Douglas WTI-2332-FT Instruction manual

To Enable Password Protection
Press and Hold,
then press Reset button once,
keep holding till LED goes ON. BLUE
WHITE
24VAC POWER
To Disable Password Protection
Press and Hold,
then press Reset button once,
keep holding till LED goes ON.
Whichever LED is ON indicates
password protection state. Group ON/OFF
Use to test.
Button actuates
a preprogrammed
relay group.
Relay Group #
ON=Single Command / Call
OFF=Multiple Command / Call
Tones allowed
during voice prompts
ON=Relay Group Control
OFF=Relay Control
Device Status
Pressing Reset Button
will cause a software
reboot of the WTI-2332.
Blinking= OK
Reset
On HookRing
USB
Telephone
Line LED ON
when USB
connected
www.DouglasLightingControl.com
WTI-2332-FT
Telephone Interface
EARTH
NET B
NET A
Service
Wink
Lonworks
FTT-10 Signal
Technical Data
WTI-2332-FT
Telephone Interface
www.DouglasLightingControls.com
n The WTI-2332-FT Telephone Interface
allows users to access the Douglas lighting
control network from a standard touch-tone
phone.
n
The WTI-2332-FT can also be integrated
into an external Lonworks control system.
n
Phone plugs directly into the RJ11 port
on the unit.
n
Using simple telephone key commands,
the user can select a relay group, check
its status, and turn it ON or OFF.
n
Voice prompts are provided for ease and
simplicity of operation. Voice prompt
responses give the user confirmation of
each command.
n
Can be password protected.
n
Automatic disconnect after several seconds
of user inactivity or when user hangs up.
Connections
n Power:
24VAC, 100mA.
n
LonWorks Data Signal: FTT-10 (78kbs)
standard LonTalk data signal.
n Telephone: dedicated line from touch-
tone phone to built-in modem port.
Operation
n WTI-2332-FT accessed by dialing
telephone number provided by system
administrator. Dialing must be paced
and deliberate.
n Upon connection, password can be
required and is entered with telephone
keypad.
n Telephone command, entered with
telephone keypad, consists of function
code (ON, OFF or status), group (or
individual relay) number, and
initiation code.
n
Voice prompts provided by system.
Network Technology Specification
n LonWorks®technology.
Environment
■ Indoors, stationary, non-vibrating,
non-corrosive atmosphere and
non-condensing humidity.
n
Ambient operating temperature:
-0°F to +120F (-15°C to +50°C).
PART No. SPECIFICATIONDESCRIPTION
DIMENSIONS & MOUNTING
WTI-2332-FT Telephone Interface
Data Signal
Connect network data signal here.
LonWorks Network: wiring is 16AWG twisted pair, non-polarized,
unshielded, stranded or solid.
RJ11 Jack
Connect the telephone
line here. Wink Button and LED
LED flashes when network
Wink command received.
Press button to clear Wink
command.
Service Button & LED
Press button to identify unit to
network for diagnosis.
Flashing LED indicates
defective unit.
Reset Button
P
ress and hold at startup
to restore defaults.
n
Telephone Interface mounts to 35mm
DIN rail installed in relay panels.
Unit shipped with DIN mounting rail.
WTI-2332-FT
Telephone
Interface
Power Terminals
Connect to 24V transformer
in panel.
Group Test Button
Press button to toggle pre-
selected group ON and OFF.
Power Indicator LED
Flashes when unit
receiving power.
Ring LED
Flashes when call is
being sent.
Telephone Online
Indicator LED
ON if modem is active.
USB Port and LED
Connect USB from pc here for
using the pc hyperterminal to
configure the unit.
LED flashes when pc is connected
and a signal is being transmitted.
6.5"
(165)
1.75"
(45)
Plan View Side View
6.5"
(165)
4.0"
(103)
WTI-2332-FT
Telephone Interface
DIP Switches
Factory Setting is all
3 switches in ON
(right) position:
#1 ON (single command per
session).
#2 ON (can enter command
during prompt).
#3 ON (relay groups activated).
#1 OFF (multiple commands per
session).
