manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Dover
  6. •
  7. Water Pump
  8. •
  9. Dover Wilden Advanced Series Instruction Manual

Dover Wilden Advanced Series Instruction Manual

Other manuals for Wilden Advanced Series

5

This manual suits for next models

1

Other Dover Water Pump manuals

Dover PSG WILDEN XPR1560 Instruction Manual

Dover

Dover PSG WILDEN XPR1560 Instruction Manual

Dover Almatec Biocor Series User manual

Dover

Dover Almatec Biocor Series User manual

Dover PSG All-Flo C050 Instruction manual

Dover

Dover PSG All-Flo C050 Instruction manual

Dover Wilden Advanced Series Instruction Manual

Dover

Dover Wilden Advanced Series Instruction Manual

Dover WILDEN BioPharm T2 Series Instruction Manual

Dover

Dover WILDEN BioPharm T2 Series Instruction Manual

Dover PSG MOUVEX AS100 Owner's manual

Dover

Dover PSG MOUVEX AS100 Owner's manual

Dover PSG WILDEN P8 Series Instruction Manual

Dover

Dover PSG WILDEN P8 Series Instruction Manual

Dover PSG Griswold 811SP Series Instruction manual

Dover

Dover PSG Griswold 811SP Series Instruction manual

Dover PSG ALL-FLO A150 Instruction manual

Dover

Dover PSG ALL-FLO A150 Instruction manual

Dover PSG Wilden P1 Instruction Manual

Dover

Dover PSG Wilden P1 Instruction Manual

Dover MOUVEX AX40 User manual

Dover

Dover MOUVEX AX40 User manual

Dover Advanced Series Troubleshooting guide

Dover

Dover Advanced Series Troubleshooting guide

Dover Wilden Advanced Series Instruction Manual

Dover

Dover Wilden Advanced Series Instruction Manual

Dover Hydro Xtreme User manual

Dover

Dover Hydro Xtreme User manual

Dover PSG ALL-FLO A075 Manual

Dover

Dover PSG ALL-FLO A075 Manual

Dover PSG WILDEN PS4 Series Instruction Manual

Dover

Dover PSG WILDEN PS4 Series Instruction Manual

Dover PSG BLACKMERMLX4B Manual

Dover

Dover PSG BLACKMERMLX4B Manual

Dover PSG WILDEN XPR860 Instruction Manual

Dover

Dover PSG WILDEN XPR860 Instruction Manual

Dover Wilden Advanced P400 Instruction Manual

Dover

Dover Wilden Advanced P400 Instruction Manual

Dover PSG WILDEN XPR460 Instruction Manual

Dover

Dover PSG WILDEN XPR460 Instruction Manual

Dover PSG WILDEN PRO-FLO Saniflo Hygienic Series Installation guide

Dover

Dover PSG WILDEN PRO-FLO Saniflo Hygienic Series Installation guide

Dover SWEP PCU25 User manual

Dover

Dover SWEP PCU25 User manual

Dover PSG ALL-FLO IOM A050 Series Owner's manual

Dover

Dover PSG ALL-FLO IOM A050 Series Owner's manual

Dover PSG Ebsray R Series Guide

Dover

Dover PSG Ebsray R Series Guide

Popular Water Pump manuals by other brands

Watershed Innovations HYDRAPUMP SMART FLEX Instructional manual

Watershed Innovations

Watershed Innovations HYDRAPUMP SMART FLEX Instructional manual

Graco Modu-Flo AL-5M instructions

Graco

Graco Modu-Flo AL-5M instructions

Messner MultiSystem MPF 3000 operating instructions

Messner

Messner MultiSystem MPF 3000 operating instructions

Xylem Bell & Gossett WEHT0311M Installation, operation and maintenance instructions

Xylem

Xylem Bell & Gossett WEHT0311M Installation, operation and maintenance instructions

