DuraComm WM-10GMT-48 Specification sheet

1
of 3
July 17, 2014
WM-10GMT-48
48 Volt Wall Mount GMT Fuse Panel
Owners Guide
(These instructions are intended for use by a technician familiar with electronic products)
•Single Bus 60Amps Max
•Up to 10 fuses
•Re /Green LED lights that in icate power an alarm activity
•Form C Relay contacts are isolate for remote fuse fail
in ication
•15 Amps max per position on output screws
•For use with 48 volt system
•3 year warranty
DESCRIPTION
The WM-10GMT-48 is a Wall Mount 60 Amp 48 VDC power distribution panel that provides up to 10 load circuits protected by
individual GMT series fuses (fuses not included). Each circuit can be fused up to 15 Amps, with a total 10-circuit load of 60 Amps
maximum. Heavy duty DC input connectors provide strong ¼ inch studs to accept up to 60 amps at 48 VDC from a single power
supply. All inputs and outputs are isolated from the frame for use in positive ground, negative ground, or floating applications. Fuses
and LED status indicators, input, output, and alarm connections are all on the front of the unit. One green LED is provided to indicate
power supply status for a bank of ten load circuits. When any fuse fails, a red LED is turned on to indicate the condition, and allow
technicians to quickly find the WM-10GMT with the failed fuse. Form C relay contacts, which are isolated from the frame and power
circuits, indicate when there is a fuse failure by providing normally open and normally closed contacts to activate remote alarm or
monitoring systems. These contacts are available via a barrier strip. Additional DuraComm services are available to customize the WM-
10GMT series distribution panels to your specifications.
SPECIFICATIONS
Input Voltage .............................................................................................................................................................................. 40-60 VDC
Input Current .......................................................................................................................................................................... 60 Amps Max
Output Amperage .......................................................................................................................... 15 Amps Max per Position, 10 positions
Size ..................................................................................................................................................................................3” H x 8” W x 5” D
Weight ................................................................................................................................................................................................. 1.6 lb
INSTALLATION WARNING
The individual user should take care to determine, prior to use or installation, whether this device is suitable, adequate or safe for the
use intended. Since individual applications are subject to great variation, DuraComm makes no representation or warranty as to the
merchantability, suitability or fitness of these units for any specific application.
DO NOT block any of the cooling vents on the sides and always allow adequate ventilation by not installing the unit inside tightly closed
spaces. Physical mounting position is not critical but the cooling vents must not be blocked.
Connect the Power Supply Positive to the red terminal labeled, “Input Positive (+)”.
Connect the Power Supply Negative to the black terminal labeled, “Input Negative (-)”.
Connect your Load to the Screw Terminals (1~ 10), Positive (+) on Upper Terminals, Negative (-) to Lower Terminals.
This completes the installation. Failures require investigation as to cause and/or repair of the unit.
THERE ARE NO USER SERVICEABLE PARTS INSIDE. SERVICE AND REPAIR MUST BE REFERRED TO QUALIFIED
FACTORY PERSONNEL

APPLICATIONS
•Inputs and
outputs are isolated from frame for use in + or
•
Has isolated remote relay contacts for fuse alarms (form C)
•Green LED for DC power on indication
•Red LED for fuse alarm indication
CONDUCTOR PRETREATMENT
All kinds
of copper conductors can be clamped without treatment. DO NOT solder tin stranded conductors. The solder yields and
fractures under high pressure. The result is increased contact resistance and excessive temperature rise. Additionally, corro
been o
bserved due to the fluxes. Notch fractures at the transition from the rigid tinned part to the flexible conductors are also p
Ferrules can be used as a protection when wiring stranded conductors. Copper ferrules prevent the current transfer from be
influenced by dissimilar metals and remove the risk of corrosion. Always use the correct tool to crimp the ferrule.
RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY
(Insulated Wire,
Current Level in Amperes
<7 AMPERES
14 AMPERES
20 AMPERES
30 AMPERES
40 AMPERES
50 AMPERES
70 AMPERES
100 AMPERES
2 of 3
outputs are isolated from frame for use in + or
– frame grounding situations.
Has isolated remote relay contacts for fuse alarms (form C)
of copper conductors can be clamped without treatment. DO NOT solder tin stranded conductors. The solder yields and
fractures under high pressure. The result is increased contact resistance and excessive temperature rise. Additionally, corro
bserved due to the fluxes. Notch fractures at the transition from the rigid tinned part to the flexible conductors are also p
Ferrules can be used as a protection when wiring stranded conductors. Copper ferrules prevent the current transfer from be
influenced by dissimilar metals and remove the risk of corrosion. Always use the correct tool to crimp the ferrule.
RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY
(Insulated Wire,
Single Conductor in free air)
Current Level in Amperes
<7 AMPERES
Wire Size
20 AWG Up to 5 feet
18 AWG Up to 10 feet
14 AMPERES
18 AWG Up to 5 feet
16 AWG Up to 10 feet
20 AMPERES
16 AWG Up to 5 feet
14 AWG Up to 10 feet
30 AMPERES
14 AWG Up to 5 feet
12 AWG Up to 10 feet
40 AMPERES
12 AWG Up to 5 feet
10 AWG Up to 10 feet
50 AMPERES
10 AWG Up to 5 feet
8 AWG Up to 10 feet
70 AMPERES
8 AWG Up to 5 feet
6 AWG Up to 10 feet
100 AMPERES
6 AWG Up to 5 feet
4 AWG Up to 10 feet
July 17, 2014
of copper conductors can be clamped without treatment. DO NOT solder tin stranded conductors. The solder yields and
fractures under high pressure. The result is increased contact resistance and excessive temperature rise. Additionally, corro
sion has
bserved due to the fluxes. Notch fractures at the transition from the rigid tinned part to the flexible conductors are also p
ossible.
Ferrules can be used as a protection when wiring stranded conductors. Copper ferrules prevent the current transfer from be
ing
influenced by dissimilar metals and remove the risk of corrosion. Always use the correct tool to crimp the ferrule.

