Eaton SONIX Io User manual

SONIXTM Io
Input/Output Unit
SonixTM lo Technical Manual

2
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
Disclaimer of warranties and limitation of liability
The information, recommendations, descriptions and safety notations in this document are based on Eaton
Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is
required, an Eaton sales
ofce should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined
in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.
THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING
WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE
SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES
THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR
MODIFY ANY CONTRACT BETWEEN THE PARTIES.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability
or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not
limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional
expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations and descriptions contained herein. The information contained in
this manual is subject to change without notice.

3
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
Glossary
Abbreviation Meaning
PA/GA Public Address and General Alarm
Sonix Sonix PA/GA System
A&B Duplicated PA/GA system architecture
N+1 Hot spare PA/GA system architecture
AB+ Sonix improved redundancy architecture
Hmi Human interface
BGM Background music
Tick-tone Short burst of tone repeated every few seconds, used to check the output of connected loudspeakers
Sense Test Periodic test carried by Sonix amplier to check integrity of 100 V line
100 V line High voltage loudspeaker connection line at nominal 100 V ac
MCB Miniature Circuit Breaker
RCBO Residual current circuit breaker with overcurrent protection
Unit ID/Number Unique identier assigned to each of Sonix module, used to identify it to the 2Mx and SAS.
Priority Number assigned to a Sonix audio source to facilitate system usage conict resolution, 31 (highest) to 1 (lowest)
PTT Push to talk
FAT Factory Acceptance Test
SAT Site Acceptance Test
Larson’s Effect When a microphone is acoustically coupled to the loudspeaker and generates feedback
2Mx Sonix 2Mx Central controller
Amp / 350-d Sonix 350 W Power Amplier with 100 V line output
Eol1 Sonix Remote End of Line unit
Eol8 Sonix Amplier to 100 V line interface unit (8 channel)
SP AD Sonix Intelligent loudspeaker monitoring unit
Hmi-Br Sonix intrinsically safe barrier (ATEX/IECEx) for connecting Hmi-5 in explosive atmospheres
Hmi-Mute Sonix 100V loudspeaker mute (Ex/SA)
Hmi-26 Sonix Human Interface access panel
Hmi-5 Sonix Small Human Interface access panel
Io Sonix Input / Output unit
Ms12 Sonix 12-message digital message store
Pbx Sonix Private branch exchange interface unit
Pm10 Sonix Power Management unit
Vw2 Sonix Beacon control and monitoring unit (2 channel)
SAS Sonix Administration Software
Amp Bus A 2Mx bus, used to communicate with and control Sonix Amplier units
HMI Bus A 2Mx bus, used to communicate with and control Sonix Hmi units
I/O Bus A 2Mx bus, used to communicate with and control Sonix input/output devices: IG, Io and Ms12
Beacon Bus A 2Mx bus, used to communicate with and control Sonix Vw2 units
Power Bus A 2Mx bus, used to communicate with and control Sonix Pm10 units
Global Bus A 2Mx bus, used to communicate with SAS application
Sync A 2Mx bus used to communicate with the second 2Mx unit when PA/GA system is congured as A&B, AB+ or N+1
system