WilTec 50739 Operation manual

WilTec

WilTec 50739 Operation manual

Franklin Electric Little Giant 555702 HRK-360S instruction sheet

Franklin Electric

Franklin Electric Little Giant 555702 HRK-360S instruction sheet

Ingersoll-Rand PD02P Series Operator's manual

Ingersoll-Rand

Ingersoll-Rand PD02P Series Operator's manual

VS ZJ Series Operating	 instruction

VS

VS ZJ Series Operating instruction

Flotec FPZS50RP owner's manual

Flotec

Flotec FPZS50RP owner's manual

SKF Lincoln FlowMaster II User and maintenance instructions

SKF

SKF Lincoln FlowMaster II User and maintenance instructions

Xylem Lowara LSB Series Installation, operation and maintenance instructions

Xylem

Xylem Lowara LSB Series Installation, operation and maintenance instructions

Water Duro Pumps DCJ500 Operating & installation instructions

Water

Water Duro Pumps DCJ500 Operating & installation instructions

Action P490 Operating instructions & parts manual

Action

Action P490 Operating instructions & parts manual

Flo King Permacore Reusable Carbon Bag Disassembly. & Cleaning Instructions

Flo King

Flo King Permacore Reusable Carbon Bag Disassembly. & Cleaning Instructions

ARO ARO PD15P-X Operator's manual

ARO

ARO ARO PD15P-X Operator's manual

Pumptec 112V Series Operating instructions and parts manual

Pumptec

Pumptec 112V Series Operating instructions and parts manual

Virax 262070 user manual

Virax

Virax 262070 user manual

Neptun NPHW 5500 operating instructions

Neptun

Neptun NPHW 5500 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

H400S
W IL-11110 - E - 0 4
R EP L A CE S W IL-11110 - E - 0 3
EOM
Engineering
Operation &
Maintenance
Advanced™Series METAL Pumps
Advance your process
TABLE OF CONTENTS
SECTION 1 CAUTIONS—READ FIRST! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
SECTION 2 WILDEN PUMP DESIGNATION SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
SECTION 3 HOW IT WORKS—PUMP & AIR DISTRIBUTION SYSTEM . . . . . . . . . . . . . . . .3
SECTION 4 DIMENSIONAL DRAWINGS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4
SECTION 5 PERFORMANCE
A. H400S Performance Curves
TPE-Fitted Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
TPE-Fitted Stainless Steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
B. H400S Suction Lift Curves
TPE-Fitted Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
TPE-Fitted Stainless Steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
SECTION 6 SUGGESTED INSTALLATION, OPERATION & TROUBLESHOOTING. . . . . . . .8
SECTION 7 ASSEMBLY / DISASSEMBLY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SECTION 8 EXPLODED VIEW & PARTS LISTING
TPE-Fitted Aluminum . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
TPE-Fitted Stainless Steel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20
CAUTION: Do not apply compressed air to the
exhaust port — pump will not function.
CAUTION: Do not over-lubricate air supply —
excesslubricationwill reducepumpperformance.
Pump is pre-lubed.
TEMPERATURE LIMITS:
Neoprene –17.7°C to 93.3°C 0°F to 200°F
Buna-N –12.2°C to 82.2°C 10°F to 180°F
EPDM –51.1°C to 137.8°C –60°F to 280°F
Viton®–40°C to 176.7°C –40°F to 350°F
Saniflex™ –28.9°C to 104.4°C –20°F to 220°F
Wil-Flex™ -40ºC to 107.2ºC –40ºF to 225ºF
Polytetrafluoroethylene (PTFE)
4.4°C to 104.4°C 40°F to 220°F
Polyurethane –12.2°C to 65.6°C 10°F to 150°F
Tetra-Flex™ PTFE w/Neoprene Backed
4.4°C to 107.2°C 40°F to 225°F
Tetra-Flex™ PTFE w/EPDM Backed
-10°C to 137°C 14°F to 280°F
NOTE: Not all materials are available for all
models. Refer to Section 2 for material options
for your pump.
CAUTION: When choosing pump materials, be
sure to check the temperature limits for all wetted
components. Example: Viton®has a maximum
limit of 176.7°C (350°F) but polypropylene has a
maximum limit of only 79°C (175°F).
CAUTION: Maximum temperature limits are
based upon mechanical stress only. Certain
chemicals will significantly reduce maximum
safe operating temperatures. Consult Chemical
Resistance Guide (E4) for chemical compatibility
and temperature limits.
WARNING: Prevention of static sparking — If
static sparking occurs, fire or explosion could
