Pag 2 di 2
OROIDAL CURRENT TRANSDUCER SERIES
MU 1142 REV.2
Description
The current transducers series FL, used with Dossena fault
locators, allow to detect the very low currents that are used for
fault location in IT industrial network. Transducers must be
installed upstream of the line or load to be monitored.
Direction for installation:
- The toroidal current transducer connections require 6.3mm
female standard faston.
- Push the transducer to fix it on the DIN rail; to remove it, use a
screw-driver, as shown in the picture.
- Cables inside the transducer must be centred and tightened
together.
- Do not bend cables/bars near transducer.
- The CT internal diameter must be two times the cable harness
diameter.
- For the right installation use terminals 1-2 of the transducer (do
not connect terminals 3-4)
TECHNICAL CHARACTERISTICS
NAME FL35 FL60 FL80 FL110 FL160 FL210 FL60A
Internal diameter (mm) 35 60 80 110 160 210 60
IL
value (mA) 0,5 0,5 0,5 1 1 1 3
Nominal current In (A) 80 120 170 260 310 360 120
Max load current (A) 480 720 1020 1560 1860 2160 720
Standards IEC 61869-2
Degree of protection IP20
Operating temperature -10 +55°C
Storage temperature -20 +80°C
Short circuit current 80kA (0,5 sec)
Transformation ratio 500 (terminals 1-2)
Application Use in combination with DOSSENA IMDs (fault location function)
Closed core
Split core
Dimensions FL35 FL60 FL80 FL110 FL160 FL210 FL60A
A (mm) 35 60 80 110 160 210 60
B (mm) 99,5 124,5 144,5 180,5 230,5 280,5 121
C (mm) 70 94,5 114,5 150,5 200,5 250,5 130
D (mm) 44,5 57 67 85 110 135 54,5
E (mm) - - - - - - 16
F (mm) - - - - - - 94,5
G (mm) 26 26 26 31 31 31 26
H (mm) 104 117 125 155 197 227 117
I (mm) 92 103 111 141 183 213 103