3
of 3
July 17, 2014
LIMITED WARRANTY
DuraComm warrants to the initial end user, each power supply manufactured by DuraComm to be free from defects in
material and workmanship, when in normal use and service for a period of three years from the date of purchase, from an
authorized DuraComm dealer.
Should a product manufactured by DuraComm fail or malfunction due to manufacturin defect, or faulty component,
DuraComm, at its option, will repair or replace the faulty product or parts thereof, which, after examination by
DuraComm, prove to be defective or not operational accordin to specifications in effect at the time of sale to the initial
end user. The product that is replaced or repaired under the provisions of this warranty, will be warranted for the
remainder of the ori inal warranty period, only, and will not extend into a new three year warranty period.
The limited warranty does not extend to any DuraComm product which has been subject to misuse, accidental dama e,
ne lect, incorrect wirin not associated with manufacture, improper char in volta es, or any product which has had the
serial number removed, altered, defaced, or chan ed in any way.
DuraComm reserves the ri ht to chan e, alter, or improve the specifications of its products at any time, and by so doin ,
incurs no obli ation to install or retrofit any such chan es or improvements in or on products manufactured prior to
inclusion of such chan es.
DuraComm requires any product needin in or out of warranty service to be returned to DuraComm. All requests for
warranty service must be accompanied by proof of purchase, such as bill of sale with purchase date identified.
DuraComm is not responsible for any expenses or payments incurred for the removal of the product from its place of use,
transportation or shippin expenses to the place of repair, or return expenses of a repaired or replacement product to its
place of use.
The implied warranties which the law imposes on the sale of this product are expressly LIMITED, in duration, to the three
(3) year time period specified herein. DuraComm will not be liable for dama es, consequential or otherwise, resultin from
the use and operation of this product, or from the breach of this LIMITED WARRANTY.
Some states do not allow limitations on the duration of the implied warranty or exclusions or limitations of incidental or
consequential dama es, so said limitations or exclusions may not apply to you. This warranty ives you specific le al
ri hts which vary from state to state.
This warranty is iven in lieu of all other warranties, whether expressed, implied, or by law. All other warranties,
includin WITHOUT LIMITATION, warranties of merchantability and fitness or suitability for a particular purpose, are
specifically excluded. DuraComm reserves the ri ht to chan e or modify its warranty and service pro rams without prior
notice.
DuraComm
®
Corporation
6655 Troost Avenue
Kansas City, MO 64131
Phone (816) 472-5544 Fax (816) 472-0959
www.duracomm.com
Table of contents
Other DuraComm Media Converter manuals
Popular Media Converter manuals by other brands

evertz
evertz 7700 Series manual

Delta Electronics
Delta Electronics Delphi Series L48DB Specification sheet

Datalogic
Datalogic Profibus AMT58 13x12 PB Series instruction manual

GOLD LABEL
GOLD LABEL GRAND ANIMATED CONCERTINA manual

B&B Electronics
B&B Electronics PESV1A manual

SIIG
SIIG CE-H23G11-S1 Quick start guides