result. Pump, valves, and containers must be
grounded to a proper grounding point when
handling flammable fluids and whenever
discharge of static electricity is a hazard.
CAUTION: Do not exceed 8.6 bar (125 psig) air
supply pressure.
CAUTION: All piping, valves, gauges and other
components installed on the liquid discharge must
have a minimum pressure rating of 20.7 bar (300 psig).
CAUTION: The discharge pressure generated by
this pump is 2X the inlet pressure supplied.
CAUTION: The process fluid and cleaning fluids
must be chemically compatible with all wetted
pump components. Consult Chemical Resistance
Guide (E4).
CAUTION: Do not exceed 82°C (180°F) air inlet
temperature for Pro-Flo V™ models.
CAUTION: Pumps should be thoroughly flushed
before installing into process lines. FDA and
USDA approved pumps should be cleaned and/
or sanitized before being used.
CAUTION: Always wear safety glasses when
operating pump. If diaphragm rupture occurs,
material being pumped may be forced out air
exhaust.
CAUTION: Before any maintenance or repair is
attempted, the compressed air line to the pump
should be disconnected and all air pressure
allowed to bleed from pump. Disconnect all
intake, discharge and air lines. Drain the pump
by turning it upside down and allowing any fluid
to flow into a suitable container.
CAUTION: Blow out air line for 10 to 20 seconds
before attaching to pump to make sure all pipeline
debris is clear. Use an in-line air filter. A 5µ (micron)
air filter is recommended.
NOTE: When installing PTFE diaphragms, it is
important to tighten outer pistons simultaneously
(turning in opposite directions) to ensure tight fit.
(See torque specifications in Section 7.)
NOTE: Cast Iron PTFE-fitted pumps come
standard from the factory with expanded PTFE
gaskets installed in the diaphragm bead of the
liquid chamber. PTFE gaskets cannot be re-used.
Consult PS-TG for installation instructions during
reassembly.
NOTE: Before starting disassembly, mark a line
from each liquid chamber to its corresponding air
chamber. This line will assist in proper alignment
during reassembly.
CAUTION: Pro-Flo®pumps cannot be used in
submersible applications. Pro-Flo V™ is available
inbothsubmersible andnon-submersibleoptions.
Do not use non-submersible Pro-Flo V™ models
in submersible applications. Turbo-Flo®pumps
can also be used in submersible applications.
CAUTION: Tighten all hardware prior to installation.
WIL-11110 - E- 04 1 WILDEN PUMP & ENGINEERING, LLC
Section 1
CAUTIONS—READ FIRST!
WILDEN PUMP & ENGINEERING, LLC 2 WIL-11110 - E- 04
Section 2
WILDEN PUMP DESIGNATION SYSTEM
H400S METAL
38 mm (1-1/2") Pump
Maximum Flow Rate:
242 lpm (64 gpm)
LEGEND
H400S /XXXXX/XX/XX/XXX/ XXX
O-RINGS
MODEL VALVE SEAT
VALVE BALLS
DIAPHRAGMS
AIR VALVE
CENTER BLOCK
AIR CHAMBERS
WETTED PARTS & OUTER PISTON
SPECIALTY
CODE
(if applicable)
MATERIAL CODES
MODEL
H400S = HIGH PRESSURE
SIMPLEX
WETTED PARTS & OUTER
PISTONS
AA = ALUMINUM/ ALUMINUM
SS = STAINLESS STEEL/
STAINLESS STEEL
AIR CHAMBERS
A = ALUMINUM
CENTER BLOCK
A = ALUMINUM
AIR VALVE
A = ALUMINUM
DIAPHRAGMS
WFS = WIL-FLEX™
[Santoprene®(Orange
Dot)]
VALVE BALL
WF= WIL-FLEX™
[Santoprene®(Orange Dot)]
VALVE SEAT
A = ALUMINUM
S = STAINLESS STEEL
VALVE SEAT O-RING
TF = PTFE (White)
NOTE: MOST ELASTOMERIC MATERIALS USE COLORED DOTS FOR IDENTIFICATION.
NOTE: Not all models are available with all material options.
Nordel®and Viton®are registered trademarks of DuPont Dow Elastomers.
Teflon®is a registered trademark of DuPont.
Halar®is a registered trademark of Solvay.
SPECIALTY CODES
0245 Reverse manifolds
0247 Discharge & inlet manifold facing exhaust
0250 Discharge manifold facing air inlet
0320 Submersible center block
0504 DIN flange
WIL-11110 - E- 04 3 WILDEN PUMP & ENGINEERING, LLC
Section 3
HOW IT WORKS—PUMP
The Wilden diaphragm pump is an air-operated, positive displacement, self-priming pump. These drawings show flow pattern
through the pump upon its initial stroke. It is assumed the pump has no fluid in it prior to its initial stroke.
FIGURE 1 When air pressure is supplied
to the pump, the air valve directs pressure
to the back side of diaphragm A. The