4
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
1. CONTENTS
2 BEFORE YOU BEGIN ....................................................................6
2.1 Packaging ................................................................................6
2.2 Electrostatic discharge ......................................................................6
2.3 Safe working practice.......................................................................6
2.4 In the box ................................................................................6
2.5 Required tools .............................................................................6
3 PRODUCT OVERVIEW...................................................................6
3.1 Product description ........................................................................6
3.2 Key features ..............................................................................6
3.3 Connectors and indicators ...................................................................7
3.3.1 Weight and dimensions.................................................................7
3.3.2 Power and utility ......................................................................7
4 INSTALLATION AND CONNECTIVITY ......................................................8
4.1 Physical installation ........................................................................8
4.2 DC Power ................................................................................8
4.3 Earth connection ..........................................................................8
4.4 Io Bus connections.........................................................................8
4.5 Input connections..........................................................................9
4.5.1 Volt-free or 5-12V driven ................................................................9
4.5.2 Connecting to sources greater than 12 V ..................................................10
4.5.3 Polarity.............................................................................10
4.6 Output connections .......................................................................10
4.6.1 Extended voltage or duplicate output support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
4.6.2 Polarity.............................................................................10
5 AVAILABLE FEATURES .................................................................11
5.1 Alarm activation and Acknowledge ...........................................................11
5.1.1 Activation ...........................................................................11
5.1.2 Acknowledge ........................................................................11
5.1.3 Zoning and Zoned alarms ..............................................................11
5.1.4 Alarm Inhibit.........................................................................11
5.2 Audio input .............................................................................11
5.2.1 Priority .............................................................................11
5.2.2 Zoning .............................................................................11
5.2.3 Routine chime .......................................................................11
5.2.4 Broadcasting as Emergency speech ......................................................12
5.2.4.1 Important Message input.............................................................12
5.2.5 Emergency speech chime ..............................................................12
5.2.6 Background Music....................................................................12
5.2.7 Audio monitoring and timeout...........................................................12
5.3 Audio Output ............................................................................12
5.4 Other PA/GA system status outputs ..........................................................13
5.4.1 Fault outputs ........................................................................13
5.4.2 Entertainment and Auxiliary Mute .......................................................13
5.4.3 System Busy ........................................................................13
5.5 Other PA/GA system control inputs...........................................................13
5.5.1 Alarm Cancel ........................................................................13

5
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
LIST OF TABLES
TABLE 1 - SONIX IO FEATURES .............................................................7
TABLE 2 - IO BUS DESCRIPTION ............................................................8
TABLE 3 - AVAILABLE ROUTINE SPEECH CHIMES.............................................12
TABLE 4 - AVAILABLE EMERGENCY SPEECH CHIMES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12
5.5.2 Alarm Attenuate .....................................................................13
5.6 Fault monitoring and reporting ...............................................................13
6 CONFIGURATION .....................................................................14
6.1 Ping-set ................................................................................14
6.2 Programming the unit .....................................................................14
7 CUSTOMISATION .....................................................................14
7.1 Firmware customisation ....................................................................14
8 MAINTENANCE .......................................................................14
LIST OF FIGURES
FIGURE 1 - SONIX IO UNIT ................................................................7
FIGURE 2 - DC POWER CONNECTIONS ......................................................8
FIGURE 3 - SINGLE IO BUS CONNECTION....................................................9
FIGURE 4 - MULTIPLE IO BUS CONNECTIONS ................................................9
FIGURE 5 - VOLT-FREE VS DRIVEN INPUT CONFIGURATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
FIGURE 6 - ISOLATED INPUT FOR > 12 V SOURCE ............................................10
FIGURE 7 - DUPLICATING OUTPUTS .......................................................10
FIGURE 8 - OUTPUT POLARITY JUMPER CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
FIGURE 9 - PBX INPUT CONNECTIONS .....................................................11

6
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
2 Before you begin
2.1 Packaging
In the interest of preserving the environment, Eaton aims
to use recycled packaging wherever practical. Due to the
physical nature of our products, we provide adequate
packaging to protect the goods during transit. Please
ensure that once unpacked, checked and installed that
all packaging is disposed / recycled in a responsible
manner.
2.2 Electrostatic discharge
The Sonix PA/GA system is largely constructed from
electronic printed circuit boards. These printed circuit
boards are sensitive to static electricity; ESD discharge
on to any of the Eaton products could cause permanent
and irreparable damage to the equipment. All such
PCB’s are shipped to you in ESD protective bags for
transit. Prior to opening the transit bags please ensure
that you are wearing either an ESD, earthed wrist strap
or other suitable means of protection.
2.3 Safe working practice
Whilst working on or within the Sonix PA/GA system it
is our prime interest that you remain safe throughout.
During this work you may be exposed to potentially
hazardous voltages, currents, confined spaces and
potentially hazardous industrial environments. Prior to
undertaking any work please ensure relevant permits
and regulations are adhered to.
2.4 In the box
• 1 x Sonix Io unit
• 1 x Technical Manual
• 2.5 Required tools
To install and commission this part you will need the
following tools.
• Flat-blade terminal screw driver
• Small Flat-blade terminal screw driver up to 2.5 mm
• Multi-meter
3 Product overview
3.1 Product description
The Sonix Io unit is designed to act as an interface
between external systems and the Sonix PA/GA system.
It can be used to initiate Alarms and affect system
state of the PA/GA system, as well as act as an audio
gateway.
It has a number of configurable inputs and outputs
intended to be interfaced to third-party external systems.
3.2 Key features
• 6 Alarm initiate inputs
• 6 associated alarm acknowledge outputs
• 2 Audio + Key-line inputs
• 1 Audio + Key-line output
• 2 Fault outputs
• 3 Mute outputs
• Ships Whistle output with alarm cadence control
• Miscellaneous
• Alarm Cancel
• Alarm Attenuate
• Alarm auto-initiate inhibit
• Important Message
• Audio monitoring