#2 OFF (cannot enter command
until prompt ends).
#3 OFF (individual relays
activated).
1
2
3
ON
OFF
Password
Activate/Disable
Buttons and LEDs
Press and hold the
password activate -
disable button. Then
press Reset button once.
Keep holding the
password activate or
disable button until
the LED goes ON.

Connecting the WTI-2332-FT Telephone
Interface to an MC-6000 System
Connect the lonworks data signal of the WTI-2332-FT to an MC-6210N-
GTW card. The MC-6210N-GTW card must have its own address with
respect to the MC-6000 system.
Technical Data
WTI-2332-FTTelephone Interface
www.DouglasLightingControls.com
Using the WTI-2332-FT Telephone
Interface
1.
The WTI-2332-FT Telephone Interface panel can be
incorporated into a Douglas W-2000 or MC-6000 lighting
control network.
2. Connect to the WTI-2332-FT line by dialing the telephone
number (supplied by the network administrator) on a touch-
tone phone whose line is connected directly to the RJ11 port
in the WTI-2332-FT.
3. Once connected, the system will prompt for the access
password when the WTI-2332-FT is configured for password
protection. Enter the password using the telephone keypad,
followed by the (#) key. The system will prompt when the
password is accepted.
If the WTI-2332-FT is configured for no password, the system
will not prompt for a password. Instead, it will proceed to the
Group Menu, where you can activate or query the status of
output relay groups.
4. The WTI-2332-FT default menu setting is relay groups. A
command can be entered with the telephone keypad to turn a
network relay group OFF, ON or query its status. The command
consists of function (OFF = 3, ON = 6, 7 = query status),
followed by the group number (1 to 3 digits, 1 to 255) followed by
(#) to initiate the request. For example, pressing keys (3, 2, 5, #)
would command group #25 to turn OFF. The system will prompt
when the command is accepted.
5. Repeat previous step as necessary to activate or query
other group(s).
6. Password can be enabled and disabled with the telephone
keypad.
The process to disable the password function is:
a) When dialed into the WTI-2332, press "9#" at any time
b) Wait to hear the prompt "Enter new password"
c) Then press "5, 5#" which will disable the password protection.
The process to enable the password function is:
a) When dialed into the WTI-2332, press "9#" at any time
b) Wait to hear the prompt "Enter new password"
c) Then enter the new password followed by a "#".
7. Hang up after the last command is accepted. Note that the
WTI-2332-FT will automatically terminate the connection if
there is a period of inactivity.
BLUE
WHITE
24VAC POWER
USB
Telephone
Line LED ON
when USB
connected
www.DouglasLightingControl.com
EARTH
NET B
NET A
Service
Wink
Lonworks
FTT-10 Signal
WTI-2332-FT
Telephone
Interface
MC-6210 -GTW
Panel Control Card
All
ON
All
OFF
1
2
4
8
16
32
64
128
OFF ON
Test
Signal
Handheld
Keypad KB-3031
Data
Signal
Activity
Panel Bus
Activity
Panel
Bus
Card Power
(24 vac)
White
Blue
V#
Data Sign al
lighting controlslighting controlslighting controls
AB
MC-6210N-GTW
CPU Module
EARTH
NET B
NET A
M C - 6 0 0 0 S y s t e m
4 8 5 D a t a S i g n a l
F T T - 1 0
L o n W o r k s
D a t a s i g n a l
Using the WTI-2332-FT Card in an
MC-6000 System
1. The Individual Relay Menu can also be selected (by either
pressing the '4' key to switch from the default Relay Group Menu
or by setting the #1 DIP switch to OFF). A command can be
entered with the telephone keypad to turn an individual relay OFF
or ON or ON with timeout, or mask the relay ON or OFF.
The command consists of function (Mask OFF = 2, OFF = 3, ON =
6, 7 = Mask ON, 8 = ON with Timeout), followed by the panel
number (1 to 3 digits, 5 to 250), followed by the relay number (2
digits, 01 to 64) followed by (#) to initiate the request. For
example, pressing keys (3, 5, 0, 5, #) would command panel 5 -
relay #5 to turn OFF.