2SLAN-DR 2018-11
WN 059730 45532
dormakaba Mounting instructions MountingMounting
3.2 Technical information
Supply voltage: 24VDC +/- 15 %
Power consumption: 60 mA
Ambient temperature: -10 °C to +55 °C
Rel. humidity: up to 93 %
(non condensing)
Protection class: Dependent on the
housing used
Ethernet 10Base-T or 100Base-Tx
Segment length max. 100 m
Cable recommendation at least CAT5 cable
3.3 LED display
The LED displays light up yellow and green.
LED on LED off
Link LED
10 MBit/s yellow
100 MBit/s green
No connection
Activity LED
Half duplex yellow
Full duplex green
No activity
4 Mounting
The mounting takes place by clipping onto a 35 mm
DIN rail.
4.1 Installation requirement
Prerequisite for the mounting is compliance with the
LAN specifications regarding transceivers, network
topology, network lengths, cable specifications, etc.
• The mounting location of the modules must be
selected so that the modules’ ambient temperature
range is maintained and any heat generated can be
dissipated.
• A minimum distance of 200 mm to high-energy
sources of interference, e.g. frequency converters, is
recommended.
• To avoid condensation, modules that have been
stored at very different temperatures must be
adjusted to the operating temperature before
commissioning.
4.2 Assignment of terminals
24V
GND
TxD1
TxD2
GND
TxD3 RxD3
GND
RxD2
RxD1
GND
24V
X1
X3
Mac-Adresse
xx-xx-xx-xx-xx-xx
Activity
LED
Link
LED