7
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
3.3 Connectors and indicators
Figure 1 - Sonix Io Unit
Item Description
1Sonix Io bus connections
248 V dc power
3Programming header
4Functional Earth
5External Alarm initiate inputs
6Alarm Acknowledge outputs
7Program (minor) fault output
8Global (major) fault output
9Entertainment Mute output
10 Pbx Audio + Keyline Input
11 Aux Audio + Keyline Input
12 Auxiliary Audio + Keyline Output
13 Auxiliary Mute output
14 Ships Whistle output
15 System Busy output
16 Important Message input
17 Alarm Cancel input
18 Alarm Attenuate input
19 Auto Alarm Initiate inhibit input
Table 1 - Sonix Io features
3.3.1 Weight and dimensions
Weight: 700g
Dimensions (H x W): 305 mm x 118 mm
3.3.2 Power and utility
Voltage: 48 V dc, recommended taken from Sonix
Pm10 unit
Current: 100 mA max consumption
J7
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
Alarm 1 Ack
Alarm 2 Ack
Alarm 3 Ack
Alarm 4 Ack
Alarm 5 Ack
Alarm 6 Ack
Alarm 1 Initiate
Alarm 2 Initiate
Alarm 3 Initiate
Alarm 4 Initiate
Alarm 5 Initiate
Alarm 6 Initiate
Program Fault
Global Fault
Entertainment Mute
Pbx Input
Screen
Auxiliary Input
Auxiliary Output
Auxiliary Mute
Ship’s Whistle
System Busy
Important Message
Alarm Cancel
Alarm Attenuate
Alarm Inhibit
SCREEN

8
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
4 Installation and connectivity
4.1 Physical installation
The Sonix Io is a DIN rail mount unit, intended to be
mounted inside the PA/GA cabinet on most standard EN
60715 rails:
• EN 50022 (Top hat, TS35, TS35D, type “O” or type
“Ω”) 35 x 7.5/15 mm rail,
• EN 50045 (mini Top hat or TS15) 15 x 5.5 mm rail,
• EN 50035 (type G or TS32) 32 x 15 mm.
Unit is simply clipped onto the appropriate rail, always
check that all sets of fixings have engaged correctly on
the rail.
ote:N Care must be taken to ensure that the product is correctly sup-
ported within the cabinet. Always check that both sets of fixings have
fully engaged on the rail and the unit is secured on both ends, with no
possibility of it to slide along the din rail.
4.2 DC Power
The Sonix Io is powered externally by 48 V dc. Eaton
recommends the supply voltage to be taken from
dedicated dc power output connection of the Sonix
Pm10 (see Pm10 Product Manual for connection details).
Green LED (D1) visible next to the power supply input
terminals illuminates to indicate that unit is powered up.
Figure 2 - DC Power connections
ote:N As these cables are power feeds, they should be – where pos-
sible – routed within the PA/GA system in a separate way to avoid
contact with signal or audio cables and reduce the possibility of inter-
ference.
Warning: Observe the polarity of incoming
power supply cables.
• Solid: 4.0 mm2
• Stranded: 2.5 mm2including sleeved or
non-sleeved ferrule
4.3 Earth connection
The Sonix Io unit has an M4 stud for connection to
Earth. The Earth connection is used as a functional
reference for the unit screening only.
It is strongly recommended that any connection be
made to Telecoms Earth only.
Cable sizing is as follows:
Recommended 4.0 mm2
Minimum 2.5 mm2
4.4 Io Bus connections
The Sonix Io connects to the Sonix PA/GA system via
the Io bus communication channel utilising duplicated
CAT6A cables. This connection carries bi-directional
audio and serial data using RS-485 standard. The Sonix
PA/GA convention is that the Io bus uses BLUE coloured
CAT6A cables which connect to the colour coordinated
Io Bus sockets on the rear of the 2Mx unit.
Bus Name Colour Connected to Data type
IO Bus Blue Io, Ms12, & PBx
units
Transmit
Unit control,
status data +
Active system
Audio
Receives System control
and status data
Table 2 - IO Bus description
How the unit is connected in the system depends on the
number of units on the Io Bus.
The 2Mx Io bus connections are always top-top and
bottom-bottom, i.e. top port of the Sonix Io connects to
the top port of the Io Bus on the 2Mx. Whereas any inter
unit Io bus connections are always top-bottom.
For single unit the return link (bottom port of Io)
connects to the bottom port of the Io Bus on the 2Mx,
as shown below.
Amp Bus
HMi Bus
HMi Bus
I/O Bus
COMPLIANT
Sonix 2Mx Unit
J7
Sonix Io Unit
Alarm 1 Initiate
Alarm 2 Initiate
Alarm 3 Initiate
Alarm 4 Initiate
Alarm 5 Initiate
Alarm 6 Initiate
Alarm 1 Ack
J7
+48V
0V
D1