compressed air moves the diaphragm
away from the center section of the pump.
The opposite diaphragm is pulled in by
the shaft connected to the pressurized
diaphragm. Diaphragm B is on its suction
stroke; air behind the diaphragm has been
forced out to the atmosphere through
the exhaust port. The movement of
diaphragm B towards the center section
of the pump creates a vacuum within
chamber B. Atmospheric pressure forces
fluid into the inlet manifold forcing the
inlet valve ball off of its seat. Liquid is
free to move past the inlet valve ball and
fill the liquid chamber (see shaded area).
FIGURE 2 Once the shaft has reached the
end of its stroke, the air valve redirects
pressurized air to the back side of
diaphragm B. This pressurized air is also
directed to the opposite side of diaphragm
A through a passageway that is routed
through the common shaft and outer piston.
The pressurized air forces diaphragm B
away from the center section while also
pushing diaphragm A to the center section.
Diaphragm B is now on its discharge stroke.
Diaphragm B forces the inlet valve ball onto
its seat due to the hydraulic forces developed
in the liquid chamber and manifold of the
pump. These same hydraulic forces lift the
discharge valve ball off of its seat, forcing
fluid to flow through the pump discharge.
The pressure on diaphragm A creates a
force on the shaft that is combined with
the pressure from diaphragm B. This total
load is transferred to the liquid creating a
liquid pressure that is 2X greater than the
supplied air pressure.
FIGURE 3 At completion of the stroke,
the air valve again redirects air to the
back side of diaphragm A, which starts
diaphragm B on its exhaust stroke. As
the pump reaches its original starting
point, each diaphragm has gone through
one exhaust and one discharge stroke.
This constitutes one complete pumping
cycle. The pump may take several cycles
to completely prime depending on the
condition of the application.
The Pro-Flo V™p a t e n ted ai r dis t rib u t ion s y s t e m inc orp o r a t e s t w o
moving parts: the air valve spool and the pilot spool. The heart
of the system is the air valve. This valve design incorporates an
unbalanced spool. The smaller end of the spool is pressurized
continuously, while the large end is alternately pressurized,
then exhausted, to move the spool. The air valve spool directs
pressurized air to one air chamber while exhausting the other.
The air causes the main shaft/diaphragm assembly to shift to
one side — discharging liquid on that side and pulling liquid in
on the other side. When the shaft reaches the end of its stroke,
the inner piston actuates the pilot spool, which pressurizes and
exhausts the large end of the air valve spool. The repositioning
of the air valve spool routes the air to the other air chamber.
HOW IT WORKS—AIR DISTRIBUTION SYSTEM
WILDEN PUMP & ENGINEERING, LLC 4 WIL-11110 - E- 04
Section 4
DIMENSIONAL DRAWINGS
H400S Aluminum DIMENSIONS
ITEM METRIC (mm) STANDARD (inch)
A 345 13.6
B 79 3.1
C 318 12.5
D 528 20.8
E 605 23.8
F 127 5.0
G 323 12.7
H 48 1.9
J 132 5.2
K 310 12.2
L 518 20.4
M 241 9.5
N 203 8.0
P 152 6.0
R 170 6.7
S 10 0.4
DIN (mm) ANSI (inch)
T 150 dia. 6.1 dia.
U 110 dia. 4.5 dia.
V 18 dia. 0.9 dia.
H400S Stainless Steel DIMENSIONS
ITEM METRIC (mm) STANDARD (inch)
A 384 15.1
B 89 3.5
C 277 10.9
D 528 20.8
E 279 11.0
F 48 1.9
G 132 5.2
H 310 12.2
J 508 20.0
K 84 3.3
L 274 10.8
M 224 8.8
N 178 7.0
P 203 8.0
R 10 0.4
DIN (mm) ANSI (inch)
S 150 dia. 6.1 dia.
T 110 dia. 4.5 dia.
U 18 dia. 0.9 dia.
WIL-11110 - E- 04 5 WILDEN PUMP & ENGINEERING, LLC
A. P400 Aluminum performance
Curves
Flow rates indicated on chart were determined by pumping water.
For optimum life and performance, pumps should be specified so that daily operation
parameters will fall in the center of the pump performance curve.
Air inlet pressure values are 50% of discharge pressure values shown on Y axis.
H400S ALUMINUM
TPE-FITTED
Section 5A
PERFORMANCE
Height .................................605 mm (23.8”)
Width ..................................345 mm (13.6”)
Depth .................................. 310 mm (12.2”)
Est. Ship Weight..Aluminum 27 kg (60 lbs)
