium extrusion, heating/cooling coils and
other metallic items can be segregated and fully recycled.
• EPP, plastic ducting, nylon corner pieces, plastic heat exchangers,
packaging material and other plastic components can be segregated
into mixed plastic and widely recycled.
• Cardboard packaging, wood, and other paper components can be
largely recycled or fully processed in energy from waste centres.
• Filter Disposal: Cardboard framed filters should be fully processed
in energy from waste centres, contact your local civic amenity site /
household waste recycling centre regarding metal / wire framed filters.
• Remaining Items can be further segregated and processed in
accordance with the zero waste hierarchy. Please call After Sales
Support for further information on items not listed above.
Ensure that this product is made safe from any electrical / water
/ refrigerant supplies before dismantling commences. This work
should only be undertaken by a qualified person in accordance
with local authority regulations and guidelines, taking into
account all site based risks.
13.0 AFTER SALES AND REPLACEMENT PARTS
For technical assistance or further product information, including spare
parts and replacement components, please contact the After Sales
Department.
If ordering spares please quote the serial number of the unit together
with the part number, if the part number is not known please give a full
description of the part required. The serial number will be found on the
identification plate attached to the unit casing.
vent.technical@domusventilation.co.uk
Installer Contact Details:
Company Name:
Contact:
Tel:
Email:
Domus Ventilation
Climate House, Western Industrial Estate, Caerphilly, CF83 1BQ, United Kingdom.
Email: [email protected]
Tel: 03443 715 523
www.domusventilation.co.uk
Technical or commercial considerations may, from time to time, make it
necessary to alter the design, performance and dimensions of equipment
and the right is reserved to make such changes without prior notice.
LAB1199R | OCTOBER 2023 PAGE 12
Table of contents
Other Domus Fan manuals
Popular Fan manuals by other brands

Airstream
Airstream 54" SLANTWALL FAN Installation & operation manual

AerAtron
AerAtron FR3 Series User manual & installation guide

Maico
Maico ER GH AP Installation and operating instructions

Westinghouse
Westinghouse Morris owner's manual

Broan
Broan qt130le installation instructions

TJERNLUND
TJERNLUND HS-3 manual