9
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
Amp Bus
HMi Bus
HMi Bus
I/O Bus
COMPLIANT
Sonix 2Mx Unit
J7
Sonix Io Unit
Alarm 1 Initiate
Alarm 2 Initiate
Alarm 3 Initiate
Alarm 4 Initiate
Alarm 5 Initiate
Alarm 6 Initiate
Alarm 1 Ack
J7
+48V
0V
D1
Figure 3 - Single Io bus connection
Where multiple Io bus units are connected, the bottom
connector of the rst Io bus unit connects to the top on the
next unit, until returning to the 2Mx, as shown below.
Amp Bus
HMi Bus
HMi Bus
I/O Bus
COMPLIANT
Sonix 2Mx Unit
Sonix Pbx Unit
I/O Bus A
I/O Bus B
Sonix Ms12 Unit
I/O Bus A
I/O Bus B
B SIDE O/P
A1...
GLOBAL ADDRESS
LINE IN
USB...
J7
Sonix Io Unit
Alarm 1 Initiate
Alarm 2 Initiate
Alarm 3 Initiate
Alarm 4 Initiate
Alarm 5 Initiate
Alarm 6 Initiate
Alarm 1 Ack
COMPLIANT
COMPLIANT
c
b
a
c
b
a
Volt-free
Driven
a
b
Normally - Closed
a
b
Normally - Open
Figure 4 - Multiple Io Bus connections
ote:N As shown in Figure 4 - Multiple Io Bus connections, the order of
connections is recommended to be Pbx, Ms12 then Io.
ote:N It is recommended that within the PA/GA cabinet the connecting
cables do not exceed 25 meters in length, regardless of the system
configuration.
4.5 Input connections
The Sonix Io unit has several inputs that can be
configured to be volt-free or driven. Each input is
independent and can be configured as required. See
section 5 and SAS manual for more details on available
configuration options.
4.5.1 Volt-free or 5-12V driven
To select between Volt-free and Driven input
configurations requires a change of jumper links
on the PCB. This change is defined on each input
independently.
Figure 5 - Volt-free vs driven input congurations
Amp Bus
HMi Bus
HMi Bus
I/O Bus
COMPLIANT
Sonix 2Mx Unit
Sonix Pbx Unit
I/O Bus A
I/O Bus B
Sonix Ms12 Unit
I/O Bus A
I/O Bus B
B SIDE O/P
A1...
GLOBAL ADDRESS
LINE IN
USB...
J7
Sonix Io Unit
Alarm 1 Initiate
Alarm 2 Initiate
Alarm 3 Initiate
Alarm 4 Initiate
Alarm 5 Initiate
Alarm 6 Initiate
Alarm 1 Ack
COMPLIANT
COMPLIANT
c
b
a
c
b
a
Volt-free
Driven
a
b
Normally - Closed
a
b
Normally - Open