Air Inlet ................................... 19 mm (3/4”)
Inlet ......................................38 mm (1-1/2”)
Outlet ...................................38 mm (1-1/2”)
Suction Lift ....................... 3.1 m Dry (10.1’)
9.3 m Wet (30.6’)
Max. Flow Rate .............. 242 lpm (64 gpm)
Max. Size Solids..................8.0 mm (5/16”)
Example:To pump 61 lpm (16 gpm) against
a discharge pressure head of 5.2 bar (75
psig) requires 4.1 bar (60 psig) and 60
Nm3/h (35 scfm) air consumption. (See
dot on chart.)
Caution: Do not exceed 8.6 bar (125 psig)
air supply pressure.
A. P400 Aluminum performance
Curves
H400S STAINLESS STEEL
TPE-FITTED
Height ................................. 528 mm (20.8")
Width .................................. 384 mm (15.1")
Depth ...................................310 mm (12.2")
Est. Ship Weight ......Stainless Steel 37 kg (82 lbs)
Air Inlet ....................................19 mm (3/4")
Inlet ...................................... 38 mm (1-1/2")
Outlet ................................... 38 mm (1-1/2")
Suction Lift ....................... 3.1 m Dry (10.2')
9.0 m Wet (29.5')
Max. Flow Rate .............. 186 lpm (49 gpm)
Max. Size Solids.................. 4.8 mm (3/16")
Example: To pump 61 lpm (16 gpm) against
a discharge pressure head of 5.2 bar
(75 psig) requires 3.8 bar (55 psig) and
81.5 Nm3/h (48 scfm) air consumption.
(See dot on chart.)
Caution: Do not exceed 8.6 bar (125 psig)
air supply pressure.
Flow rates indicated on chart were determined by pumping water.
For optimum life and performance, pumps should be specified so that daily operation
parameters will fall in the center of the pump performance curve.
Air inlet pressure values are 50% of discharge pressure values shown on Y axis.
WILDEN PUMP & ENGINEERING, LLC 6 WIL-11110 - E- 04
H400S METAL
Section 5B SUCTION LIFT CURVE
Suction lift curves are calibrated for pumps operating
at 305 m (1,000') above sea level. This chart is meant
to be a guide only. There are many variables which
can affect your pump’s operating characteristics. The
number of intake and discharge elbows, viscosity of
pumping fluid, elevation (atmospheric pressure) and
pipe friction loss all affect the amount of suction lift
your pump will attain.
NOTES
WIL-11110 - E- 04 7 WILDEN PUMP & ENGINEERING, LLC
WILDEN PUMP & ENGINEERING, LLC 8 WIL-11110 - E- 04
Section 6
SUGGESTED INSTALLATION
Section 6 Suggested
Wilden pumps are designed to meet the performance
requirements of even the most demanding pumping
applications. They have been designed and manufactured
to the highest standards and are available in a variety of
liquid path materials to meet your chemical resistance
needs. Refer to the performance section of this manual for
an in-depth analysis of the performance characteristics of
your pump. Wilden offers the widest variety of elastomer
options in the industry to satisfy temperature, chemical
compatibility, abrasion resistance and flex concerns.
The suction pipe size should be at least the equivalent or
larger than the diameter size of the suction inlet on your
Wilden pump. The suction hose must be non-collapsible,
reinforced type as these pumps are capable of pulling a high
vacuum. Discharge piping should also be the equivalent
or larger than the diameter of the pump discharge which
will help reduce friction losses. It is critical that all fittings
and connections are airtight or a reduction or loss of pump
suction capability will result.
INSTALLATION: Months of careful planning, study,
and selection efforts can result in unsatisfactory pump
performance if installation details are left to chance.
Premature failure and long term dissatisfaction can be
avoided if reasonable care is exercised throughout the
installation process.
LOCATION: Noise, safety, and other logistical factors usually
dictate where equipment will be situated on the production
floor. Multiple installations with conflicting requirements
can result in congestion of utility areas, leaving few choices
for additional pumps.
Within the framework of these and other existing conditions,
every pump should be located in such a way that six key