10
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
ote:N Inputs are not voltage polarity conscious when in driven mode
and can be wired either way around.
ote:N Volt-free mode supplies a low current from a local 5V supply to
sense the contact position. This is common to all inputs and care must
be taken to avoid swapping the common on non-isolated systems.
Warning: Do not exceed 30 V ac or 60 V dc input
potential, risk of shock.
The maximum input voltage when Driven mode is
selected is 12 V dc or ac. This is due to the current
limiting resistor in each input circuit reaching its
maximum power threshold. If higher voltages are a
system requirement then a relay should be used to
isolate the inputs from the source.
Warning: Do not exceed 12 V dc/ac input drive
or damage might occur to unit.
4.5.2 Connecting to sources greater than 12 V
A relay should be used to isolate the input from any
sources that are greater than 12 V.
Figure 6 - Isolated input for > 12 V source
ote:N The Sonix Io input should be configured as volt-free when using
an external isolating relay.
4.5.3 Polarity
Polarity of the inputs are congured by SAS and can be
either normally open or normally closed. The unit will
ignore its inputs until after the conguration has been
loaded on a cold start to avoid incorrect latch up. This
takes approximately 7 seconds.
4.6 Output connections
The Sonix Io output ports are volt-free relay contacts
with hardware selectable normally open or normally
closed. The relays controlling the outputs are small low
power variants and are only rated for 1A at 24 V dc.
Warning: Do not exceed 30 V ac or 24 V dc on
the relay contacts.
4.6.1 Extended voltage or duplicate output support
For controlling voltages in excess of 24 V dc / 30 V
ac a correctly rated external relay should be used to
provide the isolation. Also, if multiple independent
outputs are required by the system design, then
isolation should be maintained by using an external
relay with multiple contacts.
Figure 7 - Duplicating outputs
4.6.2 Polarity
The polarity of the outputs is set by a 2-position
jumper link for each output. These can be found
adjacent to each output on the PCB.
Figure 8 - Output polarity jumper conguration
Important
Message
Alarm
Cancel
Alarm
Attenuate
Alarm
Inhibit
System
Busy
Input > 12 V
Entertainment
Mute
Pbx
Input
SCREEN
Global
Fault
Line-level
Audio
Key-Line
Global
Fault
Entertainment
Mute
Pbx
Input
Program
Fault
24V dc
Output 1
Output 2
Output 3
Amp Bus
HMi Bus
HMi Bus
I/O Bus
COMPLIANT
Sonix 2Mx Unit
Sonix Pbx Unit
I/O Bus A
I/O Bus B
Sonix Ms12 Unit
I/O Bus A
I/O Bus B
B SIDE O/P
A1...
GLOBAL ADDRESS
LINE IN
USB...
J7
Sonix Io Unit
Alarm 1 Initiate
Alarm 2 Initiate
Alarm 3 Initiate
Alarm 4 Initiate
Alarm 5 Initiate
Alarm 6 Initiate
Alarm 1 Ack
COMPLIANT
COMPLIANT
c
b
a
c
b
a
Volt-free
Driven
a
b
Normally - Closed
a
b
Normally - Open

11
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
5 Available features
5.1 Alarm activation and Acknowledge
The Sonix Io unit has 6 pairs of alarm activation input
and alarm acknowledge output. Each pair is configured
to be associated with an alarm(s) set/trigger on the PA/
GA system.
ote:N Most of the input and outputs on the Sonix Io are configured in
software, please see the SAS manual for more details.
5.1.1 Activation
The alarm initiation inputs 1 – 6 are independent of each
other and can be configured to activate one or more
alarms out of the twelve alarms available. Alarms 6 to 12
are not usually used but can be utilised as part a system
customisation.
Multiple inputs can be configured to activate the same
alarm, this allows for isolated connections to multiple
independent systems. This feature can also be used to
generate additional independent acknowledge outputs
where there is un-used capacity on the unit.
ote:N Alarm initiate inputs can be associated with multiple PA/GA
Alarms and will activate all associated outputs when initiated.
5.1.2 Acknowledge
The acknowledge output will activate on any associated
PA/GA system alarms being active. For example, if the
input was configured to be associated with alarms 1, 2
and 3, then the acknowledge output will activate when
either alarms 1, 2 or 3 activate.
ote:N It is not required to utilise the Alarm activation input in order to
generate an alarm acknowledge output, but they are configured as a
pair and not independently.
5.1.3 Zoning and Zoned alarms
Currently Zoning for the Alarms is fixed inside the Sonix
2Mx central controller firmware. By default it is set to
all zones. Customisation is available on request, please
contact your local Eaton representative.
ote:N Specific zoning requires custom 2Mx firmware, available on
request.
ote:N Zoned Alarms are possible on the Sonix PA/GA system but are
considered as ETO.
5.1.4 Alarm Inhibit
The alarm inhibit input is used to prevent alarm
activation of the Sonix Io Alarm inputs. While the inhibit
is active the alarm inputs are ignored, its intended use
is to allow for the maintenance of third-party systems or
cabling without needing to modify the PA/GA system.
ote:N Eaton recommends that this input be used with a key switch to
prevent accidental activation.
Warning: Activating the Alarm Inhibit will
prevent ALL alarms from being remotely
activated via the Sonix Io unit but manual
initiation via access panels is still possible.
5.2 Audio input
The Sonix Io has 2 audio inputs: Pbx and Aux (-iliary).
They are comprised of a transformer isolated line-
level audio input and associated key-line for activation.
Activating the key-line will cause the Io unit to request
access to the PA/GA system to broadcast the available
audio on Io unit input. Once the PA/GA system has
given access to the Io unit, it will begin passing audio
through.
Figure 9 - Pbx input connections
5.2.1 Priority
The priority of these audio inputs into the PA/GA system
is defined by the priority configuration option set on the
Sonix Io unit. If both inputs are active, then the Pbx input
will be given higher priority over the Aux input.
ote:N The Pbx input has a higher priority than the Aux input and will
override the Aux input.
5.2.2 Zoning
Currently zoning for the two inputs is fixed inside the
Sonix 2Mx central controller firmware. Customisation
is available on request, please contact your local Eaton
representative.
ote:N Zoning requires custom 2Mx firmware, available on request.
5.2.3 Routine chime
The Sonix Io can be configured to play one of three
different chimes before each routine speech broadcast,
the chimes are referred to as single, double and triple
bong. Selection of a chime creates a delay before
routing the incoming audio to the PA/GA system whilst
the chime plays.
Important
Message
Alarm
Cancel
Alarm
Attenuate
Alarm
Inhibit
System
Busy
Input > 12 V
Entertainment
Mute
Pbx
Input
SCREEN
Global
Fault
Line-level
Audio
Key-Line

12
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
Warning: Chime will override the rst few
seconds of the incoming audio stream with no
method to buffer it, causing the audio to be lost.
Chime Name Sound Notes
Single Bong 660Hz decaying gong over
~4seconds
Double Bong 660Hz then 550Hz decaying
gongs over ~5.5seconds The decaying gongs
have the new gong
superimposed over the
top after ~1.1s
Triple Bong
660Hz then 550Hz then
400Hz decaying gongs over
~7seconds
None No chime
No chime is generated,
voice is routed to the
system without delay
Table 3 - Available Routine Speech Chimes
All chime options for routine speech broadcasts can be
set in conguration, see SAS Product Manual for details.
5.2.4 Broadcasting as Emergency speech
To broadcast any incoming audio as Emergency Speech
the Important message input needs to be activated rst.
If the Important message input is active, then the Sonix
Io will ag the broadcast as Emergency speech and it
will be given higher priority on the PA/GA system.
5.2.4.1 Important Message input
The important message input is a latching input with
timeout after 30 seconds of no active key-line input.
Alarm cancel also resets the input ag.
ote:N The Important Message input is a latching input, a brief activation
will cause it to hold active until the timeout occurs or PA/GA system
alarm cancel in activated.
5.2.5 Emergency speech chime
The Sonix Io can be congured to play one of three
different chimes before each emergency speech
broadcast. These chimes are different to the routine
speech chimes. Selection of a chime creates a delay
between activating PTT and routing voice to the PA/GA
system while the chime plays.
Warning: As with routine, emergency chime will
override the rst few seconds of the incoming
audio stream and with no method to buffer it,
causing the audio to be lost.
Available chimes on the Io are:
Chime Name Sound Notes
Chime 1 1 kHz tone for 1second Long beep
Chime 2 1 kHz tone 400ms ON 400ms
OFF 400ms ON Double beep
Chime 3 1 kHz tone 100ms ON 100ms
OFF repeated 5 times Multiple fast beeps
None No chime
No chime is generated,
and voice is routed to the
system without delay
Table 4 - Available Emergency Speech Chimes
All chime options for emergency speech broadcasts
can be set in conguration, see SAS Product Manual for
details.
5.2.6 Background Music
The Aux input is used to deliver background music
(BGM) to the PA/GA system. This is controlled and
setup elsewhere (see 2Mx Technical Manual), but the
Aux key-line needs to be active before BGM can be
activated on the system.
ote:N Eaton suggest using a rack mounted switch to globally enable/
disable BGM.
5.2.7 Audio monitoring and timeout
Each audio input can be monitored for DTMF tones
during idle, while the key-line is not active. Also,
excessive key-line durations can be monitored as a fault
situation if congured in software.
See SAS manual for more details.
5.3 Audio Output
The Sonix Io has a single audio output, with transformer
isolated line-level audio and associated key-line.
The key-line will activate and audio will be routed out on
the following events as standard:
• 10 seconds of any alarm tone every ~ 64 seconds
• All Emergency Speech
• All Routine Speech
ote:N Customisations of the events that enable this output are avail-
able as ETO.