factors are balanced against each other to maximum
advantage.
ACCESS: First of all, the location should be accessible. If
it’s easy to reach the pump, maintenance personnel will
have an easier time carrying out routine inspections and
adjustments. Should major repairs become necessary, ease
of access can play a key role in speeding the repair process
and reducing total downtime.
AIR SUPPLY: Every pump location should have an air line
large enough to supply the volume of air necessary to
achieve the desired pumping rate. Use air pressure up to
a maximum of 8.6 bar (125 psig) depending on pumping
requirements.
For best results, the pumps should use a 5µ (micron) air
filter, needle valve and regulator. The use of an air filter
before the pump will ensure that the majority of any pipeline
contaminants will be eliminated.
SOLENOID OPERATION: When operation is controlled by a
solenoid valve in the air line, three-way valves should be
used. This valve allows trapped air between the valve and
the pump to bleed off which improves pump performance.
Pumping volume can be estimated by counting the number
of strokes per minute and then multiplying the figure by the
displacement per stroke.
MUFFLER: Sound levels are reduced below OSHA
specifications using the standard Wilden muffler. Other
mufflers can be used to further reduce sound levels, but
they usually reduce pump performance.
ELEVATION: Selecting a site that is well within the pump’s
dynamic lift capability will assure that loss-of-prime issues will
be eliminated. In addition, pump efficiency can be adversely
affected if proper attention is not given to site location.
PIPING: Final determination of the pump site should not be
made until the piping challenges of each possible location
have been evaluated. The impact of current and future
installations should be considered ahead of time to make
sure that inadvertent restrictions are not created for any
remaining sites.
The best choice possible will be a site involving the shortest
and straightest hook-up of suction and discharge piping.
Unnecessary elbows, bends, and fittings should be avoided.
Pipe sizes should be selected to keep friction losses within
practical limits.All piping should be supported independently
of the pump. In addition, the piping should be aligned to
avoid placing stress on the pump fittings.
Flexible hose can be installed to aid in absorbing the forces
created by the natural reciprocating action of the pump. If the
pump is to be bolted down to a solid location, a mounting
pad placed between the pump and the foundation will assist
in minimizing pump vibration. Flexible connections between
the pump and rigid piping will also assist in minimizing
pump vibration. If quick-closing valves are installed at any
point in the discharge system, or if pulsation within a system
becomes a problem, a surge suppressor (SD Equalizer®)
should be installed to protect the pump, piping and gauges
from surges and water hammer.
If the pump is to be used in a self-priming application, make
sure that all connections are airtight and that the suction lift is
within the model’s ability. Note: Materials of construction and
elastomer material have an effect on suction lift parameters.
Please refer to the performance section for specifics.
When pumps are installed in applications involving flooded
suction or suction head pressures, a gate valve should be
installed in the suction line to permit closing of the line for
pump service.
Pumps in service with a positive suction head are most efficient
when inlet pressure is limited to 0.5–0.7 bar (7–10 psig).
Premature diaphragm failure may occur if positive suction
is 0.7 bar (10 psig) and higher.
SUBMERSIBLE APPLICATIONS: Pro-Flo V™ pumps can be
used for submersible applications, when using the Pro-Flo
V™ submersible option. Turbo-Flo™ pumps can also be
used for submersible applications.
NOTE: Pro-Flo®and Accu-Flo™ pumps are not submersible.
ALL WILDEN PUMPS ARE CAPABLE OF PASSING SOLIDS.
A STRAINER SHOULD BE USED ON THE PUMP INTAKE TO
ENSURE THAT THE PUMP'S RATED SOLIDS CAPACITY IS
NOT EXCEEDED.
CAUTION: DO NOT EXCEED 8.6 BAR (125 PSIG) AIR
SUPPLY PRESSURE.