13
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
5.4 Other PA/GA system status outputs
The Sonix Io unit has following general outputs, driven
from the Sonix PA/GA system.
5.4.1 Fault outputs
The Sonix Io unit has 2 fault outputs, Global Fault and
Program Fault, also known as Major and Minor faults
respectively. The source of the faults is chosen by the
2Mx central controller, with the Global fault activating
on any issues with the system and the Program fault
normally restricted to a subset. These faults can be
disabled in software, see SAS manual for details.
ote:N Customisation of the fault outputs currently requires ETO firm-
ware, please contact your local Eaton representative to discuss your
requirements.
5.4.2 Entertainment and Auxiliary Mute
The Entertainment and Auxiliary mutes activate on any
broadcast that is above Routine Speech, i.e. Alarms
and Emergency Speech. It is intended to silence any
entertainment systems, such as background music,
televisions or private cinema, and allow any broadcast
messages to be clearly received.
Polarity is congured using external links, see section
4.6.2.
ote:N Entertainment Mute does not activate on routine speech.
ote:N Auxiliary mute follows the same pattern as Entertainment mute
and does not activate on routine speech.
5.4.3 System Busy
The System Busy output is activated whenever the
system is no longer idle, i.e. during Routine speech,
Alarms and Emergency speech. This includes
background music. Any testing activity like sense tests
and Ticktone (See 350-d amplier manual for more
details) are not included.
5.4.4 Ships Whistle
The Ships Whistle output is intended to be connected
to third-party equipment, typically the collision alert
warning or international maritime destress on vessels,
to allow that system to be activated when an alarm
is running. The alarm, or multiple alarms, it will be
associated with, are set as part of Sonix Io conguration.
The output can also be congured to pulse in sync with
the alarm cadence.
ote:N Cadence options only impact output when selected with inter-
rupted alarms.
Please see SAS manual for more complete conguration
details.
5.5 Other PA/GA system control inputs
The Sonix Io unit has the following control inputs into
Sonix PA/GA system.
5.5.1 Alarm Cancel
The Alarm Cancel input generates a short, approximately
2 seconds, active pulse when the input is rst activated
and will only re-trigger if the input is subsequently
cleared. This is to prevent a fault on the input from
locking the system out of generating alarms.
ote:N Holding this input active does NOT prevent alarms being acti-
vated on the Sonix Io or elsewhere after the initial request.
5.5.2 Alarm Attenuate
The Alarm Attenuate input is also an edge triggered
signal. Each new activation will cause the system to
change state between full volume alarms and attenuated
alarms. Attenuated alarms can be disabled elsewhere
in the system and the input will only have an effect if an
alarm is currently active.
ote:N Activating this input with no alarm will generate a short indicator
event on any Sonix Hmi-26 access panel connected to the system.
5.6 Fault monitoring and reporting
The Sonix Io unit has built-in fault monitoring for the
following issues:
• Temperature
• Internal audio pathways using idle DTMF monitoring
• External audio input using idle DTMF monitoring
• External audio timeout monitoring
• PA/GA system Data monitoring
• PA/GA audio pathways using idle DTMF monitoring
All faults are reported into the Sonix PA/GA system via
the 2Mx central controller and the Sonix Administration
Software (SAS).

14
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com
6 Conguration
The conguration options are detailed within the SAS
manual.
6.1 Ping-set
To ping-set a Sonix Io the following procedure needs to
be followed:
1. Connect Computer with SAS installed and working
with the system via the data connection cable.
2. Navigate to Io configuration screen.
3. Press Ping-set and enter a new Unit ID.
ote:N Unit ID’s need to be unique for all Io units on the system.
4. Once the software has sent the ping-set command
ALL Io units that receive the command will be
waiting to accept for 10 seconds.
5. Activating Alarm Cancel on the Io unit during this 10
second window will cause that local panel to accept
the new Unit ID.
6. Any Io unit which has not had Alarm Cancel pressed
during the 10 second window will discard the
command and retain their current Unit ID and
configuration.
6.2 Programming the unit
Programming the unit is usually performed during
manufacture and is not usually required in the eld.
1. Ensure 48V dc power input is available
2. Back-up configuration if required
ote:N Configuration can be corrupted during programming, re-configu-
ration after programming is recommended
3. Disconnect unit from PA/GA system
4. Isolate unit from third-party connections
5. Connect programmer to J10, carefully observe the
orientation key
6. Program unit using Eaton approved firmware
7. Verify firmware on unit
8. Power cycle unit
9. Reconnect PA/GA system and verify/update
configuration as required
10. Reconnect third-party connections
Warning: Only programme with Eaton approved
rmware.
Warning: Unit will likely activate its outputs in
random patterns during programming.
7 Customisation
The standard version of the Sonix Io unit has been
designed with mostly xed function inputs and outputs
and some limited conguration., any customisations
should be discussed with your local Eaton representative
before ordering.
7.1 Firmware customisation
Please contact your Eaton representative if the standard
operation of the Sonix system and/or Io unit is not
fullling the needs of your system.
8 Maintenance
The Io unit itself does not require any specic
maintenance but the following general maintenance
should be performed monthly:
Warning: Remove fuse / power off the unit
before proceeding!
• Check the unit for visible damage (scratches, bumps).
• Check connections and cable integrity - replace
damaged cables, tighten terminal connector’s loose
screws.
• Check unit fixing to rack
•
Notice: Do not use sharp objects, water, aggressive
cleaning agents or solvent to clean the unit.

15
Sonix Io Unit Technical Manual
SONIX IO TECHNICAL MANUAL TM366 / A June 2022 www.eaton.com

All specifications, dimensions, weights and tolerances are nominal (typical)
and Eaton reserve the right to vary all data without prior notice.
No liability is accepted for any consequence of use.
Eaton
Unit B, Sutton Parkway
Oddicroft Lane
Sutton in Ashfield
United Kingdom
NG17 5FB
T: +44 (0) 1623 444 400
www.crouse-hinds.com/hac
© 2022 Eaton
All Rights Reserved
Printed in UK
Publication
No.TM366 / A
June 2022
Eaton and SONIX™ are
registered trademarks.
All other trademarks are property
of their respective owners.
Changes to the products, to the information contained in this
document, and to prices are reserved; so are errors and omissions.
Only order confirmations and technical documentation by Eaton is
binding. Photos and pictures also do not warrant a specific layout or
functionality. Their use in whatever form is subject to prior approval
by Eaton. The same applies to Trademarks (especially Eaton, Moeller,
and Cutler-Hammer). The Terms and Conditions of Eaton apply, as
referenced on Eaton Internet pages and Eaton order confirmations.
Table of contents
Other Eaton I/O System manuals

Eaton
Eaton CBEU-02 Manual

Eaton
Eaton EASY618 RE Series Manual

Eaton
Eaton ELC-EX08NNDR User manual

Eaton
Eaton 105U-1 User manual

Eaton
Eaton AIM User manual

Eaton
Eaton xComfort CBEU-02/02 User manual

Eaton
Eaton Moeller EU5E-SWD-8DX Manual

Eaton
Eaton XN-1RS232 User manual

Eaton
Eaton ELC Series User manual

Eaton
Eaton ECIO-DN User manual
Popular I/O System manuals by other brands

CREVIS
CREVIS FnIO S Series NA-9161 quick guide

ICP DAS USA
ICP DAS USA PET-7000 Series quick start guide

ICP DAS USA
ICP DAS USA tET Series user manual

Allen-Bradley
Allen-Bradley POINT I/O 1734-OE2C installation instructions

ICPDAS
ICPDAS DIO-48 quick start guide

Crestron
Crestron DigitalMedia DMC Series installation guide